Instructions to installation
The distance between air duct outlet and air conditioner outlet is according to the length of actually installed air duct and in service behavior of the static pressure terminal: Installation sketch map for long and short air duct is showed below, when connect to short air duct, using low static terminal (terminal color is white), the distance between air duct outlet and air conditioner outlet is no more than 0.5m; when connect to long air duct, using middle static terminal (terminal color is red), the distance between air duct outlet and air conditioner outlet could be within 5m at this point.
Figure 5
sling dog | joint of air diffuser |
| |
drain piping |
|
air return duct |
|
transition air outlet | air diffuser |
air return shutter air duct duct |
|
Drain piping of condensed water should keep a downhill grade of 1% or more. Use insulating pipe to cover the drain piping of condensed water to keep warmth.
As figure shown, suspend and install the unit.
Figure 6 | M8 broad foundation bolt |
|
M8 suspension screw | Unit |
|
M8 broad lock ring
M8 nut
Installation for air duct of indoor unit
1. Installation of air discharge duct
This type of unit uses circular air duct with its caliber of 180mm.
An additional transitive air duct is necessary for the circular air duct to connect to the air supply inlet. It should be also connected to its respective air diffuser separately. See Fig.1. Adjust the wind speed of each air diffuser outlet to keep in line on the whole, so as to meet a demand of the air conditioner in the room.
| flexible joint or | transitive air duct |
Indoor unit | static pressure | circular air duct |
| box |
joint of air diffuser
air diffuser
Fig1: Duct connected