Desa HDCFTP Checking GAS Connections, Test Pressures In Excess Of 1/2 Psig 3.5 kPa

Page 18

INSTALLATION

Continued

4.Apply pipe joint sealant lightly to male threads of gas connector attached to flexible gas line/ equipment shutoff valve (see Figure 26).

5.Check all gas connections for leaks. See Checking Gas Connections.

6.Replace branch support back into fireplace. Feed flexible gas line into fireplace base area while replacing branch support. Make sure the entire flexible gas line is in fireplace base area. Reattach branch support to fireplace with screws removed in step 2 on page 17.

To Fireplace

Equipment Shutoff

Gas Regulator

Valve Provided by

 

Installer

PRESSURE TESTING GAS SUPPLY PIPING SYSTEM

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.

Disconnect appliance with its appliance main

 

gas valve (control valve) and equipment

 

shutoff valve from gas supply piping system.

 

Pressures in excess of 1/2 psig will damage

 

heater regulator.

2.

Cap off open end of gas pipe where equipment

 

shutoff valve was connected.

3.

Pressurize supply piping system by either

 

opening propane/LP supply tank valve for

 

propane/LP gas or opening main gas valve

 

located on or near gas meter for natural gas,

 

or using compressed air.

4.

Check all joints of gas supply piping system.

 

Apply a noncorrosive leak detection fluid to

Flexible Gas Line from Fireplace Gas Regulator Provided with Fireplace

PROPANE/LP

To External

Regulator

NATURAL

To Gas Supply

 

gas joints. Bubbles forming show a leak.

5.

Correct all leaks at once.

6.

Reconnect heater and equipment shutoff valve

 

to gas supply. Check reconnected fittings for

 

leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

Figure 26 - Attaching Flexible Gas Line

to Equipment Shutoff Valve

CHECKING GAS CONNECTIONS

WARNING: Test allgas piping and connections, internal and external to unit, for leaks after installing or servicing. Correct all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detec- tion fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

CAUTION: Make sure exter- nal regulator has been installed between propane/LPsupply and fireplace. See guidelines under Connecting to Gas Supply, page 16.

1.Close equipment shutoff valve (see Fig- ure 27).

2.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas, or using compressed air.

3.Check all joints from gas meter for natural or propane/LP supply to equipment shutoff valve (see Figures 28 and 29, page 19). Ap- ply a noncorrosive leak detection fluid to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Equipment

Open

Shutoff

 

Valve

 

 

Closed

Figure 27 - Equipment Shutoff Valve

18

www.desatech.com

111044-01E

Image 18
Contents Shown with Optional Cabinet Mantel/Hearth Base Accessory HDCFTP, HDCFTN, Cgcftp and Cgcftn14,000 to 26,000 Btu/Hr with Thermostat Table of Contents Safety Information Local Codes Product InformationProvide adequate clearances around air openings Product Features AssemblyUnpacking Providing Adequate Ventilation Assembling HoodConfined and Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Heater Location Determining if You Have a Confined or Unconfined SpaceVentilation Air From Inside Building InstallationVentilation AIR Ventilation Air From OutdoorsInstallation Items Check GAS TypeLocating Fireplace BUILT-IN Fireplace Installation Rough Opening for Installing WallIf you have not assembled firebox, follow instructions on Attaching Fireplace to Wall StudsMantel Clearances for BUILT- in Installation Optional Mantel InstallationInstalling Blower Accessory Removing Upper Louver AssemblyRemoving Valve Cover Shield Removing Valve Cover ShieldInstalling Switch Plate to Valve Cover Shield For Built-In InstallationConnecting to GAS Supply Attaching Wood Base to Solid FloorExtension Cord Connecting Equipment Shutoff Valve to Heater Control Installation Items NeededChecking GAS Connections Test Pressures In Excess Of 1/2 Psig 3.5 kPaTest Pressures Equal To or Less Than 1/2 Psig 3.5 kPa Equipment Shutoff Valve For Your SafetyRead Before Lighting Propane/LPTo Turn OFF GAS To Appliance Operating FireplaceLighting Instructions Shutting Off FireplaceThermostat Control Operation Manual Lighting ProcedureInspecting Burner Burner Flame PatternCabinet Cleaning MaintenanceBurner Injector Holder and Pilot AIR Inlet Hole Air PassagewaysTroubleshooting Observed Problem Possible Cause RemedyODS/pilot lights but flame goes Out when control knob is reDelayed ignition of burner Manifold pressure is too low Press in control knob fullyGas regulator defective Nance, Replace gas regulator Burner orifice Clean burner see CleaningWalls or furniture Cleaners, etc. may turn into Air in gas line Minute Operate burner until air isGas leak. See Warning Service Hints SpecificationsReplacement Parts Technical ServiceIllustrated Parts Breakdown Models Cgcftp and CgcftnParts List Part Number KEY Hdcftp Hdcftn Cgcftp Cgcftn Description QTYAccessories Parts Centrals FBDWarranty Information Keep this WarrantyLimited Warranty VENT-FREE Compact Fireplace