Panasonic CU-5E36QBU service manual Installation Instruction, Select The Best Location

Page 17

10. Installation Instruction

10.1 Select The Best Location

If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not obstructed.

There should not be any animal or plant which could be affected by hot air discharged.

Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.

Do not place any obstacles which may cause a short circuit of the discharged air.

 

Refrigerant piping size

 

 

Outdoor Unit

CU-5E36***

 

 

Liquid - side

ø1/4" (ø6.35 mm) thickness 1/32" (t0.8 mm)

 

 

Gas - side

ø3/8" (ø9.52 mm) thickness 1/32" (t0.8 mm)

*(ø1/2" (ø12.7 mm) thickness 1/32" (t0.8 mm))

 

*In case of indoor is CS-E24***, then ø1/2" (ø12.7 mm) thickness 1/32" (t0.8 mm) gas-pipe size must be used together with CZ-MA2P (pipe size expander)

Outdoor Unit

CU-5E36***

Min. total piping length for additional gas

147.6 ft (45 m)

If total piping length of all indoor units exceeds the minimum length listed above, additionally charge with 0.2 oz (20g) of refrigerant (R410A) for each additional feet (meter) of piping.

Allowable piping length

Outdoor Unit

 

CU-5E36***

 

 

 

 

Allowable piping length of each indoor unit (min. ~ max.)

 

9.8 ft ~ 82.0 ft (3 m ~ 25 m)

 

 

 

 

Allowable total piping length of all indoor unit

 

262.4 ft (80 m) or less

 

 

 

 

Height difference between indoor and outdoor unit

Outdoor unit located on upper side

 

49.2 ft (15 m) or less

 

 

 

Outdoor unit located otherwise

 

24.6 ft (7.5 m) or less

 

 

 

 

 

 

Height difference between indoor unit

Outdoor unit located on upper side

 

24.6 ft (7.5 m) or less

 

 

 

Outdoor unit located otherwise

 

49.2 ft (15 m) or less

 

 

 

 

 

 

17

Image 17
Contents Destination Canada Air Conditioner Outdoor UnitTable of Contents Safety Precautions Page Outdoor Unit SpecificationsOutdoor Unit ∙ Multi Split Combination Possibility Room Indoor Unit Capacity Total Indoor Dimensions Refrigeration Cycle Diagram Block Diagram Electronic Controller Noise Filter WiringElectronic Circuit Diagram Main Printed Circuit Board Printed Circuit BoardPage Check Points Installation InformationSelect The Best Location Installation InstructionConnect The Piping Install The Outdoor UnitCutting and Flaring the Piping Evacuation Of The EquipmentHeat Insulation Connect The Cable To The Outdoor UnitDisposal Of Outdoor Unit Drain Water Operation Control Cooling Powerful OperationCooling Operation Outdoor fan controlHeating Room Temp Sampling Control Powerful OperationHeating Operation Simultaneous Operation Control Electronic Parts Temperature Rise Protection 2 Cool Electronic Parts Temperature Rise Protection 1 CoolProtection Control Freeze Prevention control CoolHeating overload control Heat Cooling overload control CoolIPM power transistor Protection Control Time Delay Safety Control Restart ControlDeice Control 13.10 30 seconds Force OperationCompressor discharge high pressure protection control Compressor Protection Control Gas leak detection controlValve close detection control Test Run Operation Servicing ModePump down operation SW1 Power Save Mode Wiring Error CheckMode priority function Cooling only functionSelf Diagnosis Function Troubleshooting GuidePage Page Outdoor Unit Removal Procedure Disassembly and Assembly InstructionsRemoving the Cabinet Top Plate Remove the Control Board Cover and Particular PlatesRemoving the Cabinet Front Plate Removing the Propeller Fan and Fan Motor Removing the Control P.C. BoardOne Indoor Unit Operation Technical DataOperation Characteristics Page Page Page Page Page Page Page Two Indoor Unit Operation Page Page Page Page Page Page Page Page Page Page Page Three Indoor Unit Operation Page Page Page Page Page Page Page Four Indoor Unit Operation Page Five Indoor Unit Operation Page Exploded View and Replacement Parts List Safety REF.NO Description & Name QTY CU-5E36QBU Remark Installation Instruction