8.6.3 EIA-485

Figure 8.6.3a is the simplest setup with an EIA-485 bus connection to DSAi module "A" and with a Link Ports connection to DSAi module "B". These modules could be operating individually or as part of a cluster.

Only the "A" module EIA-485 port is connected to the PC and there is a Link Port connection between the "A" PLink and the "B" SLink.

When a DSAi module receives a message (the source is not important) it checks the message address to see if it matches its own address. If it matches, the module will use the message.

In the example Figure 8.6.3a, the PC is sending a message to module "A". The message address matches its own address so it uses the message

PC DSA

PILOT

485

 

CM1

 

SLink

 

 

 

 

 

DSA “A”

PLink

485

 

CM1

 

SLink

 

 

 

 

 

DSA “B”

PLink

Figure 8.6.3a EIA-485

Figure 8.6.3b illustrates what happens when the message is for another module, in this case module "B". If the message address does not match, DSAi module “A” will repeat the message out of all its communication ports except for the one where the message was received. As shown in Figure 8.6.3b, module "B" would get the message through the Link Ports.

The reason module “A” blindly repeats the message like this is that it does not know which communication port is connected to module "B" or to any other modules.

PC DSA

PILOT

MESSAGE

FOR "B"

485

CM1

SLink

 

DSA "A"

 

 

NO MATCH,

 

 

RESEND

 

 

PLink

 

If it received the message through the EIA-485 port, it would repeat the message to the SLink, the PLink and to the CobraNet CM-1 card, if installed.

This communication method of blindly passing on control messages is the basic principle behind the DSAi communication system. It is simple and works well. However, incorrectly configured control data wiring will lead to communication loops. Communication loops mean that communications will fail, often randomly.

485

CM1

SLink

 

DSA "B"

 

 

ADDRESS MATCHES,

 

USE IT

 

 

PLink

 

Figure 8.6.3b

EIA-485

8.6.4 EIA-485 CONSIDERATIONS

The EIA-485 connection is very durable when used correctly. It is capable of controlling many devices over very long distances. It is important to understand the limitations of this networking bus to avoid loss of communication. Three things are of primary importance.

1.Avoid T-branches: these will invariably cause loops somewhere in the system.

2.Avoid stubs or branches: these will disturb the bus impedance causing signal reflections and resulting data corruption.

3.Ensure the 120 ohm end of line termination is configured correctly. Incorrect termination means the same problem and results as in #2.

In the examples below, it does not matter if the modules in the system are configured into clusters or operated individually. Because of their length restrictions, where Link cables are shown, the modules so connected would be in close physical proximity.

39

Image 43
Contents Page Safety Precautions Read this First Precauciones DE Seguridad LEA Esto Primero EC Declaration of Conformity Contents Page Shipping Damage ContentsIntroduction UnpackingQuick Start Audio Signal ConnectionChapter Returning Products to EAWAC Mains Installation Daisy Chaining Audio and Computer Signal Between ModulesComputer Control Connection Signal End / Power End Physical InstallationDescription Signal ProcessingSystem Overview 4 DSAi Block Diagrams FeaturesElectronic Engineering Design Applications4a Angled Radiation Pattern Designing DSAi Systems DSAPilotLow Frequency Performance Comparison to Traditional ProductsAnalog Audio and EIA-485 Computer Control Installation2 Audio a & Audio B Recommended Conductor Gauge AWG to 18 AWG / 0.2 mm to 1 mm CobraNet Audio and Computer Control 3 Basic CobraNet DiagramCabling Fault Detect Supervisory Monitoring 3a Single DSAi Fault on 2 PowerCon Plug AC Mains Power Connection4 Fuse Grounding2 Signal End / Power End 3 DSAi Cluster Configurations 4a Wall Mounted 6 Mounting Height Lift the enclosure onto the structure-mounted Wall Brackets Initial Set-Up Acoustical InstallationOperational Functions OperationSignal Monitoring Normal Operation Operational Check ListOperational ‘DOS’ and ‘DONTS’ How to Contact EAW Maintenance and ServiceWarranty Service ItemsAppendices Inspections and MaintenanceDSA250i Only TroubleshootingEIA-485 CobraNet EIA-485 Network NotesSupport For CobraNet Support For EthernetDSAi Connections 3a EIA-485 Example 5c Example One path was to the EIA-485 port. So when B responds 6c Example Right Side Back Mechanical DrawingsRight Side Wall Bracket Full Scale