EXTENSION ANALOG OUTPUT
4.5.3Output signal setting
Set the output signals to be monitored. Set Pr. 306 to output the same signal from terminals AM0 and AM1 and Pr. 306 and Pr. 310 to output different signals. For details of signal definitions, refer to Pr. 54 and Pr. 158 of the inverter manual (applied).
Pr. 306/Pr. 310 | Types of Monitor | Increments |
| |
Setting | ||||
|
|
| ||
1 | Output frequency | 0.01Hz | Pr. 55 | |
2 | Output current | 0.01A/0.1A *2 | Pr. 56 | |
3 | Output voltage | 0.1V | 800V | |
5 | Frequency setting | 0.01Hz | Pr. 55 | |
6 | Running speed | 1(r/min) | The value converted with the Pr. 37 value from Pr. 55. | |
8 | Converter output voltage | 0.1V | 800V | |
9 *1 | Regenerative brake duty | 0.1% | Pr. 70 | |
10 | Electronic thermal relay | 0.1% | Electronic thermal relay function operation level | |
function load factor | ||||
|
|
| ||
11 | Output current peak value | 0.01A/0.1A *2 | Pr. 56 | |
12 | Converter output voltage | 0.1V | 800V | |
peak value | ||||
|
|
| ||
13 | Input power | 0.01kW/0.1kW *2 | Rated inverter power × 2 | |
14 | Output power | 0.01kW/0.1kW *2 | Rated inverter power × 2 | |
17 | Load meter | 0.1% | Pr. 56 | |
21 | Reference voltage output | | | |
24 | Motor load factor | 0.1% | 200% | |
50 | Power saving effect | Variable according to parameters | Inverter capacity | |
52 | PID set point | 0.1% | 100% | |
53 | PID process value | 0.1% | 100% |
*1 Setting can be made only for the
*2 The setting depends on capacities. (55K
18