APPENDIX A BLOWER PERFORMANCE TABLES
DIRECT DRIVE
CPG060 DOWN SHOT
CPG060 DIRECT DRIVE DOWN SHOT
SPEED | EXTERNAL STATIC | STANDARD |
|
|
| |
PRESSURE (ESP) | AMPS | WATTS | RPM | |||
TAP | CFM | |||||
in w.c. |
|
|
| |||
|
|
|
|
| ||
|
|
|
|
|
| |
| 0.10 | 1237 | 1.64 | 180 | 638 | |
| 0.20 | 1191 | 1.75 | 194 | 682 | |
T1 | 0.30 | 1127 | 1.80 | 200 | 715 | |
| 0.40 | 1065 | 1.89 | 214 | 753 | |
| 0.50 | 994 | 1.97 | 220 | 797 | |
| 0.10 | 1437 | 2.13 | 248 | 687 | |
| 0.20 | 1384 | 2.24 | 254 | 726 | |
T2 | 0.30 | 1312 | 2.29 | 262 | 759 | |
| 0.40 | 1245 | 2.42 | 280 | 803 | |
| 0.50 | 1185 | 2.54 | 294 | 847 | |
| 0.10 | 1988 | 4.49 | 558 | 885 | |
| 0.20 | 1942 | 4.58 | 574 | 907 | |
| 0.30 | 1882 | 4.69 | 582 | 935 | |
T3 | 0.40 | 1847 | 4.80 | 600 | 962 | |
| 0.50 | 1784 | 4.87 | 612 | 990 | |
| 0.60 | 1762 | 4.97 | 626 | 1008 | |
| 0.70 | 1688 | 5.05 | 642 | 1039 | |
| 0.10 | 2106 | 5.14 | 650 | 924 | |
| 0.20 | 2050 | 5.26 | 670 | 951 | |
| 0.30 | 1993 | 5.32 | 678 | 969 | |
T4 | 0.40 | 1960 | 5.47 | 696 | 1001 | |
0.50 | 1920 | 5.54 | 706 | 1021 | ||
| 0.60 | 1880 | 5.61 | 726 | 1041 | |
| 0.70 | 1810 | 5.73 | 736 | 1072 | |
| 0.80 | 1760 | 5.81 | 750 | 1093 | |
| 0.90 | 1694 | 5.84 | 752 | 1122 | |
| 0.10 | 2199 | 5.87 | 762 | 968 | |
| 0.20 | 2146 | 5.96 | 772 | 989 | |
| 0.30 | 2121 | 6.06 | 788 | 1012 | |
| 0.40 | 2066 | 6.15 | 804 | 1039 | |
T5 | 0.50 | 2010 | 6.21 | 814 | 1056 | |
| 0.60 | 1978 | 6.32 | 834 | 1084 | |
| 0.70 | 1919 | 6.28 | 830 | 1102 | |
| 0.80 | 1837 | 6.22 | 814 | 1122 | |
| 0.90 | 1738 | 6.04 | 786 | 1127 |
NOTES:
Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM correction for wet coil = 4 %. 5 Ton models are shipped from the factory with speed tap set on T4.
27