Haier AD092XLERA, AD182XLERA Indoor unit communication addresses setting, Installation check

Page 23
1. Indoor unit communication addresses setting

CAUTION! FAIL TO DO THIS, THE UNIT WILL NOT WORK. Instructions to installation

1. Indoor unit communication addresses setting

CAUTION! FAIL TO DO THIS, THE UNIT WILL NOT WORK.

This kind of indoor units can only set the address by using the Dip Switches.

(1).Please note that the address must be set as following: Indoor unit that connect to valve A, the address must be 1; Indoor unit that connect to valve B, the address must be 2; Indoor unit that connect to valve C, the address must be 3; Indoor unit that connect to valve D, the address must be 4;

(2). Address setting procedure when using the DIP switches SW01 and SW03. A. The DIP switches SW01 and SW03 are on the indoor unit PCB.

B. Change the position of DIP 7 of SW01 from OFF to ON, if fail to do this, the addresses set by SW03 will not work.

C. Use SW03 to set the addresses as following (DO NOT CHANGE OTHER DIP SWITCHES):

SW01

SW03

INDOOR UNIT

OUTDOOR

 

 

ADDRESS

VALVE

 

1

2

3

4

5

6

7

8

 

1

2

3

4

5

6

7

8

 

1

A

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

6

7

8

 

2

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

6

7

8

 

3

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

6

7

8

 

4

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

2.Installation check and trial operation

Check the Layout of the Drain Pipe and Connection Wires, and also the piping and address setting. The drain pipe should be placed underneath, and the connection wires should be placed upside; and the drain pipe especially the section inside the machine and indoors must be wound up with insulating material to preserve heat. The drain pipe shall be sloped and no concave and convex shall occur along the whole pipe. And the cases as the right figure indicates shall not occur.

3.Installation check

2.Installation check and trial operation Is power supply voltage required?

3.Installation check Is water completely drained to outdoors?

Manual background Are power wire and connection wires between indoor and outdoor units correctly connected?

Manual background Is any gas leaked from the pipe connectors?

Manual background Are series numbers of the terminals on the indoor and outdoor units corresponding to each other?

Manual background Is the connection section of the auxiliary pipe insulated? Is the indoor unit fixed firmly? Manual background Is noise big?

21

Image 23
Contents R410A MULTI SPLIT SERIES ROOM AIR CONDITIONER No.0010577705AD092XLERA AD122XLERA AD142XLERA AD182XLERA Trouble shooting ContentsSafety precautions Notes for safetyDisposal of the old air conditioner Safety Instructions and WarningsCautions Cautions SpecificationsSafety precautions Safety precautions CAUTIONSLocation CAUTIONS ON INSTALLATIONSafety precautions WiringNotes for safety INDOOR UNIT Parts and FunctionsThe followings are not malfuncition Trouble shootingTrouble shooting Unit fails to startCustomer Need-to-know Using DirectionsInsufficient cooling When trouble happensCooled air blown out when heating Insufficient cooling or heating1. Safety precautions Instructions to installationInstructions to installation PRECAUTION2. Preparation for installation Instructions to installation 3. Accessories for installation4. Choose the installation place 5.Installation procedurea h g Instructions to installationInstructions to installation Installation for air duct of indoor unit1. Installation of air discharge duct Installing the suspension screw 2. Installation of air return duct3. Air duct insulation Instructions to installationSteel reinforcement structure RequirementsInstructions to installation Original concrete slabInsulation treatment Instructions to installationPipe and insulation material HoseInstalling torque Instructions to installationPipe expansion dimensions as follows Connecting pipeInstructions to installation 1. Indoor unit communication addresses setting2.Installation check and trial operation 3.Installation checkInstructions to installation Wiring methods4.Trial operation Communication cable Shield wire H05RN-F2X1.5 mm2 Failure codeInstructions to installation 4 Wiring of indoor unitFailure code 3.Failrue codes maked with * are resumable Failure codeHAIER GROUP