Failure code
| TROUBLE SHOOTING | FAILURE CODE | POSSIBLE REASONS | |
| (indoor unit) | (CHECK THE WIRED | ||
| REMOTE CONTROLLER) |
| ||
|
|
| ||
| Abnormal communication |
|
| Wrong connection, or use the wired controller |
| between wired controller and | 07 | * | |
| be disconnected, faulty PCB | |||
| indoor unit PCB | |||
|
|
| ||
| Drainage system abnormal | 08 | * | The |
| position, or the float switch broken down or the | |||
|
|
| float switch disconnected,or at wrong position | |
|
|
|
|
|
| Indoor unit address repeated | 09 |
| Wrong setting of indoor unit address |
|
|
|
|
|
| Abnormal communication | 0E |
| Faulty indoor unit PCB |
| between chip TMP/807 and chip |
| ||
| TMP/846 |
|
|
|
| TROUBLE SHOOTING | FAILURE CODE | POSSIBLE REASONS | |
| (CHECK THE WIRED | |||
| (ourdoor unit) | |||
| REMOTE CONTROLLER) |
| ||
|
|
| ||
|
|
|
|
|
| Faulty defrost sensor Te | 14 | * | Sensor disconnected, or broken, or short circuit |
|
| Sensor disconnected, or broken, or short circuit | ||
| Faulty sensor Tao | 15 | ||
|
| * |
| |
| Faulty sensor Ts |
| Sensor disconnected, or broken, or short circuit | |
| 16 | * | ||
|
|
| ||
| Faulty sensor Td | 17 | Sensor disconnected, or broken, or short circuit | |
|
| * | Over current of the system, or broken of the | |
| Input overcurrent | 19 | ||
|
| current sensor,or malfunction with indoor or | ||
|
|
|
| outdoor fan motors, or faulty PCB. |
|
|
|
|
|
|
|
|
| High pressure switch is disconnected, or high |
| System high pressure | 1E | * | pressure switch worked, or Tc too high and |
| faulty outdoor fan motor when cooling, or | |||
| protection | |||
|
| faulty indoor fan motors when heating, or | ||
|
|
|
| |
|
|
|
| refrigerant overabundance |
|
|
|
| Low pressure switch is disconnected, or low |
| System low pressure | 1F | * | pressure switch worked, or Te too low and |
| faulty outdoor fan motors when heating, or | |||
| protection | |||
|
| faulty indoor fan motor when cooling, or | ||
|
|
|
| |
|
|
|
| refrigerant shortage |
|
|
|
|
|
| IPM protection | 20 |
| IPM over current, or short circuit, or IPM |
|
| temperature too high, or IPM input voltage | ||
|
|
|
| too low,or faulty SPDU(or ISPM). |
| EEPROM fault | 21 |
| Faulty outdoor unit PCB |
|
|
|
| |
|
|
|
|
|
| Over hot protection of |
|
| Serious lack of refrigerant of the system, or |
| 22 |
| the ambient temperature too high, or PMVs be | |
| compressor |
| ||
|
|
| blocked | |
|
|
|
| |
|
|
|
|
|
| Over hot protection of SPDU | 23 |
| Ambient tempreatrue too high, or outdoor fan |
| (or ISPM) |
| be blocked, or bad air circulation of outdoor unit | |
|
|
|
|
|
| DC fan motor fault | 24 |
| Fan is blocked, or the terminal is disconnected |
|
|
|
| from the PCB |
|
|
|
|
|