Panasonic CU-5E36QBU service manual Compressor Protection Control Gas leak detection control

Page 28

DC peak current control

o When IPMDC current exceeds set value of 30.0 ± 3.0 A, the compressor will stop.

o If the DC peak current detected within 30 seconds after operation starts, compressor will restart after

1 minute.

oIf the DC peak current detected 30 seconds or more after operation starts, compressor will restart after 2 minutes.

oWithin 30 seconds after compressor restarts, if the DC peak current is exceeded set value continuously for 7 times, all indoor and outdoor relays will be cut off (“F99” is indicated).

Error reset can be done by power supply reset.

13.13 Compressor Protection Control (Gas leak detection control 1)

Control start conditions

o For 5 minutes, the compressor continuously operates and total current is low. o During Cooling or Soft Dry operation:

Indoor intake temperature — indoor piping temperature is below 39.2°F (4°C). o During Heating operation:

Indoor pipe temperature — indoor intake temperature is below 37.4°F (3°C). o Not during deice control.

o Compressor ON with maximum frequency.

Control content

o Compressor stops (and restart after 3 minutes)

o If the conditions above happen 4 times within 60 minutes, the unit will stop operation (“F91” is indicated).

13.14 Compressor Protection Control (Gas leak detection control 2)

This control detect gas leakage condition to prevent compressor damage.

Control start condition

o All connected indoor units capability supply ON. o Compressor ON with maximum frequency.

o Not during annual cooling.

o Compressor discharge temperature high.

Control content

o Compressor OFF during this control (“F91” is memorized in EEPROM)

o If the above conditions happen 2 times within 60 minutes, indoor units’ Timer LED will blinks (“F91” is indicated at all indoor units)

13.15 Valve close detection control

This control detects 3-way valve close condition to prevent damage to refrigerant cycle.

Start conditions:

o For all connected indoor units, if Indoor intake temperature — indoor piping temperature are between 28.4°F (-2°C) and 35.6°F (2°C) continuously for 5 minutes after compressor ON at first cooling operation.

o The first cooling operation is defined as cooling operation is ON for less than 8 minutes after new installation or after pump down.

Control content

o During this control, compressor stop, indoor units’ Timer LED will blink. (“F91” is indicated at indoor units)

Error reset can be done by power supply reset or reset by using remote control.

13.16 Compressor discharge high pressure protection control

This control protect by using high pressure switch during operation.

Start conditions

o High pressure switch is activated (from normally close to open) when outdoor operation mode is cooling or heating during compressor running.

Control 1 content

o Compressor stop when high pressure switch is opened and restart after high pressure switch closed. If this condition happen 4 times within 30 minutes, “F94” is indicated.

o After 30 minutes, counter is reset if this condition does not happen for 4 times.

Control 1 stop conditions o Power supply reset

o Reset by using remote control

28

Image 28
Contents Air Conditioner Outdoor Unit Destination CanadaTable of Contents Safety Precautions Page Specifications Outdoor UnitOutdoor Unit ∙ Multi Split Combination Possibility Room Indoor Unit Capacity Total Indoor Dimensions Refrigeration Cycle Diagram Block Diagram Wiring Electronic Controller Noise FilterElectronic Circuit Diagram Printed Circuit Board Main Printed Circuit BoardPage Installation Information Check PointsInstallation Instruction Select The Best LocationInstall The Outdoor Unit Connect The PipingEvacuation Of The Equipment Cutting and Flaring the PipingConnect The Cable To The Outdoor Unit Heat InsulationDisposal Of Outdoor Unit Drain Water Cooling Powerful Operation Operation ControlCooling Operation Outdoor fan controlHeating Operation Powerful OperationHeating Room Temp Sampling Control Simultaneous Operation Control Electronic Parts Temperature Rise Protection 1 Cool Electronic Parts Temperature Rise Protection 2 CoolProtection Control Freeze Prevention control CoolCooling overload control Cool Heating overload control HeatTime Delay Safety Control Restart Control IPM power transistor Protection ControlDeice Control 13.10 30 seconds Force OperationValve close detection control Compressor Protection Control Gas leak detection controlCompressor discharge high pressure protection control Pump down operation SW1 Servicing ModeTest Run Operation Wiring Error Check Power Save ModeMode priority function Cooling only functionTroubleshooting Guide Self Diagnosis FunctionPage Page Disassembly and Assembly Instructions Outdoor Unit Removal ProcedureRemoving the Cabinet Top Plate Remove the Control Board Cover and Particular PlatesRemoving the Cabinet Front Plate Removing the Control P.C. Board Removing the Propeller Fan and Fan MotorOperation Characteristics Technical DataOne Indoor Unit Operation Page Page Page Page Page Page Page Two Indoor Unit Operation Page Page Page Page Page Page Page Page Page Page Page Three Indoor Unit Operation Page Page Page Page Page Page Page Four Indoor Unit Operation Page Five Indoor Unit Operation Page Exploded View and Replacement Parts List Safety REF.NO Description & Name QTY CU-5E36QBU Remark Installation Instruction