Vermont Casting DVT38IN installation instructions Fresh Air Restrictor Plate

Page 22

Chateau™

FP1243a

Fig. 26 Secure termination to wall.

Vertical Through-the-Roof

Applications

Use of Restrictor Plate

for Vertical Venting Applications

The primary purpose for the vent restrictor is to regain flame height under certain venting conditions as outlined below.

NOTE: The joints of the inner pipe (flue pipe) must be taped with 550°F or higher temperature metal adhesive tape that meets the requirements of F.A.R. 25.853(a) High temperature sealant milpack or stove cement

of 550°F or higher could be used instead. The joints of The outer pipe (fresh air pipe) must be taped with 315°F or higher temperature metal adhesive tape or the use of high temperature milpack or stove cement would be applicable. When using the unitized 30°, 45° or 90° elbows, apply 1/4” bead of high temperature, 550°F or higher, sealant (milpack or stove cement) to the joint of the inner pipe (flue pipe) and the straight section as it is impossible to be taped. The outer pipe must be taped with 315°F high temperature metal adhesive tape for proper sealing.

For vertically venting either propane or natural gas units, with vertical vent heights of 12’ (3.7 m) or greater, (measured from the top of the flue collar) the restrictor plate as supplied with this unit should be used. (Fig.

27)Also, the fresh air restrictor plate could be adjusted according to your vent height. (Fig. 27) Refer to Pages 26 & 27, Figures 36 & 38 for restrictor plate installation and fresh air restrictor plate adjustment.

DVT44 - Natural or LP

12'

 

(3.7m)

Use 6���"

or Greater

DVT38 - Natural or LP

 

'X'

Use 5���"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fresh Air Restrictor Plate

XSetting

30’ to 40’

#1

20’ to 29’

#2

12’ to 19’

#3

FP1409

Fig. 27 Restrictor plate use in straight up installation.

For vertical venting configurations that include a minimum vertical rise of 12’ (3.7 m) and a maximum horizontal offset of 10’ (3 m) the 4¹⁄₂” restrictor plate supplied with this unit should be used. The fresh air restrictor plate could be adjusted to the setting #3 (DVT44IN Only). (Fig. 28) Refer to Pages 26 & 27, Figures 36 & 38 for restrictor plate installation and fresh air restrictor plate adjustment.

10' (3m) Max.

Natural or LP

Use 4���"

Flue Restrictor Plate

12'

(Refer to Page 17 and

(3.7m)

Page 22, Figure 36)

Min. Rise

 

Fresh Air Restrictor Plate Setting = None or #3 Only

FP1410

Fig. 28 Restrictor plate use with horizontal offset.

This Gas Fireplace has been approved for,

Vertical installations up to 40’ (12 m) in height. Up to a 20’ (6 m) horizontal vent run can be installed within the vent system using a maximum of three

(3) 90° elbows. (Fig. 29)

A 2’ (610 mm) vertical section must be installed before any offset. A maximum of 20’ (6.1 m) horizon- tal and three (3) 90° elbows may be installed with a minimum of 12’ (3.66 m) vertical section above the flue collar of the unit. (Fig. 29)

22

20011956

Image 22
Contents INSTALLER/CONSUMER Safety Information What to do if YOU Smell GASTable of Contents Certified To Installation & Operating InstructionsPlease Review the Following Carefully Clear of ALL Obstructions Requirements for the Commonwealth of MassachusettsGas Equipment Venting System not Provided Fireplace Dimensions DVT38IN Clearance to Combustibles Locating Your FireplaceMantels Framing and Finishing HearthFinal Finishing Gas Inlet and Manifold Pressures Gas Line InstallationGas Specifications High ElevationsControl System Installation Control SystemSpecial Feature for Cold Climates Inside view of wireless wall switchIntroduction Hand-Held Remote Control Transmitter Operating InstructionsKey Settings LCD Liquid Crystal DisplayManual Function Thermostat FunctionCP Childproof Feature Continuous Pilot FeatureSetting LOCK-OUT CP Thermostatic Updating Feature Operational NotesGeneral Venting Location of Vent TerminationCanadian Installations1 US Installations2 General Venting Information Termination LocationApplication Quick Reference for Fresh Air Restrictor Plate / Flue BaffleDVT38N DVT38P DVT44N DVT44P General Information Assembling Vent Pipes SK8 Venting Pipes Canadian InstallationsUSA Installations Horizontal TerminationSidewall Applications Use of the Restrictor Plates Horizontal Venting ApplicationsSidewall Installation StepAlways install horizontal venting on a level plane Vertical height requirementFresh Air Restrictor Plate Vertical Through-the-Roof Installation Typical offset applicationMin 610mm Chimney Components Component Description Model NumberRestrictor Plate Installation Glass Frame Assembly RemovalGlass Cleaning Glass InformationCeramic Refractory Installation Appliance Kit Model DescriptionLog, Lava Rock and Ember Placement DVT38IN LogsDVT44IN Logs Position the Log Grate Burner. Remove the twoPosition the Log Front Left. Pos- Figure Position the Log Rear LeftPosition the Log Front Middle Right DVT38IN logset complete Flame Characteristics Correct pilot flame appearanceTrim Installation Lighting Instructions Lighting & Operating InstructionsTurning Off the Gas to the Appliance American Flame Gas Control System TroubleshootingIgniter operation Troubleshooting American Flame Gas Control System American Flame Gas Control System Error Codes What to CheckConversion Procedure Conversion PrecautionsFuel Conversion Instructions Converting the Gas Control Valve Check Manifold PressureInjector Orifice Size Matrix Air Shutter SettingsPilot Flame Adjustment Valve Minimum Rate ScrewCleaning the Control System MaintenanceBurner and Burner Compartment DVT38IN, DVT44IN DVT38IN DVT44IN Colonial Red Limestone HerringboneFuel Conversion Kits Wall Mountable Wireless Remote Transmitter AccessoriesBack-up Battery Kit Ceramic Refractory KitsLimited Lifetime Warranty Product Covered by this WarrantyEfficiency Ratings Model EnerGuide Ratings Fireplace Efficiency %