Haier CWH12A, CWH18A Electrical Requirements, Recommended Grounding Method, Power Supply Cord

Page 6

Electrical Requirements

WARNING

Electrical Shock Hazard

Plug into a grounded 3 prong outlet.

Do not remove ground prong.

Do not use an adapter.

Do not use an extension cord.

Failure to follow these instructions can result in death, fire, or electrical shock.

Ground wire must be connected to the ground screw located in the lower right corner of the air conditioner when the air conditioner is in the cabinet.

The electrical ratings for your air conditioner are listed on the model and serial number label. The model and serial number label is located on the right-hand side of the air conditioner cabinet.

Specific electrical requirements are listed in the chart below. Follow the requirements for the type of plug on the power supply cord.

Power Supply Cord Wiring Requirements

115-volt (103.5 min. to 126.5 max.)

0 to 12 amps

 

 

15-amp time-delay fuse or

 

 

circuit breaker

 

 

Use on single outlet circuit only.

 

 

 

¹⁄₄"

230-volt (207 min. to 253 max.)

0 to 12 amps

(0.6 cm)

 

 

15-amp time-delay fuse or

 

 

 

 

 

 

circuit breaker

 

 

Use on single outlet circuit only.

Recommended Grounding Method

This air conditioner must be grounded. This air conditioner is equipped with a power supply cord having a grounded 3 prong plug. To minimize possible shock hazard, the cord must be plugged into a mating, grounded 3 prong outlet, grounded in accordance with all local codes and ordinances. If a mating outlet is not available, it is the customer's responsibility to have a properly grounded 3 prong outlet installed by a qualified electrical installer.

It is the customer's responsibility:

To contact a qualified electrical installer.

To assure that the electrical installation is adequate and in conformance with National Electrical Code, ANSI/NFPA 70 - latest edition, and all local codes and ordinances.

Copies of the standards listed may be obtained from:

National Fire Protection Association

One Batterymarch Park

Quincy, MA 02269

Power Supply Cord

NOTE: Your air conditioner’s device may differ from the ones shown.

A B

TEST

RESET

TEST

RESET

AB

A.Test button

B.Reset button

230-volt (207 min. to 253 max.)

 

 

0 to 16 amps

 

 

20-amp time-delay fuse or

 

 

circuit breaker

 

 

Use on single outlet circuit only.

 

 

 

¹⁄₂"

230-volt (207 min. to 253 max.)

0 to 24 amps

(1.3 cm)

 

 

30-amp time-delay fuse or

 

 

 

 

 

 

circuit breaker

 

 

Use on single outlet circuit only.

 

 

 

This room air conditioner is equipped with a power supply cord required by UL. This power supply cord contains state-of-the-art electronics that sense leakage current. If the cord is crushed, the electronics detect leakage current and power will be disconnected in a fraction of a second.

5

Image 6
Contents Climatiseurdepièce Table of Contents Table DES MatièresAIR Conditioner Safety Parts supplied Through-the-Wall InstallationTools and Parts Tools NeededWindow Installation Location RequirementsPower Supply Cord Electrical RequirementsRecommended Grounding Method To test your power supply cord Unpack the Air ConditionerRemove packaging materials Window Installation-Prepare the Cabinet Back viewBottom view Window Installation-Position Cabinet in window Complete Window Installation Windowsill ViewThrough-the-Wall Cabinet Installation Complete Installation Starting Your Air Conditioner Cool Only ModelsMode Fan Speed TemperatureTimer Delay Filter MonitorPower Using the Remote ControlTo clear Timer delay program To see or change the remaining time in hoursTimer Super ControlSleep Control Changing Air Direction Exhaust Air VentNormal Sounds Repairing Paint Damage Cleaning the Air FilterCleaning the Front Panel Annual MaintenanceAir conditioner blows fuses or trips circuit breakers Air conditioner seems to run too muchWater drips from cabinet into your house Assistance or Service IntheU.S.AInCanada Page Sécurité DU Climatiseur Votre sécurité et celle des autres est très importanteExigences D’INSTALLATION Exigences d’emplacementOutillage et pièces Installation dans une fenêtre 23 58,4 cmExigences électriques Méthode recommandée de liaison à la terre Cordon dalimentationPour tester le cordon dalimentation Instructions Dinstallation Déballage du climatiseurEnlèvement des matériaux demballage Installationdans unefenêtre-Préparationde la caisse Vue arrièreVue de dessous Installation dans une fenêtre-Préparationde la fenêtre Placez le boîtier dans la fenêtreVue du châssis de fenêtre Installation des rideaux latérauxAchever l’installation sur la fenêtre Vue du seuil du châssis de fenêtreOption 1-Moulure de bois, métal ou plastique Installation de la caisse dansun murInstallation du cadre de bois Option 2-Mur de plâtre sans moulureAchever l’installation Insérer le climatiseur dans la caisseUtilisation DU Climatiseur Mise en marche du climatiseurModèles du refroidissement seulement Fan Speed vitesse du ventilateur ModeFilter Monitor témoin du filtre Timer Delay minuterie différée TempératurePour voir ou modifier le temps résiduel en heures Power alimentation Utilisationde la télécommandeSystème de commande Smart Commande SuperCommande Sleep veille Timer MinuterieSons normaux Changement de direction de lairVentilation Pour voir le temps résiduel en heures ou le modifierEntretien DU Climatiseur DépannageLe climatiseur semble fonctionner trop longtemps Assistance OU Service AuxÉtats-UnisAuCanada Page Made In China