Haier AD182XLERA, AD142XLERA Requirements, Instructions to installation, Original concrete slab

Page 20
Original concrete slab

Steel reinforcement structure Instructions to installation

Original concrete slab

Use hole hinge, hole plunger or hole bolt.

Steel reinforcement structure

Use steel angle or new support steel angle directly.

Hanging bolt

Suspension screw

Support steel angle

Hanging of the indoor unit

Fasten the nut on the suspension screw and then hang the suspension screw in the Tslot of the suspension part of the unit.

Aided with a level meter, adjust level of the unit within 5 mm.

Hanging of the indoor unit CAUTION

In order to drain water normally, the drain pipe shall be processed as specified in the installation manual and shall be thermal insulated to avoid dew generation. Improper hose connection may cause indoor water leakage.

Requirements

Requirements The indoor drain pipe shall be thermal insulated.

Manual background The connection part between the drain pipe and the indoor unit shall be insulated so as to prevent dew generation.

Manual background The drain pipe shall be slant downwards (greater than 1/100). The middle part shall not be of Stype elbow, otherwise abnormal sound will be produced.

Manual background The horizontal length of the drain pipe shall be less than 20 m. In case of long pipe, supports shall be provided every 1.5 ñ 2m to prevent wavy form.

Manual background Central piping shall be laid out according to the following figure.

Manual background Take care not to apply external force onto the drain pipe connection part.

1.5m~2m

Support

 

 

 

 

 

 

 

 

 

Insulation

 

 

 

 

 

 

Down slope

 

 

 

(supplied by

 

 

 

above 1/100

S type elbow

the user)

 

 

 

 

 

 

To the largest (app. 10cm)

VP30

Down slope above 1/100

Wall

Outside

Slant

Drain pipe (supplied by the user)

18

Image 20
Contents R410A MULTI SPLIT SERIES ROOM AIR CONDITIONER No.0010577705AD092XLERA AD122XLERA AD142XLERA AD182XLERA Contents Safety precautionsNotes for safety Trouble shootingDisposal of the old air conditioner Safety Instructions and WarningsCautions Specifications CautionsSafety precautions CAUTIONS Safety precautionsCAUTIONS ON INSTALLATION Safety precautionsWiring LocationNotes for safety Parts and Functions INDOOR UNITTrouble shooting The followings are not malfuncitionUnit fails to start Trouble shootingUsing Directions Customer Need-to-knowWhen trouble happens Cooled air blown out when heatingInsufficient cooling or heating Insufficient coolingInstructions to installation 1. Safety precautionsInstructions to installation PRECAUTION2. Preparation for installation 3. Accessories for installation 4. Choose the installation place5.Installation procedure Instructions to installationInstructions to installation a h gInstructions to installation Installation for air duct of indoor unit1. Installation of air discharge duct 2. Installation of air return duct 3. Air duct insulationInstructions to installation Installing the suspension screwRequirements Instructions to installationOriginal concrete slab Steel reinforcement structureInstructions to installation Pipe and insulation materialHose Insulation treatmentInstructions to installation Pipe expansion dimensions as followsConnecting pipe Installing torque1. Indoor unit communication addresses setting 2.Installation check and trial operation3.Installation check Instructions to installationInstructions to installation Wiring methods4.Trial operation Failure code Instructions to installation4 Wiring of indoor unit Communication cable Shield wire H05RN-F2X1.5 mm2Failure code Failure code 3.Failrue codes maked with * are resumableHAIER GROUP