Heat Controller A-MMH18FA-1, B-MMH12FA-1, B-MMC12FA-1 manual Electronic Parts Troubleshooting Guide

Page 66

Troubleshooting Guide

ElectronicPartsTroubleshooting Guide

Refer to electronic contorol device drawing & schematic diagram.

Trouble 1

The Product doesn’t operate at all.

Turn off the main power and wait until LED on outdoor PCB is off.

Turn on the main power again.

Is "Beeping" sound is made from the indoor unit?

NO

Check the voltage of power(AC208V/AC230V, 60Hz).

The voltage of main power.

The voltage applied to the unit.

The connecting method of Indoor/Outdoor connecting cable (each color)

The P.C.B. Ass'y

(Fuse, Noise Filter, Power Transformer, IC01D, IC02D, etc.)

YES

Primarily, the operating condi- tion of Micom is O.K.

Check CN-DISP1

The operation check of the P.C.B. Ass'y

 

Procedure

 

Specification

 

Remedy

 

 

 

 

 

 

1)

The input voltage of power trans-

1)

AC230V ± 30V

1)

Replace

 

former.

 

: Check the rated voltage

 

power transfomer.

2)

The output voltage of power

2)

15V ± 1.5V

2)

Replace

 

transformer.

 

 

 

power transfomer.

3)

IC01D(7812)

3)

DC12V

3) Replace IC01D.

4)

IC02D(7805)

4)

DC5V

4) Replace IC02D.

5)

IC01A(KIA7036)

5)

The voltage of micom pin 29

5)

Replace IC01A.

 

 

 

: DC4.5V

 

 

 

 

 

 

 

 

Wall Mounted Multi-Zone Split System Air Conditioner

- 66 -

Image 66
Contents Heat CONTROLLER, INC Table of Contents Symbols Used in this Manual KBtu/h 2 roomsKBtu/h 3 rooms Be sure not to do Be sure to follow the instruction Safety PrecautionsInstallation Control box securely Cuit and breakerDefective installation stand Do not install, remove, or reDo not install the product on a Do not allow water to run into electric partsWhen the product is soaked Be cautious that water can Never enter the productFlooded or submerged, contact Install the drain hose to ensure that Keep level even when Installing the productUse two or more people to lift and transport the product Operational Do not use the remote is the batteries have leaked Seaside applications and installation Selecting the locationOutdoor UnitDimensions Indoor UnitSplit Type Indoor Outdoor Unit 18kBtu/h24kBtu/h UE2 36kBtu/hProduct Specifications Indoor Unit Type Wall Mounted ModelOutdoor Unit Multiple piping models MMC18FA-1 MMH18FA-1MMC24FA-1 MMH24FA-1 MMC36FA-1 MMH36FA-1 Installation Installation PartsInstallation Tools Selecting the best location Piping length and elevation Multi Piping Type18 / 24 kBtu/h KBtu/h Installing Installation PlateStandard Type Drilling the hole in the wallFlaring Work and Connection of Piping Flaring workConnecting the Piping CheckIndoor Indoor unit installation Wrap the insulation material around the all connectionsFor left rear piping Wrap the insulation material around the connecting por- tion Good case Bad caseRemote Control Preparationoptional Outdoor Outdoor unit 18/24 kBtu/hOutdoor unit 36 kBtu/h Connect the cable to the Indoor unit Tions ETL recognized and CSA certifiedConnect the cable to the Outdoor unit Outdoor unitMethods of connecting the cable How to connect wiring to the terminalsModel Checking the drainage To check the drainageDrain piping Secure the taped piping along the exterior wall using Insulating the Pipe and Special Piping ApplicationsPreparation Air Purging and EvacuationLeak checking Leakage testRepeat evacuation procedure for each indoor unit EvacuationFinishing the job Charging AdditionalTest Running Split TypeHeating Mode Operation Cooling Mode OperationSoft Dry Operation Mode OperationDefrost ControlHeating Fuzzy OperationFuzzy Operation for Cooling Airflow Speed Selection On-Timer OperationOff-Timer Operation Fuzzy Operation for DehumidificationChaos Swing Mode Off-Timer = On-Timer OperationSleep Timer Operation Chaos Natural Wind ModeForced Operation Buzzer SoundFunction of Indoor Unit Split Type Indoor UnitFunction of Outdoor Unit Remote Control Operation Time Setting Buttons Used to adjust the timeCooling Model , Heat Pump Model Disassembly To remove the Grille from the ChassisTo remove the Control Box To remove the Motor Cover Schematic Diagram Electronic Control DeviceIndoor Unit Outdoor Unit TMP87CM41FRY-4WAY RY-LIQ RY-GAS RY-FANL RY-FANH Wiring Diagram Indoor Unit Outdoor UnitMMC24FA-1 Component Locations Bottom ViewDisplay Assembly Split Type 6871A20680 Component side Solder side MMC18FA-1 Troubleshooting GuideRefrigeration Cycle Diagram MMH18FA-1MMH24FA-1 MMC36FA-1 MMH36FA-1Error Indicator Indoor ErrorOutdoor Error Self-diagnosis FunctionCycle Troubleshooting Guide Trouble analysisElectronic Parts Troubleshooting Guide Procedure Specification RemedyProduct doesnt operate with the remote controller Compressor/Outdoor Fan dont operate Check Point Comp. on Comp. OFFTrouble 4 When indoor Fan does not operate NectorVoltage of Connectors according to Indoor Fan Speed RY-COMP-BWhen Vertical Louver does not operate Indoor air sensor Error CodeCheck Point Indoor inlet pipe sensorDescription Cause of error Check point & Normal condition Power input AC 230V.Outdoor, IndoorCommunication line is shorted at GND Comp OFF Outdoor air sensor Condensor pipe sensorPipe sensor Way, 3-way Valve Way Valve Liguid SideProcedure Pumping downReplace the valve and service port caps EvacuationAll the refrigerant leaked After Evacuation Replace the valve stem nuts and the service port nutGas Charging Connect the gauge to the charging cylinderExploded View Model B-MMC09FA-1, B-MMH09FA-1, B-MMC12FA-1, B-MMH12FA-1Model A-MMC18FA-1, A-MMH18FA-1 Model A-MMC24FA-1, A-MMH24FA-1 Model A-MMC36FA-1, A-MMH36FA-1 Heat CONTROLLER, INC 08/06/2008