Haier AD122XLERA Instructions to installation, Piping Connection, Connecting pipe, O.D.mm, ΓΏ6.35

Page 22
Piping Connection

Pipe expansion dimensions as follows: Instructions to installation

Piping Connection

AD092XLERA

AD122XLERA

AD142XLERA

AD182XLERA

Flare connection

Gas pipe

3-way valve

 

 

Indoor

 

Outdoor

Unit

 

unit

 

Liquid

2-way valve

 

pipe

 

Flare connection

Flare connection

Gas pipe

3-way valve

 

A

 

 

Indoor

 

Outdoor

Unit

 

unit

 

Liquid

2-way valve

 

pipe

 

Flare connection

To gas pipe Connecting pipeInstalling torqueIncreased installingO.D.(mm)torque (N-m)ÿ6.35

A(adaptor, from ÿ9.52 9.52 to ÿ12.70 12.7)

To outdoor unit

Pipe expansion dimensions as follows:

Pipe diameter ÿ

Size A (mm)

6.35 mm (1/4")

0.8 ~ 1.5

9.52 mm (3/8")

1.0 ~ 1.8

12.7 mm (1/2")

1.2 ~ 2.0

 

 

Correct

 

 

Incorrect

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Slope Damage Bur Partial Overlong

A Manual background

Pipe expander

Manual background The connection of indoor unit pipes must use double spanners.

Manual background The installing torque shall be as given in the following table.

Connecting pipe

Installing torque

Increased installing

O.D.(mm)

(N-m)

torque (N-m)

ÿ6.35

11.8 (1.2kgf-m)

13.7 (1.4 kgf-m)

ÿ9.52

24.5 (2.5kgf-m)

29.4 (3.0 kgf-m)

ÿ12.70

49.0 (5.0 kgf-m)

53.9 (5.5 kgf-m)

Double-spanner operation

20

Image 22
Contents AD092XLERA AD122XLERA AD142XLERA AD182XLERA No.0010577705R410A MULTI SPLIT SERIES ROOM AIR CONDITIONER Notes for safety ContentsSafety precautions Trouble shootingCautions Safety Instructions and WarningsDisposal of the old air conditioner Specifications CautionsSafety precautions CAUTIONS Safety precautionsWiring CAUTIONS ON INSTALLATIONSafety precautions LocationNotes for safety Parts and Functions INDOOR UNITTrouble shooting The followings are not malfuncitionUnit fails to start Trouble shootingUsing Directions Customer Need-to-knowInsufficient cooling or heating When trouble happensCooled air blown out when heating Insufficient coolingInstructions to installation 1. Safety precautions2. Preparation for installation PRECAUTIONInstructions to installation 5.Installation procedure 3. Accessories for installation4. Choose the installation place Instructions to installationInstructions to installation a h g1. Installation of air discharge duct Installation for air duct of indoor unitInstructions to installation Instructions to installation 2. Installation of air return duct3. Air duct insulation Installing the suspension screwOriginal concrete slab RequirementsInstructions to installation Steel reinforcement structureHose Instructions to installationPipe and insulation material Insulation treatmentConnecting pipe Instructions to installationPipe expansion dimensions as follows Installing torque3.Installation check 1. Indoor unit communication addresses setting2.Installation check and trial operation Instructions to installation4.Trial operation Wiring methodsInstructions to installation 4 Wiring of indoor unit Failure codeInstructions to installation Communication cable Shield wire H05RN-F2X1.5 mm2Failure code Failure code 3.Failrue codes maked with * are resumableHAIER GROUP