Heat Controller B-MMC12FA-1, B-MMH12FA-1 manual Function of control, Cooling Mode Operation

Page 41

Operation

Operation

Functionofcontrol

1. MAIN UNIT FUNCTION

DISPLAY

Operation Indicator

On while in appliance operation, off while in appliance pause

Flashing if unit is disconnected or has experienced a short in the thermistor (3 seconds off/0.5 sec on).

Sleep Timer Indicator

• On while in sleep time mode, off when sleep timer mode is canceled or appliance operation is paused.

Timer Indicator

• On while in timer mode (on/off), off when timer mode is completed or canceled

Defrost Indicator

Off except when units is in hot start mode (heat pump model only) or while unit is running in defrost control mode.

Cooling Mode Operation

When the intake air temperature reaches 0.5°C(0.9°F) below the set point temp, the compressor and the out- door fan stop.

When it reaches 0.5°C(0.9°F) above the set point temp, they start to operate again.

Compressor ON Temp

Set point Temp+0.5°C(0.9°F)

Compressor OFF Temp

Set point Temp-0.5°C(0.9°F)

While the compressor is running, operating with the airflow speed set by the remote control. While compressor is off, fan operates at low speed regardless of the set point.

Soft Dry Operation Mode

When the dehumidification operation input by the remote control is received, the intake air temperature is detected and the set point temp is automatically set according to the intake air temperature.

26°C(78.8°F) Intake Air Temp

25°C(77°F)

24°C(75.2°F) Intake Intake Air Temp<26°C(78.8°F)

Intake Air Temp-1°C(30.2°F)

18°C(64.4°F) Intake Intake Air Temp<24°C(75.2°F)

Intake Air Temp-0.5°C(31.1°F)

Intake Air Temp<18°C(64.4°F)

18°C(64.4°F)

While the compressor is off, the indoor fan repeats low airflow speed and stop.

While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification operation and 4-min compressor off repeat.

Compressor ON Temp. Set point Temp+0.5°C(0.9°F) Compressor OFF Temp. Set point Temp-0.5°C(0.9°F)

In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.

Heating Mode Operation

When the intake air temp reaches +3°(37.4°F)…above the set point temp, the compressor is turned off. When below the set point temp, the compressor is turned on.

Compressor ON Temp. Set point Temp. Compressor OFF Temp. Set point Temp.+3°C(37.4°F)

While compressor is on, the indoor fan is off when the indoor pipe temp. is below 20°C(68°F), when above 27°C(80.6°F) , it operates at low speed. When the indoor pipe temp is between 20°C(68°F) and 27°C(80.6°F), it

- 41 -

Service Manual

Image 41
Contents Heat CONTROLLER, INC Table of Contents KBtu/h 3 rooms Symbols Used in this ManualKBtu/h 2 rooms Installation Safety PrecautionsBe sure not to do Be sure to follow the instruction Control box securely Cuit and breakerDo not install the product on a Do not install, remove, or reDefective installation stand Do not allow water to run into electric partsFlooded or submerged, contact When the product is soaked Be cautious that water canNever enter the product Use two or more people to lift and transport the product Install the drain hose to ensure that Keep level even whenInstalling the product Operational Do not use the remote is the batteries have leaked Selecting the locationOutdoor Unit Seaside applications and installationSplit Type Indoor DimensionsIndoor Unit 18kBtu/h Outdoor Unit24kBtu/h 36kBtu/h UE2Indoor Unit Type Wall Mounted Model Product SpecificationsMMC18FA-1 MMH18FA-1 Outdoor Unit Multiple piping modelsMMC24FA-1 MMH24FA-1 MMC36FA-1 MMH36FA-1 Installation Tools InstallationInstallation Parts Selecting the best location 18 / 24 kBtu/h KBtu/h Piping length and elevationMulti Piping Type Drilling the hole in the wall Installing Installation PlateStandard TypeFlaring work Flaring Work and Connection of PipingIndoor Connecting the PipingCheck Wrap the insulation material around the all connections Indoor unit installationFor left rear piping Wrap the insulation material around the connecting por- tion Bad case Good caseRemote Control Preparationoptional Outdoor unit 36 kBtu/h OutdoorOutdoor unit 18/24 kBtu/h Tions ETL recognized and CSA certified Connect the cable to the Indoor unitOutdoor unit Connect the cable to the Outdoor unitHow to connect wiring to the terminals Methods of connecting the cableModel Drain piping Checking the drainageTo check the drainage Insulating the Pipe and Special Piping Applications Secure the taped piping along the exterior wall usingLeak checking Air Purging and EvacuationPreparation Leakage testFinishing the job Repeat evacuation procedure for each indoor unitEvacuation Additional ChargingSplit Type Test RunningSoft Dry Operation Mode Cooling Mode OperationHeating Mode Operation OperationFuzzy Operation for Cooling Defrost ControlHeatingFuzzy Operation Off-Timer Operation On-Timer OperationAirflow Speed Selection Fuzzy Operation for DehumidificationSleep Timer Operation Off-Timer = On-Timer OperationChaos Swing Mode Chaos Natural Wind ModeBuzzer Sound Forced OperationSplit Type Indoor Unit Function of Indoor UnitFunction of Outdoor Unit Cooling Model , Heat Pump Model Remote Control OperationTime Setting Buttons Used to adjust the time To remove the Grille from the Chassis DisassemblyTo remove the Control Box To remove the Motor Cover Indoor Unit Schematic DiagramElectronic Control Device TMP87CM41F Outdoor UnitRY-4WAY RY-LIQ RY-GAS RY-FANL RY-FANH Indoor Unit Outdoor Unit Wiring DiagramMMC24FA-1 Bottom View Component LocationsDisplay Assembly Split Type 6871A20680 Component side Solder side Refrigeration Cycle Diagram Troubleshooting GuideMMC18FA-1 MMH18FA-1MMH24FA-1 MMH36FA-1 MMC36FA-1Outdoor Error Indoor ErrorError Indicator Self-diagnosis FunctionTrouble analysis Cycle Troubleshooting GuideProcedure Specification Remedy Electronic Parts Troubleshooting GuideProduct doesnt operate with the remote controller Check Point Comp. on Comp. OFF Compressor/Outdoor Fan dont operateNector Trouble 4 When indoor Fan does not operateRY-COMP-B Voltage of Connectors according to Indoor Fan SpeedWhen Vertical Louver does not operate Check Point Error CodeIndoor air sensor Indoor inlet pipe sensorCommunication line is shorted at GND Description Cause of error Check point & Normal conditionPower input AC 230V.Outdoor, Indoor Comp OFF Pipe sensor Outdoor air sensorCondensor pipe sensor Way Valve Liguid Side Way, 3-way ValvePumping down ProcedureAll the refrigerant leaked Replace the valve and service port capsEvacuation Gas Charging Replace the valve stem nuts and the service port nutAfter Evacuation Connect the gauge to the charging cylinderModel B-MMC09FA-1, B-MMH09FA-1, B-MMC12FA-1, B-MMH12FA-1 Exploded ViewModel A-MMC18FA-1, A-MMH18FA-1 Model A-MMC24FA-1, A-MMH24FA-1 Model A-MMC36FA-1, A-MMH36FA-1 08/06/2008 Heat CONTROLLER, INC