Panasonic CU-5E36QBU Heating Operation, Heating Room Temp Sampling Control, Powerful Operation

Page 23

11.2 Heating Operation

11.2.1Outdoor fan control

When heating operation is enabled, based on outdoor ambient temperature, fan motor control will be adjusted according to figure below for Heating overload control:

11.2.2Heating Room Temp Sampling Control

To improve the judgment accuracy, indoor room temperature sampling starts when any indoor unit has stopped capability supplied (heating thermo-off) during heating operation with compressor ON, outdoor unit will send signal to all thermo-off indoor units to ON fan motor and get room temperature sample.

To prevent discharge temperature drop at indoor units which is ON when sampling the room temperature of heating thermo-off units, the compressor frequency is increased accordingly.

However, if indoor room temperature is much higher compare to remote control setting temperature, before thermo-off, sampling of corresponding indoor unit will be cancelled.

11.2.3Powerful Operation 2

During cooling / heating operation, this control is to provide fast cooling / heating operation compare to normal operation.

Operation start if all condition below are complied: o Powerful operation ON for indoor unit.

o Not under Annual Cooling control.

Operation content:

o Outdoor fan speed will adjust automatically.

o Compressor frequency will adjust automatically.

Operation stop when comply either one of the follow conditions: o When the powerful operation is OFF for all indoor units.

o When annual cooling control activated.

23

Image 23
Contents Destination Canada Air Conditioner Outdoor UnitTable of Contents Safety Precautions Page Outdoor Unit SpecificationsOutdoor Unit ∙ Multi Split Combination Possibility Room Indoor Unit Capacity Total Indoor Dimensions Refrigeration Cycle Diagram Block Diagram Electronic Controller Noise Filter WiringElectronic Circuit Diagram Main Printed Circuit Board Printed Circuit BoardPage Check Points Installation InformationSelect The Best Location Installation InstructionConnect The Piping Install The Outdoor UnitCutting and Flaring the Piping Evacuation Of The EquipmentHeat Insulation Connect The Cable To The Outdoor UnitDisposal Of Outdoor Unit Drain Water Outdoor fan control Cooling Powerful OperationOperation Control Cooling OperationHeating Room Temp Sampling Control Powerful OperationHeating Operation Simultaneous Operation Control Freeze Prevention control Cool Electronic Parts Temperature Rise Protection 1 CoolElectronic Parts Temperature Rise Protection 2 Cool Protection ControlHeating overload control Heat Cooling overload control Cool13.10 30 seconds Force Operation Time Delay Safety Control Restart ControlIPM power transistor Protection Control Deice ControlCompressor discharge high pressure protection control Compressor Protection Control Gas leak detection controlValve close detection control Test Run Operation Servicing ModePump down operation SW1 Cooling only function Wiring Error CheckPower Save Mode Mode priority functionSelf Diagnosis Function Troubleshooting GuidePage Page Remove the Control Board Cover and Particular Plates Disassembly and Assembly InstructionsOutdoor Unit Removal Procedure Removing the Cabinet Top PlateRemoving the Cabinet Front Plate Removing the Propeller Fan and Fan Motor Removing the Control P.C. BoardOne Indoor Unit Operation Technical DataOperation Characteristics Page Page Page Page Page Page Page Two Indoor Unit Operation Page Page Page Page Page Page Page Page Page Page Page Three Indoor Unit Operation Page Page Page Page Page Page Page Four Indoor Unit Operation Page Five Indoor Unit Operation Page Exploded View and Replacement Parts List Safety REF.NO Description & Name QTY CU-5E36QBU Remark Installation Instruction