UNVENTED PROPANE/LP GAS FIREPLACE

INSTALLATION

Continued

INSTALLING GAS PIPING TO FIREPLACE LOCATION

WARNING: A qualified ser- vice person must connect fire- place to gas supply. Follow all local codes.

CAUTION: Never connect fire- place directly to the propane/LP supply. This fireplace requires an external regulator (not supplied). Install the external regulator be- tween the fireplace and propane/ LP supply.

Installation Items Needed

Before installing fireplace, make sure you have the items listed below.

external regulator (supplied by installer)

piping (check local codes)

sealant (resistant to propane/LP gas)

equipment shutoff valve *

test gauge connection *

sediment trap

tee joint

pipe wrench

approved flexible gas line with gas connec- tor (if allowed by local codes) (not provided)

*A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Pur- chase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 34.

The installer must supply an external regu- lator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incom- ing gas pressure, heater regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure

24.Pointing the vent down protects it from freezing rain or sleet.

CAUTION: Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used in cer- tain areas. Check your local codes. Use pipe of 1/2" diameter or greater to allow proper gas volume to fire- place. If pipe is too small, undue loss of pressure will occur.

Installation must include an equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from fireplace (see Figure 25).

IMPORTANT: Install equipment shutoff valve in an accessible location. The equip- ment shutoff valve is for turning on or shutting off the gas to the appliance.

Check your building codes for any special requirements for locating equipment shutoff valve to fireplaces.

Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged fireplace valves.

CAUTION: Use pipe joint seal- ant that is resistant to liquid pe- troleum (LP) gas.

 

 

External

 

Propane/LP

 

 

Regulator

 

 

 

 

Supply Tank

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vent Pointing Down

Figure 24 - External Regulator with Vent Pointing Down

We recommend that you install a sediment trap in supply line as shown in Figure 25. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and fireplace. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps mois- ture and contaminants. This keeps them from going into fireplace gas controls. If sediment trap is not installed or is installed wrong, fireplace may not run properly.

CSA Design-

Certified Equipment

Shutoff Valve With

1/8" NPT Tap*

 

From

 

External

 

Regulator

 

(11" W.C. to

3" Minimum

14 " W.C.

Pressure

Pipe Cap Tee

Nipple Joint

Sediment Trap

Figure 25 - Gas Connection

*Purchase the optional CSA design-certi- fied equipment shutoff valve from your dealer. See Accessories, page 34.

For more information, visit www.desatech.com

14

107570

Image 14
Contents OWNER’S Operation and Installation Manual What to do if YOU Smell GASSafety Information Unvented PROPANE/LP GAS FireplaceUnpacking Product IdentificationLocal Codes Product Features AIR for Combustion and VentilationDetermining if You Have a Confined or Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Fireplace Location Building Ventilation AIRVentilation Air From Inside Ventilation Air From OutdoorsCheck GAS Type InstallationInstallation Clearances Electrical HookupRelocating Wall Switch Installation SequenceRemoval of Fireplace Screen and Floor Assembly Lines and wiring when moving floor Installing Variable Speed Blower Accessory Mounting Wall Switch to Side of MantelInstalling Plastic Bushing for Power Cord Operating the BlowerInstalling Thermostatic Blower Accessory Lower Rear Wall Firebox BlowerInstalling Bushings Left Side Exit shown Installing GAS Piping to Fireplace Location Installation Items NeededPressure Testing Fireplace Gas Connections Connecting Fireplace to GAS SupplyPressure Testing Gas Supply Piping System Checking GAS ConnectionsConventional Fireplace Installation Checking Gas JointsBUILT-IN Fireplace Installation Inserting Fireplace Into Cabinet MantelInstalling Hood Mantel Clearances for Built-In InstallationInstalling Logs CGEFP33PR Installing Logs EFP33PRInstalling Screen Installing Battery Into RemoteUsing Hand-Held Wireless Remote Control For Your Safety Read Before LightingUsing Supplied Wall Switch Operating FireplaceOptional Blower Operation Manual Lighting Instructions For Electrical Power OutageTo Turn OFF GAS To Appliance Cleaning and Maintenance Inspecting BurnersTroubleshooting Observed Problem Possible CauseObserved Problem Possible Cause Remedy Gas leak. See Warning statement Wiring Diagram Service Hints SpecificationsReplacement Parts Technical ServiceParts Dealers Illustrated Parts Breakdown Parts List Remote Control Fireplace EFP33PR and CGEFP33PRFirebox KEY Part Number Description QTY Corner Mantel AccessoriesBlower Accessory GA3750 Series and GA3650T Series Equipment Shutoff Valve GA5010Diameter Holes This page Intentionally Left Blank 107570 Warranty Information