EXTENSION ANALOG OUTPUT

4.5.2Calibration of meter

(1) Outputting the same select signals from terminals AM0 and AM1 (Pr. 309 = 0 or 10)

START

Connect a DC voltmeter (or DC ammeter) across terminals AM0 (or terminal AM1) and AMC.

Use Pr. 323 (Pr. 324) to calibrate the meter when the voltage (current) input is 0.

Set "21" (reference voltage output) in Pr. 306.

Run the inverter

Use Pr. 901 to perform adjustment, then set.

END

At this time, check that the polarity is correct

If the meter needle does not point to 0 when voltage or current input is 0, use Pr. 323 AM0 0V adjustment or Pr. 324 AM1 0mA adjustment to calibrate the meter

At this time, the following analog signal is actually output and deflects the meter.

<across terminals AM0-AMC>

Maximum output voltage set previously (factory setting: 10VDC) <across terminals AM1-AMC>

Maximum output current set previously (factory setting: 20mADC)

press to set.

In Pr. 306, set the types of the signals to be output.

(Refer to page 18.)

CAUTION

1.If calibration is made without "21" (reference voltage output) set in Pr. 306, Terminals FM/AM of the inverter is calibrated. To calibrate the extension analog output, always set "21" in Pr. 306.

2.When the plug-in option used was remounted on other inverter, use Pr. 323 and Pr. 324 to calibrate again.

16

Image 21
Contents FR-A7AY Safety Instructions This section is specifically about Safety mattersInjury Prevention  Contents  Digital Output PRE-OPERATION Instructions Unpacking and Product ConfirmationPacking confirmation Front view PartsRear view Terminal layoutOutput signals SpecificationsMemo Pre-Installation Instructions Installation and WiringRemove the inverter front cover Installation ProcedureTightening Torque Cable Size Wiring30K or less 37K or more Name Setting Range Minimum Initial Refer to Number Parameter ListValue Parameter List Extension Analog Output Wiring ExampleInternal Block Diagram Terminals Terminal Symbol Terminal Name DescriptionExtension Analog Output Function Parameter List Parameter Name Setting Range Minimum Initial NumberSetting Adjustment ProcedureStart Calibration of meterExtension Analog Output Types of Monitor Increments Full-Scale Value Output signal settingWhen Pr = 0 When Pr = 10 Analog signal adjustment Pr , Pr , Pr , PrInstructions Digital Output Digital Output Digital Output Function Parameter List Name Initial Value Setting RangeSetting Output Signal ListFunction Setting FunctionRO2 Print Date Manual Number Revision Revisions