Panasonic CU-5E36QBU service manual Evacuation Of The Equipment, Cutting and Flaring the Piping

Page 19

CUTTING AND FLARING THE PIPING

1.Please cut using pipe cutter and then remove the burrs.

2.Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end down to avoid the metal powder entering the pipe.

3.Please make flare after inserting the flare nut onto the copper pipes.

10.4 Evacuation Of The Equipment

WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure.

1.Connect a charging hose with a push pin to the Low side of a charging set and the service port of the gas side 3-way valve.

2.Connect the micron gauge between vacuum pump and service port of outdoor units.

3.Turn on the power switch of the vacuum pump and make sure that connect digital micron gauge and to pull down to a value of 500 microns.

4.To make sure micron gauge a value 500 microns and close the low side valve of the charging set and turn off the vacuum pump.

5.Disconnect the vacuum pump house from the service port of the 3-way valve.

6.Tighten the service port caps of gas side

3-way valve at a torque of 13.3 Ibf.ft (18 N•m) with a torque wrench.

7.Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “Open” using a hexagonal wrench (5/32" (4 mm)).

8.Mount valve caps onto the 2-way valve and 3-way valve.

o Be sure to check for gas leakage.

If micron gauge value does not descend 500 microns, take the following measures:

-If the leak stops when the piping connections are tightened further, continue working from step .

-If the leak does not stop when the connections are retightened, repair location of leak.

-Do not release refrigerant during piping work for installation and reinstallation.

-Take care of the liquid refrigerant, it may cause frostbite.

19

Image 19
Contents Destination Canada Air Conditioner Outdoor UnitTable of Contents Safety Precautions Page Outdoor Unit SpecificationsOutdoor Unit ∙ Multi Split Combination Possibility Room Indoor Unit Capacity Total Indoor Dimensions Refrigeration Cycle Diagram Block Diagram Electronic Controller Noise Filter WiringElectronic Circuit Diagram Main Printed Circuit Board Printed Circuit BoardPage Check Points Installation InformationSelect The Best Location Installation InstructionConnect The Piping Install The Outdoor UnitCutting and Flaring the Piping Evacuation Of The EquipmentHeat Insulation Connect The Cable To The Outdoor UnitDisposal Of Outdoor Unit Drain Water Outdoor fan control Cooling Powerful OperationOperation Control Cooling OperationHeating Operation Powerful OperationHeating Room Temp Sampling Control Simultaneous Operation Control Freeze Prevention control Cool Electronic Parts Temperature Rise Protection 1 CoolElectronic Parts Temperature Rise Protection 2 Cool Protection ControlHeating overload control Heat Cooling overload control Cool13.10 30 seconds Force Operation Time Delay Safety Control Restart ControlIPM power transistor Protection Control Deice ControlValve close detection control Compressor Protection Control Gas leak detection controlCompressor discharge high pressure protection control Pump down operation SW1 Servicing ModeTest Run Operation Cooling only function Wiring Error CheckPower Save Mode Mode priority functionSelf Diagnosis Function Troubleshooting GuidePage Page Remove the Control Board Cover and Particular Plates Disassembly and Assembly InstructionsOutdoor Unit Removal Procedure Removing the Cabinet Top PlateRemoving the Cabinet Front Plate Removing the Propeller Fan and Fan Motor Removing the Control P.C. BoardOperation Characteristics Technical DataOne Indoor Unit Operation Page Page Page Page Page Page Page Two Indoor Unit Operation Page Page Page Page Page Page Page Page Page Page Page Three Indoor Unit Operation Page Page Page Page Page Page Page Four Indoor Unit Operation Page Five Indoor Unit Operation Page Exploded View and Replacement Parts List Safety REF.NO Description & Name QTY CU-5E36QBU Remark Installation Instruction