Goodmans CPG SERIES installation manual Electrical Wiring, Power and Low Voltage Block Connections

Page 9

ELECTRICAL WIRING

WARNING

HIGH VOLTAGE!

DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

Electrical Code. If long wires are required, it may be neces- sary to increase the wire size to prevent excessive voltage drop. Wires should be sized for a maximum of 3% voltage drop.

CAUTION

TO AVOID PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, USE ONLY COPPER CONDUCTORS.

WARNING

HIGH VOLTAGE!

TO AVOID PERSONAL INJURY OR DEATH DUE TO

ELECTRICAL SHOCK, DO NOT TAMPER WITH FACTORY

WIRING. THE INTERNAL POWER AND CONTROL WIRING

OF THESE UNITS ARE FACTORY-INSTALLED AND HAVE

BEEN THOROUGHLY TESTED PRIOR TO SHIPMENT.

CONTACT YOUR LOCAL REPRESENTATIVE IF

ASSISTANCE IS REQUIRED.

CAUTION

TO PREVENT DAMAGE TO THE WIRING, PROTECT WIRING FROM SHARP EDGES. FOLLOW NATIONAL ELECTRICAL CODE AND ALL LOCAL CODES AND ORDINANCES. DO NOT ROUTE WIRES THROUGH REMOVABLE ACCESS PANELS.

CAUTION

CONDUIT AND FITTINGS MUST BE WEATHER-TIGHT TO PREVENT WATER ENTRY INTO THE BUILDING.

For unit protection, use a fuse or HACR circuit breaker that is in excess of the circuit ampacity, but less than or equal to the maximum overcurrent protection device. DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE.

All line voltage connections must be made through weather- proof fittings. All exterior power supply and ground wiring must be in approved weatherproof conduit.

The main power supply wiring to the unit and low voltage wiring to accessory controls must be done in accordance with these instructions, the latest edition of the National Electriacl Code (ANSI/NFPA 70), and all local codes and ordinances. All field wiring shall conform with the temperature limitations for Type T wire (63°F/35°C rise).

The main power supply for the CPG036XXX3,4,7 through CPG072 shall be three-phase, three wire. The power sup- ply for the CPG036XXX1 through CPG060 shall be single- phase, two wire. The unit is factory wired for the voltage shown on the unit’s data plate.

NOTE: If supply voltage is 208V, lead on primary of trans- former TRANS1 must be moved from the 230V to the 208V tap.

Main power wiring should be sized for the minimum wire ampacity shown on the unit’s database. Size wires in accor- dance with the ampacity tables in Article 310 of the National

CAUTION

TO PREVENT IMPROPER AND DANGEROUS OPERATION DUE TO WIRING ERRORS, LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. VERIFY PROPER OPERATION AFTER SERVICING.

NOTE: A weather-tight disconnect switch, properly sized for the unit total load, must be field installed. An external field supplied disconnect may be mounted on the exterior panel.

Ensure the data plate is not covered by the field-supplied disconnect switch.

Some disconnect switches are not fused. Protect the power leads at the point of distribution in accordance with the unit data plate.

The unit must be electrically grounded in accordance with local codes or, in the absence of local codes, with the latest edition of the National Electrical Code (ANSI-NFPA 70). A ground lug is provided for this purpose. Size grounding conductor in accordance with Table 250-95 of the National Electrical Code. Do not use the ground lug for connecting a neutral conductor.

Connect power wiring to the compressor contactor closest to the entrance located within the main control box.

MAIN POWER

LOW VOLTAGE

BLOCK

LOW VOLTAGE

ENTRANCE POWER THRU

THE CURB

Power and Low Voltage Block Connections

WARNING

FAILURE OF UNIT DUE TO OPERATION ON IMPROPER LINE VOLTAGE OR WITH EXCESSIVE PHASE UNBALANCE CONSTITUTES PRODUCT ABUSE AND WILL VOID YOUR WARRANTY AND MAY CAUSE SEVERE DAMAGE TO THE UNIT ELECTRICAL COMPONENTS.

9

Image 9
Contents CPG Series Safety Instructions Replacement PartsHigh Voltage General InformationUnit Location Clearances Roof TOP Duct Connections Roof Curb POST-INSTALLATION ChecksRigging Details Weights shown are belt drive with no accessories Power and Low Voltage Block Connections Electrical WiringAreas Without Convenience Outlet GAS Supply PipingInlet GAS Pressure GAS Piping Checks Propane GAS InstallationsVenting Condensate Drain Connection Circulating AIR and FiltersPRE-STARTUP Instructions STARTUP, ADJUSTMENTS, and ChecksPercent voltage unbalance Must not exceed 2% Three Phase Models OnlyRollout Protection Control Manifold Pressure Check PSC Motor Flame Sensor and Ignition Electrode Location Normal Sequence of OperationCheck rollout limit TroubleshootingAdjustment Input RatingInput Btu/Hr = Motor Sheave Adjustments AIR Flow AdjustmentsMaintenance PSC MotorCabinet Finish Maintenance Burner Flame CPG036 Direct Drive Horizontal CPG036 Direct Drive Down ShotCPG048 Direct Drive Horizontal CPG048 Direct Drive Down ShotCPG060 Direct Drive Down Shot CPG060 Direct Drive Horizontal CPG048 Standard Belt Drive Horizontal CPG036 Standard Belt Drive HorizontalCPG060 Standard Belt Drive Horizontal CPG072 Standard Belt Drive Horizontal806 744 CPG048 High Static Belt Drive Down Shot CPG036 High Static Belt Drive Down ShotCPG060 High Static Belt Drive Down Shot CPG072 High Static Belt Drive Down ShotCPG048 High Static Belt Drive Horizontal CPG036 High Static Belt Drive HorizontalCPG060 High Static Belt Drive Horizontal CPG072 High Static Belt Drive HorizontalAppendix B Electrical Data Appendix C Unit Dimensions Appendix D Wiring Diagrams IIC CPG036480451D Single Phase 240V/60HZ Direct Drive208-240/1/60 0140L00510 REV a INSTALLER/SERVICEMANCPG0360480901D Single Phase 240V/60HZ Direct Drive 208-240/1/60 0140L00506 REV a YL/PK CPG0060*1D Single Phase 240V/60HZ Direct Drive240/1/60 0140L00429 REV B CPG060*3D Three Phase 208-230V/60HZ Direct YL PKS1 TB1 CPG060*3D Three Phase 208-230V/60HZ Direct Drive Motor Wires CPG036048*3D Three Phase 208-230V/60HZ Direct Drive208-240/3/60 0140L00512 REV B CPG036048*3D Three Phase 230V/60HZ Direct Drive 208-240/3/60 0140L00507 REV B 460-575/3/60 0140L00870 REV B 460-575/3/60 0140L00870 REV B Y1 C LPS HPS PLF High Voltage VMR IGN CPG0360480454B Three Phase 575V/60HZ Belt DriveCPG0360480453B Three Phase 240V/60HZ Belt Drive 208-240/3/60 0140L00979 REV B Goodman Manufacturing Company, L.P