Heat Controller B-MMC09FA-1 Error Code, Check Point, Indoor air sensor, Indoor inlet pipe sensor

Page 72

Troubleshooting Guide

ErrorCode

Trouble Shooting

Error

Description

Cause of error

Check point & Normal condition

code

 

 

 

 

 

 

 

 

 

• Open / Short

Normal resistor : 10K/ at 25°C(77°F) (Unplugged)

01

Indoor air sensor

• Soldered poorly

Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)

 

 

• Internal circuit error

 

 

 

 

 

 

 

 

 

• Open / Short

Normal resistor : 5K/ at 25°C(77°F) (Unplugged)

02

Indoor inlet pipe sensor

• Soldered poorly

Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)

 

 

• Internal circuit error

 

 

 

 

 

 

 

 

 

• Open / Short

Normal resistor : 5K/ at 25°C(77°F) (Unplugged)

06

Indoor outlet pipe sensor

• Soldered poorly

Normal voltage : 2.5Vdc / at 25°C(77°F) (plugged)

 

 

• Internal circuit error

 

 

 

 

 

 

 

10K

2.5Vdc

V

Check the resistance / voltage

Check Point

1.Unplug the sensor on Indoor unit PCB.

2.Estimate the resistance of each sensor

3.If the resistance of the sensor is 10K/5Kat 25°C(77°F), then sensor is normal

4.If the resistance of the sensor is 0 Kor , then sensor is abnormal. Change the sensor.

5.Plug the sensor onto the Indoor unit PCB and Power ON.

6.Estimate the voltage of each sensor.

7.If the voltage of the sensor is 2.5Vdc / at 25°C(77°F), then sensor is normal.

8.If the resistance of the sensor is 0 or 5Vdc, then sensor is abnormal. Repair or Change the PCB

Wall Mounted Multi-Zone Split System Air Conditioner

- 72 -

Image 72
Contents Heat CONTROLLER, INC Table of Contents Symbols Used in this Manual KBtu/h 2 roomsKBtu/h 3 rooms Safety Precautions InstallationBe sure not to do Be sure to follow the instruction Control box securely Cuit and breakerDo not install, remove, or re Do not install the product on aDefective installation stand Do not allow water to run into electric partsWhen the product is soaked Be cautious that water can Never enter the productFlooded or submerged, contact Install the drain hose to ensure that Keep level even when Installing the productUse two or more people to lift and transport the product Operational Do not use the remote is the batteries have leaked Seaside applications and installation Selecting the locationOutdoor UnitDimensions Indoor UnitSplit Type Indoor Outdoor Unit 18kBtu/h24kBtu/h UE2 36kBtu/hProduct Specifications Indoor Unit Type Wall Mounted ModelOutdoor Unit Multiple piping models MMC18FA-1 MMH18FA-1MMC24FA-1 MMH24FA-1 MMC36FA-1 MMH36FA-1 Installation Installation PartsInstallation Tools Selecting the best location Piping length and elevation Multi Piping Type18 / 24 kBtu/h KBtu/h Installing Installation PlateStandard Type Drilling the hole in the wallFlaring Work and Connection of Piping Flaring workConnecting the Piping CheckIndoor Indoor unit installation Wrap the insulation material around the all connectionsFor left rear piping Wrap the insulation material around the connecting por- tion Good case Bad caseRemote Control Preparationoptional Outdoor Outdoor unit 18/24 kBtu/hOutdoor unit 36 kBtu/h Connect the cable to the Indoor unit Tions ETL recognized and CSA certifiedConnect the cable to the Outdoor unit Outdoor unitMethods of connecting the cable How to connect wiring to the terminalsModel Checking the drainage To check the drainageDrain piping Secure the taped piping along the exterior wall using Insulating the Pipe and Special Piping ApplicationsAir Purging and Evacuation Leak checkingPreparation Leakage testRepeat evacuation procedure for each indoor unit EvacuationFinishing the job Charging AdditionalTest Running Split TypeCooling Mode Operation Soft Dry Operation ModeHeating Mode Operation OperationDefrost ControlHeating Fuzzy OperationFuzzy Operation for Cooling On-Timer Operation Off-Timer OperationAirflow Speed Selection Fuzzy Operation for DehumidificationOff-Timer = On-Timer Operation Sleep Timer OperationChaos Swing Mode Chaos Natural Wind ModeForced Operation Buzzer SoundFunction of Indoor Unit Split Type Indoor UnitFunction of Outdoor Unit Remote Control Operation Time Setting Buttons Used to adjust the timeCooling Model , Heat Pump Model Disassembly To remove the Grille from the ChassisTo remove the Control Box To remove the Motor Cover Schematic Diagram Electronic Control DeviceIndoor Unit Outdoor Unit TMP87CM41FRY-4WAY RY-LIQ RY-GAS RY-FANL RY-FANH Wiring Diagram Indoor Unit Outdoor UnitMMC24FA-1 Component Locations Bottom ViewDisplay Assembly Split Type 6871A20680 Component side Solder side Troubleshooting Guide Refrigeration Cycle DiagramMMC18FA-1 MMH18FA-1MMH24FA-1 MMC36FA-1 MMH36FA-1Indoor Error Outdoor ErrorError Indicator Self-diagnosis FunctionCycle Troubleshooting Guide Trouble analysisElectronic Parts Troubleshooting Guide Procedure Specification RemedyProduct doesnt operate with the remote controller Compressor/Outdoor Fan dont operate Check Point Comp. on Comp. OFFTrouble 4 When indoor Fan does not operate NectorVoltage of Connectors according to Indoor Fan Speed RY-COMP-BWhen Vertical Louver does not operate Error Code Check PointIndoor air sensor Indoor inlet pipe sensorDescription Cause of error Check point & Normal condition Power input AC 230V.Outdoor, IndoorCommunication line is shorted at GND Comp OFF Outdoor air sensor Condensor pipe sensorPipe sensor Way, 3-way Valve Way Valve Liguid SideProcedure Pumping downReplace the valve and service port caps EvacuationAll the refrigerant leaked Replace the valve stem nuts and the service port nut Gas ChargingAfter Evacuation Connect the gauge to the charging cylinderExploded View Model B-MMC09FA-1, B-MMH09FA-1, B-MMC12FA-1, B-MMH12FA-1Model A-MMC18FA-1, A-MMH18FA-1 Model A-MMC24FA-1, A-MMH24FA-1 Model A-MMC36FA-1, A-MMH36FA-1 Heat CONTROLLER, INC 08/06/2008