Desa Tech CGEFP33PR installation manual AIR for Combustion Ventilation

Page 5

OWNER’S MANUAL

AIR FOR

COMBUSTION AND

VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install fireplace plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example: Space size 22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling height) = 3168 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example: 3168 cu. ft. (volume of space) 50 cu. ft. = 63.3 or 63,300 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free fireplace

 

___________________ Btu/Hr

 

 

 

 

Gas water heater*

 

___________________ Btu/Hr

 

 

 

 

Gas furnace

 

___________________ Btu/Hr

Example:

 

 

 

Vented gas heater

 

___________________ Btu/Hr

Gas water heater

 

40,000

Btu/Hr

Gas fireplace logs

 

___________________ Btu/Hr

Vent-free fireplace

+

33,000

Btu/Hr

Other gas appliances*

+

___________________ Btu/Hr

Total

=

73,000

Btu/Hr

Total

=

___________________ Btu/Hr

 

 

 

 

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_____________ Btu/Hr (maximum the space can support)

_____________ Btu/Hr (actual amount of Btu/Hr used)

Example: 63,300 Btu/Hr (maximum the space can support) 73,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework work sheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin- ing room or add ventilation grills between rooms. See Ventilation Air from Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air from Outdoors, page 6.

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANS Z223.1, Section 5.3 or applicable local codes.

Continued

107570

5

For more information, visit www.desatech.com

Image 5
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualUnvented PROPANE/LP GAS Fireplace Safety InformationUnpacking Product IdentificationLocal Codes AIR for Combustion and Ventilation Product FeaturesDetermining if You Have a Confined or Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Fireplace Location Ventilation Air From Inside Ventilation AIRBuilding Ventilation Air From OutdoorsInstallation Clearances InstallationCheck GAS Type Electrical HookupRelocating Wall Switch Installation SequenceRemoval of Fireplace Screen and Floor Assembly Lines and wiring when moving floor Mounting Wall Switch to Side of Mantel Installing Variable Speed Blower AccessoryOperating the Blower Installing Plastic Bushing for Power CordLower Rear Wall Firebox Blower Installing Thermostatic Blower AccessoryInstalling Bushings Left Side Exit shown Installation Items Needed Installing GAS Piping to Fireplace LocationPressure Testing Gas Supply Piping System Connecting Fireplace to GAS SupplyPressure Testing Fireplace Gas Connections Checking GAS ConnectionsChecking Gas Joints Conventional Fireplace InstallationInserting Fireplace Into Cabinet Mantel BUILT-IN Fireplace InstallationMantel Clearances for Built-In Installation Installing HoodInstalling Logs EFP33PR Installing Logs CGEFP33PRInstalling Battery Into Remote Installing ScreenUsing Supplied Wall Switch For Your Safety Read Before LightingUsing Hand-Held Wireless Remote Control Operating FireplaceOptional Blower Operation Manual Lighting Instructions For Electrical Power OutageTo Turn OFF GAS To Appliance Inspecting Burners Cleaning and MaintenanceObserved Problem Possible Cause TroubleshootingObserved Problem Possible Cause Remedy Gas leak. See Warning statement Wiring Diagram Replacement Parts SpecificationsService Hints Technical ServiceParts Dealers Illustrated Parts Breakdown Remote Control Fireplace EFP33PR and CGEFP33PR Parts ListFirebox KEY Part Number Description QTY Blower Accessory GA3750 Series and GA3650T Series AccessoriesCorner Mantel Equipment Shutoff Valve GA5010Diameter Holes This page Intentionally Left Blank 107570 Warranty Information