11. Operation Control

11.1 Cooling Operation

11.1.1Outdoor fan control

When cooling operation is enabled, based on outdoor ambient temperature, fan motor control will be adjusted according to figure below:

11.1.2Annual Cooling control

This control is to enable cooling operation when outdoor ambient temperature is low.

Control start conditions:

o Cooling operation is activated with compressor ON.

o Outdoor ambient temperature is less than 59°F (15°C).

Control contents:

o When the above conditions are fulfilled, based on outdoor pipe temperature, the outdoor fan motor will operate according to figure below:

To improve the judgment accuracy during annual cooling control, outdoor ambient temperature sampling for 2 minutes will be activated every 35 minutes under designated fan speed.

Control stop conditions:

o When either one of the start conditions are not complied.

11.1.3Cooling Powerful Operation 1

During cooling operation, this control is to concentrate outdoor unit capability to the powerful operation enabled indoor unit by temporary stop the capability supply to low load demand indoor units.

Operation start condition:

o Powerful operation ON for targeted indoor unit.

Operation content:

o If other indoor units (where Powerful operation are OFF) achieve setting temperature continuously for

1 minute after received powerful command from indoor unit, then capability supply to other indoor units are stopped for minimum 3 minutes.

Capability supply stop period follows powerful operation period.

Operation stops when comply either one of the following conditions:

o When other indoor units (where Powerful operation are OFF) is demand for capacity. o When the powerful operation is OFF for all indoor units.

o When Quiet operation received from 1 indoor unit. o When protection control starts.

22

Image 22
Contents Air Conditioner Outdoor Unit Destination CanadaTable of Contents Safety Precautions Page Specifications Outdoor UnitOutdoor Unit ∙ Multi Split Combination Possibility Room Indoor Unit Capacity Total Indoor Dimensions Refrigeration Cycle Diagram Block Diagram Wiring Electronic Controller Noise FilterElectronic Circuit Diagram Printed Circuit Board Main Printed Circuit BoardPage Installation Information Check PointsInstallation Instruction Select The Best LocationInstall The Outdoor Unit Connect The PipingEvacuation Of The Equipment Cutting and Flaring the PipingConnect The Cable To The Outdoor Unit Heat InsulationDisposal Of Outdoor Unit Drain Water Cooling Operation Cooling Powerful OperationOperation Control Outdoor fan controlHeating Operation Powerful OperationHeating Room Temp Sampling Control Simultaneous Operation Control Protection Control Electronic Parts Temperature Rise Protection 1 CoolElectronic Parts Temperature Rise Protection 2 Cool Freeze Prevention control CoolCooling overload control Cool Heating overload control HeatDeice Control Time Delay Safety Control Restart ControlIPM power transistor Protection Control 13.10 30 seconds Force OperationValve close detection control Compressor Protection Control Gas leak detection controlCompressor discharge high pressure protection control Pump down operation SW1 Servicing ModeTest Run Operation Mode priority function Wiring Error CheckPower Save Mode Cooling only functionTroubleshooting Guide Self Diagnosis FunctionPage Page Removing the Cabinet Top Plate Disassembly and Assembly InstructionsOutdoor Unit Removal Procedure Remove the Control Board Cover and Particular PlatesRemoving the Cabinet Front Plate Removing the Control P.C. Board Removing the Propeller Fan and Fan MotorOperation Characteristics Technical DataOne Indoor Unit Operation Page Page Page Page Page Page Page Two Indoor Unit Operation Page Page Page Page Page Page Page Page Page Page Page Three Indoor Unit Operation Page Page Page Page Page Page Page Four Indoor Unit Operation Page Five Indoor Unit Operation Page Exploded View and Replacement Parts List Safety REF.NO Description & Name QTY CU-5E36QBU Remark Installation Instruction