Desa HDCFTP installation manual Gas leak. See Warning

Page 26

TROUBLESHOOTING

Continued

WARNING: If you smell gas

Shut off gas supply.

Do not try to light any appliance.

Do not touch any electrical switch; do not use any phone in your building.

Immediately call your gas supplier from a neighbor’s phone. Fol- low the gas supplier’s instructions.

If you cannot reach your gas supplier, call the fire department.

IMPORTANT: Operating fireplace where impurities in air exist may create odors. Cleaning supplies, paint, paint remover, cigarette smoke, cements and glues, new carpet or textiles, etc., create fumes. These fumes may mix with combustion air and create odors.

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

 

 

 

 

 

Fireplace produces a clicking/

1.

Metal expanding while heating

1.

This is common with most

ticking noise just after burner is

 

or contracting while cooling

 

fireplaces. If noise is excessive,

lit or shut off

 

 

 

contact qualified service person

 

 

 

 

 

Fireplace produces unwanted

1.

Fireplace burning vapors from

1.

Ventilate room. Stop using

odors

 

paint, hair spray, glues, etc.

 

odor causing products while

 

 

(see IMPORTANT statement

 

fireplace is running

 

 

above)

2.

Refill supply tank

 

2.

Low fuel supply

 

3.

Gas leak. See Warning

3.

Locate and correct all leaks

 

 

statement at top of page

 

(see Checking Gas Connec-

 

 

 

 

tions, page 18)

 

 

 

 

 

Fireplace shuts off in use (ODS

1.

Not enough fresh air is avail-

1.

Open window and/or door for

operates)

 

able

 

ventilation

 

2.

Low line pressure

2.

Contact local propane/LP or

 

3.

O D S / p i l o t i s p a r t i a l l y

 

natural gas company

 

3.

Clean ODS/pilot (see Cleaning

 

 

clogged

 

and Maintenance, page 22)

 

 

 

 

 

Gas odor even when control knob

1.

Gas leak. See Warning

1.

Locate and correct all leaks

is in OFF position

 

statement at top of page

 

(see Checking Gas Connec-

 

2.

Control valve defective

 

tions, page 18)

 

2.

Replace control valve

 

 

 

 

 

Gas odor during combustion

1.

Foreign matter between con-

1.

Take apart gas tubing and

 

 

trol valve and burner

 

remove foreign matter

 

2.

Gas leak. See Warning

2.

Locate and correct all leaks

 

 

statement at top of page

 

(see Checking Gas Connec-

 

 

 

 

tions, page 18)

 

 

 

 

 

Moisture/condensation noticed

1.

Not enough combustion/ven-

1.

Refer to Air for Combustion

on windows

 

tilation air

 

and Ventilation requirements

 

 

 

 

(page 6)

26

www.desatech.com

111044-01E

Image 26
Contents 14,000 to 26,000 Btu/Hr with Thermostat Shown with Optional Cabinet Mantel/Hearth Base AccessoryHDCFTP, HDCFTN, Cgcftp and Cgcftn Table of Contents Safety Information Provide adequate clearances around air openings Local CodesProduct Information Unpacking Product FeaturesAssembly Providing Adequate Ventilation Assembling HoodConfined and Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Heater Location Determining if You Have a Confined or Unconfined SpaceVentilation Air From Inside Building InstallationVentilation AIR Ventilation Air From OutdoorsLocating Fireplace Installation ItemsCheck GAS Type BUILT-IN Fireplace Installation Rough Opening for Installing WallIf you have not assembled firebox, follow instructions on Attaching Fireplace to Wall StudsMantel Clearances for BUILT- in Installation Optional Mantel InstallationInstalling Blower Accessory Removing Upper Louver AssemblyRemoving Valve Cover Shield Removing Valve Cover ShieldInstalling Switch Plate to Valve Cover Shield For Built-In InstallationExtension Cord Connecting to GAS SupplyAttaching Wood Base to Solid Floor Connecting Equipment Shutoff Valve to Heater Control Installation Items NeededTest Pressures Equal To or Less Than 1/2 Psig 3.5 kPa Checking GAS ConnectionsTest Pressures In Excess Of 1/2 Psig 3.5 kPa Equipment Shutoff Valve For Your SafetyRead Before Lighting Propane/LPTo Turn OFF GAS To Appliance Operating FireplaceLighting Instructions Shutting Off FireplaceThermostat Control Operation Manual Lighting ProcedureInspecting Burner Burner Flame PatternCabinet Cleaning MaintenanceBurner Injector Holder and Pilot AIR Inlet Hole Air PassagewaysTroubleshooting Observed Problem Possible Cause RemedyODS/pilot lights but flame goes Out when control knob is reDelayed ignition of burner Manifold pressure is too low Press in control knob fullyGas regulator defective Nance, Replace gas regulator Burner orifice Clean burner see CleaningWalls or furniture Cleaners, etc. may turn into Air in gas line Minute Operate burner until air isGas leak. See Warning Service Hints SpecificationsReplacement Parts Technical ServiceIllustrated Parts Breakdown Models Cgcftp and CgcftnParts List Part Number KEY Hdcftp Hdcftn Cgcftp Cgcftn Description QTYAccessories Parts Centrals FBDLimited Warranty VENT-FREE Compact Fireplace Warranty InformationKeep this Warranty