Heat Controller A-MMC24FA-1, B-MMH12FA-1, B-MMC12FA-1, B-MMC09FA-1 manual Function of Outdoor Unit

Page 47

Operation

FunctionofOutdoor Unit

Outdoor Unit

Operating Step

Compressor step varies considering conditions such as room temperature, operating room number, temperature gap between room temperature and set point temperature and so on.

LEV Control

The linear expansion valve is pulse is modulated to keep constant superheat or subcooling.

Outdoor Fan Control

Outdoor fan operates at High or Off to respond to the load condition.

R/Valve Control(Heating Model Only)

Reversing valves is used to change cooling to heating, heating to cooling.

Defrost Function

After 45 minutes in heating mode, defrost mode will take effect if the outdoor pipe temp is below 5°C (23°F). The defrost mode will end when the outdoor pipe temp is above 12°C (53.6°F) or after the unit has been operated in cooling mode for 9 minutes.

To de-ice the outdoor heat exchanger in low temperature conditions, the unit will defrost by changing the operating mode from heating to cooling, while turning off both indoor and outdoor fans.

Oil Return System

In single(one) compressor operation duration, another compressor will operate for 30 seconds every 1 hours.

compressor Overload Protection

To protect compressor from being overloaded, the compressor overload protector will turn the compressor off.

High Pressure Protction

If the refrigerant cycle's pressure is too high, above 36.7 kgf/cm2 (521.997psi), the high pressure switch will turn the compressor off.

- 47 -

Service Manual

Image 47
Contents Heat CONTROLLER, INC Table of Contents KBtu/h 3 rooms Symbols Used in this ManualKBtu/h 2 rooms Control box securely Cuit and breaker Safety PrecautionsInstallation Be sure not to do Be sure to follow the instructionDo not allow water to run into electric parts Do not install, remove, or reDo not install the product on a Defective installation standFlooded or submerged, contact When the product is soaked Be cautious that water canNever enter the product Use two or more people to lift and transport the product Install the drain hose to ensure that Keep level even whenInstalling the product Operational Do not use the remote is the batteries have leaked Selecting the locationOutdoor Unit Seaside applications and installationSplit Type Indoor DimensionsIndoor Unit 18kBtu/h Outdoor Unit24kBtu/h 36kBtu/h UE2Indoor Unit Type Wall Mounted Model Product SpecificationsMMC18FA-1 MMH18FA-1 Outdoor Unit Multiple piping modelsMMC24FA-1 MMH24FA-1 MMC36FA-1 MMH36FA-1 Installation Tools InstallationInstallation Parts Selecting the best location 18 / 24 kBtu/h KBtu/h Piping length and elevationMulti Piping Type Drilling the hole in the wall Installing Installation PlateStandard TypeFlaring work Flaring Work and Connection of PipingIndoor Connecting the PipingCheck Wrap the insulation material around the all connections Indoor unit installationFor left rear piping Wrap the insulation material around the connecting por- tion Bad case Good caseRemote Control Preparationoptional Outdoor unit 36 kBtu/h OutdoorOutdoor unit 18/24 kBtu/h Tions ETL recognized and CSA certified Connect the cable to the Indoor unitOutdoor unit Connect the cable to the Outdoor unitHow to connect wiring to the terminals Methods of connecting the cableModel Drain piping Checking the drainageTo check the drainage Insulating the Pipe and Special Piping Applications Secure the taped piping along the exterior wall usingLeakage test Air Purging and EvacuationLeak checking PreparationFinishing the job Repeat evacuation procedure for each indoor unitEvacuation Additional ChargingSplit Type Test RunningOperation Cooling Mode OperationSoft Dry Operation Mode Heating Mode OperationFuzzy Operation for Cooling Defrost ControlHeatingFuzzy Operation Fuzzy Operation for Dehumidification On-Timer OperationOff-Timer Operation Airflow Speed SelectionChaos Natural Wind Mode Off-Timer = On-Timer OperationSleep Timer Operation Chaos Swing ModeBuzzer Sound Forced OperationSplit Type Indoor Unit Function of Indoor UnitFunction of Outdoor Unit Cooling Model , Heat Pump Model Remote Control OperationTime Setting Buttons Used to adjust the time To remove the Grille from the Chassis DisassemblyTo remove the Control Box To remove the Motor Cover Indoor Unit Schematic DiagramElectronic Control Device TMP87CM41F Outdoor UnitRY-4WAY RY-LIQ RY-GAS RY-FANL RY-FANH Indoor Unit Outdoor Unit Wiring DiagramMMC24FA-1 Bottom View Component LocationsDisplay Assembly Split Type 6871A20680 Component side Solder side MMH18FA-1 Troubleshooting GuideRefrigeration Cycle Diagram MMC18FA-1MMH24FA-1 MMH36FA-1 MMC36FA-1Self-diagnosis Function Indoor ErrorOutdoor Error Error IndicatorTrouble analysis Cycle Troubleshooting GuideProcedure Specification Remedy Electronic Parts Troubleshooting GuideProduct doesnt operate with the remote controller Check Point Comp. on Comp. OFF Compressor/Outdoor Fan dont operateNector Trouble 4 When indoor Fan does not operateRY-COMP-B Voltage of Connectors according to Indoor Fan SpeedWhen Vertical Louver does not operate Indoor inlet pipe sensor Error CodeCheck Point Indoor air sensorCommunication line is shorted at GND Description Cause of error Check point & Normal conditionPower input AC 230V.Outdoor, Indoor Comp OFF Pipe sensor Outdoor air sensorCondensor pipe sensor Way Valve Liguid Side Way, 3-way ValvePumping down ProcedureAll the refrigerant leaked Replace the valve and service port capsEvacuation Connect the gauge to the charging cylinder Replace the valve stem nuts and the service port nutGas Charging After EvacuationModel B-MMC09FA-1, B-MMH09FA-1, B-MMC12FA-1, B-MMH12FA-1 Exploded ViewModel A-MMC18FA-1, A-MMH18FA-1 Model A-MMC24FA-1, A-MMH24FA-1 Model A-MMC36FA-1, A-MMH36FA-1 08/06/2008 Heat CONTROLLER, INC