Hitachi NB5741XD manual Basic Error Codes, Error Name Probable Causes Code

Page 10

Error Codes

The L100 series inverters will trip on over-current, over-voltage, and under-voltage to protect the inverter. The motor output turns OFF, allowing the motor to free-run to a stop. Press the Stop/Reset key to reset the inverter and clear the error.

Basic Error Codes

Error

Name

Probable Cause(s)

Code

 

 

 

 

 

 

 

 

E01

Over current event while

• Inverter output was short-circuited

at constant speed

• Motor shaft is locked

 

 

• Load is too heavy

E02

Over current event during

• A dual-voltage motor is wired

deceleration

incorrectly

 

 

Note: The L100 will over current trip

E03

Over current event during

at nominally 200% of rated current

 

acceleration

 

E04

Over current event for

• DC braking power(A_54) set too

other conditions

high

 

 

• Current transformer / noise error

 

 

 

E05

Overload protection

• Motor overload is detected by the

 

 

electronic thermal function

E07

Over voltage protection

• DC bus voltage exceeds a threshold,

 

 

due to regenerative energy from motor

E08

EEPROM error

Built-in EEPROM memory experi-

 

 

enced noise, high temperature, etc.

E09

Under-voltage error

• DC bus voltage decreased enough to

 

 

cause a control circuit fault

E11

CPU error

Built-in CPU had internal error

 

 

E22

 

 

 

 

 

E12

External trip

• [EXT] input signal detected

 

 

E13

USP (Unattended Start

• When (USP) was enabled, an error

Protection)

occurred when power was applied

 

 

while a Run signal was present

 

 

 

E14

Ground fault

• A ground fault was detected

 

between the inverter output and the

 

 

motor. This feature protects the

 

 

inverter, and does not protect humans.

 

 

 

E15

Input over-voltage

• Input voltage was higher than the

 

specified value, 60 sec. after powerup

 

 

 

 

 

E21

Inverter thermal trip

• Inverter internal temperature is

 

above the threshold

 

 

 

 

 

9

Image 10
Contents Hitachi Power Circuit Terminals Control Circuit Terminals Description Ratings and NotesRUN Basic Wiring Diagram L100Inverter Keypad Operation HitachiPage Keypad Navigation Map Powerup Test Step Description Via Keypad Via Logic TerminalsBasic Error Codes Error CodesError Name Probable Causes Code Error Trip Conditions Step DisplayRestoring Factory Default Settings Action Display Function/ParameterGroup Monitoring Functions Parameter TablesFunc Name / Description Units Code Monitor Mode Trip History Navigation MapFunc Name / Description Default Set Code Value Group Main Profile ParametersDefault Func Name / Description Value Set Code FE / -FU Group Standard FunctionsAVR enabled AVR disabled AVR enabled except during decel Group Fine-tuning Functions B12 Level of electronic thermal setting Rated Current Group Intelligent Terminal Functions Rated Current Symbol Code Input Terminal Name Intelligent Input Terminal ListingIntelligent Output Terminal Listing Analog Input ConfigurationExternal Frequency Command Input Analog Output Function Listing