13.8 Deice Control

When outdoor pipe temperature and outdoor air temperature is low, deice operation starts where indoor fan motor and outdoor fan motor stop, indoor unit horizontal vane close and operation LED blink with compressor ON.

13.9 Time Delay Safety Control (Restart Control)

The compressor will not restart within three minutes after compressor is stopped.

This control is not applicable if the power supply reset or after deice condition.

13.10 30 seconds Force Operation

Once the compressor starts operation, it will not stop its operation for 30 seconds in order to cycle back compressor oil.

However, it can be stopped using remote control or Auto OFF/ON button at indoor unit.

13.11 Total Current Control

By referring to table below, during normal (default) operation, the running current refer to Hi values and during Power Save Mode, the running current refer to Lo values.

When the outdoor unit total running current (AC) exceeds X value, compressor frequency will decrease.

If the running current does not exceed X value for 5 seconds, compressor frequency will increase.

However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 3 minutes.

Operation Mode

 

CU-5E36QBU

 

 

 

X (A)

Y (A)

 

 

 

 

 

 

Cooling/Soft Dry (A)

Hi

19.43

 

 

 

 

Lo

13.56

 

 

 

 

 

 

 

Cooling/Soft Dry (B)

Hi

17.32

 

 

 

 

Lo

13.56

23.07

 

 

 

 

Cooling/Soft Dry (C)

Hi

17.32

 

 

 

 

Lo

13.56

 

 

 

 

 

 

 

Heating

Hi

20.06

 

 

 

 

Lo

14.03

 

 

 

 

 

 

 

The first 30 minutes of cooling operation, (A) will be applied.

13.12 IPM (power transistor) Protection Control

Overheating Prevention Control

o If IPM temperature rises to 176°F (80°C), outdoor fan speed will be increased.

o When the IPM temperature rises to 203°F (95°C), compressor operation will stop immediately. o Compressor operation restarts when temperature decreases to 194°F (90°C).

o If IPM temperature detected less than -22°F (-30°C), IPM is judged as open circuit (“F96” is indicated).

27

Image 27
Contents Destination Canada Air Conditioner Outdoor UnitTable of Contents Safety Precautions Page Outdoor Unit SpecificationsOutdoor Unit ∙ Multi Split Combination Possibility Room Indoor Unit Capacity Total Indoor Dimensions Refrigeration Cycle Diagram Block Diagram Electronic Controller Noise Filter WiringElectronic Circuit Diagram Main Printed Circuit Board Printed Circuit BoardPage Check Points Installation InformationSelect The Best Location Installation InstructionConnect The Piping Install The Outdoor UnitCutting and Flaring the Piping Evacuation Of The EquipmentHeat Insulation Connect The Cable To The Outdoor UnitDisposal Of Outdoor Unit Drain Water Outdoor fan control Cooling Powerful OperationOperation Control Cooling OperationPowerful Operation Heating OperationHeating Room Temp Sampling Control Simultaneous Operation Control Freeze Prevention control Cool Electronic Parts Temperature Rise Protection 1 CoolElectronic Parts Temperature Rise Protection 2 Cool Protection ControlHeating overload control Heat Cooling overload control Cool13.10 30 seconds Force Operation Time Delay Safety Control Restart ControlIPM power transistor Protection Control Deice ControlCompressor Protection Control Gas leak detection control Valve close detection controlCompressor discharge high pressure protection control Servicing Mode Pump down operation SW1Test Run Operation Cooling only function Wiring Error CheckPower Save Mode Mode priority functionSelf Diagnosis Function Troubleshooting GuidePage Page Remove the Control Board Cover and Particular Plates Disassembly and Assembly InstructionsOutdoor Unit Removal Procedure Removing the Cabinet Top PlateRemoving the Cabinet Front Plate Removing the Propeller Fan and Fan Motor Removing the Control P.C. BoardTechnical Data Operation CharacteristicsOne Indoor Unit Operation Page Page Page Page Page Page Page Two Indoor Unit Operation Page Page Page Page Page Page Page Page Page Page Page Three Indoor Unit Operation Page Page Page Page Page Page Page Four Indoor Unit Operation Page Five Indoor Unit Operation Page Exploded View and Replacement Parts List Safety REF.NO Description & Name QTY CU-5E36QBU Remark Installation Instruction