Heat Controller B-MMH09FA-1 manual Description Cause of error Check point & Normal condition

Page 73

 

 

 

Troubleshooting Guide

 

 

 

 

 

Error

Description

Cause of error

Check point & Normal condition

 

code

 

 

 

 

 

 

 

 

 

 

 

 

 

• Power input AC 230V.(Outdoor, Indoor)

 

 

 

 

• The connector for transmission is disconnected.

 

05 / 53

Communication

 

• The connecting wires are misconnected.

 

(Indoor Outdoor)

• Poor Communication

• The GND 1,2 is not connected at main GND.

 

 

 

 

 

 

• The communication line is shorted at GND.

 

 

 

 

• Transmission circuit of outdoor PCB is abnormal.

 

 

 

 

• Transmission circuit of indoor PCB is abnormal.

 

 

 

 

 

 

Check Point

1.Check the input power AC 230V.(Outdoor, Indoor)

2.Check that the communication wires are correctly connected.

Adjust the connection of wire

Confirm the "Live", "Neutral“ wires.

3.Check the resistance between communication line and GND.(Normal : Over 2M)

4.Check the connector for communication is correctly connected.

5.Check the connection of GND1, GND2, and main GND.

6.If one indoor unit is operating normally, outdoor PCB has no problem.

Check the other indoor unit.

* CH05 is displayed at indoor unit, CH53 is displayed at outdoor unit.

- 73 -

Service Manual

Image 73
Contents Heat CONTROLLER, INC Table of Contents KBtu/h 2 rooms Symbols Used in this ManualKBtu/h 3 rooms Installation Safety PrecautionsBe sure not to do Be sure to follow the instruction Control box securely Cuit and breakerDo not install the product on a Do not install, remove, or reDefective installation stand Do not allow water to run into electric partsNever enter the product When the product is soaked Be cautious that water canFlooded or submerged, contact Installing the product Install the drain hose to ensure that Keep level even whenUse two or more people to lift and transport the product Operational Do not use the remote is the batteries have leaked Selecting the locationOutdoor Unit Seaside applications and installationIndoor Unit DimensionsSplit Type Indoor 18kBtu/h Outdoor Unit24kBtu/h 36kBtu/h UE2Indoor Unit Type Wall Mounted Model Product SpecificationsMMC18FA-1 MMH18FA-1 Outdoor Unit Multiple piping modelsMMC24FA-1 MMH24FA-1 MMC36FA-1 MMH36FA-1 Installation Parts InstallationInstallation Tools Selecting the best location Multi Piping Type Piping length and elevation18 / 24 kBtu/h KBtu/h Drilling the hole in the wall Installing Installation PlateStandard TypeFlaring work Flaring Work and Connection of PipingCheck Connecting the PipingIndoor Wrap the insulation material around the all connections Indoor unit installationFor left rear piping Wrap the insulation material around the connecting por- tion Bad case Good caseRemote Control Preparationoptional Outdoor unit 18/24 kBtu/h OutdoorOutdoor unit 36 kBtu/h Tions ETL recognized and CSA certified Connect the cable to the Indoor unitOutdoor unit Connect the cable to the Outdoor unitHow to connect wiring to the terminals Methods of connecting the cableModel To check the drainage Checking the drainageDrain piping Insulating the Pipe and Special Piping Applications Secure the taped piping along the exterior wall usingLeak checking Air Purging and EvacuationPreparation Leakage testEvacuation Repeat evacuation procedure for each indoor unitFinishing the job Additional ChargingSplit Type Test RunningSoft Dry Operation Mode Cooling Mode OperationHeating Mode Operation OperationFuzzy Operation Defrost ControlHeatingFuzzy Operation for Cooling Off-Timer Operation On-Timer OperationAirflow Speed Selection Fuzzy Operation for DehumidificationSleep Timer Operation Off-Timer = On-Timer OperationChaos Swing Mode Chaos Natural Wind ModeBuzzer Sound Forced OperationSplit Type Indoor Unit Function of Indoor UnitFunction of Outdoor Unit Time Setting Buttons Used to adjust the time Remote Control OperationCooling Model , Heat Pump Model To remove the Grille from the Chassis DisassemblyTo remove the Control Box To remove the Motor Cover Electronic Control Device Schematic DiagramIndoor Unit TMP87CM41F Outdoor UnitRY-4WAY RY-LIQ RY-GAS RY-FANL RY-FANH Indoor Unit Outdoor Unit Wiring DiagramMMC24FA-1 Bottom View Component LocationsDisplay Assembly Split Type 6871A20680 Component side Solder side Refrigeration Cycle Diagram Troubleshooting GuideMMC18FA-1 MMH18FA-1MMH24FA-1 MMH36FA-1 MMC36FA-1Outdoor Error Indoor ErrorError Indicator Self-diagnosis FunctionTrouble analysis Cycle Troubleshooting GuideProcedure Specification Remedy Electronic Parts Troubleshooting GuideProduct doesnt operate with the remote controller Check Point Comp. on Comp. OFF Compressor/Outdoor Fan dont operateNector Trouble 4 When indoor Fan does not operateRY-COMP-B Voltage of Connectors according to Indoor Fan SpeedWhen Vertical Louver does not operate Check Point Error CodeIndoor air sensor Indoor inlet pipe sensorPower input AC 230V.Outdoor, Indoor Description Cause of error Check point & Normal conditionCommunication line is shorted at GND Comp OFF Condensor pipe sensor Outdoor air sensorPipe sensor Way Valve Liguid Side Way, 3-way ValvePumping down ProcedureEvacuation Replace the valve and service port capsAll the refrigerant leaked Gas Charging Replace the valve stem nuts and the service port nutAfter Evacuation Connect the gauge to the charging cylinderModel B-MMC09FA-1, B-MMH09FA-1, B-MMC12FA-1, B-MMH12FA-1 Exploded ViewModel A-MMC18FA-1, A-MMH18FA-1 Model A-MMC24FA-1, A-MMH24FA-1 Model A-MMC36FA-1, A-MMH36FA-1 08/06/2008 Heat CONTROLLER, INC