Lincoln Electric IM836-B manual Auxiliary Power Receptacles, Standby Power Connections

Page 14

A-6

INSTALLATION

A-6

 

 

 

AUXILIARY POWER RECEPTACLES

Start the engine and set the “IDLER” control switch to the “High Idle” mode. Voltage is now correct at the receptacles for auxiliary power. This must be done before a tripped GFCI receptacle can be reset prop- erly. See the MAINTENANCE section for detailed information on testing and resetting the GFCI recep- tacle.

The auxiliary power of the RANGER 305D consists of two 20 Amp-120 VAC (5-20R) duplex receptacles with GFCI protection and one 50 Amp 120/240 VAC (14-50R) receptacle. The 240 VAC receptacle can be split for single phase 120 VAC operation.

The auxiliary power capacity is 10,000 watts Peak, 9,500 Watts Continuous of 60 Hz, single phase power. The auxiliary power capacity rating in watts is equivalent to volt-amperes at unity power factor. The max permissible current of the 240 VAC output is 40 amps. The 240 VAC output can be split to provide two separate 120 VAC outputs with a max permissi- ble current of 40 Amps per output to two separate 120 VAC branch circuits (these circuits cannot be paralleled). Output voltage is within ± 10% at all loads up to rated capacity. All auxiliary power is protected by circuit breakers.

The 120 V auxiliary power receptacles should only be used with three wire grounded type plugs or approved double insulated tools with two wire plugs. The current rating of any plug used with the system must be at least equal to the current capacity of the associated receptacle.

NOTE: The 240 V receptacle has two 120 V circuits, but are of opposite polarities and cannot be paral- leled.

STANDBY POWER CONNECTIONS

The RANGER 305D is suitable for temporary, stand- by or emergency power using the engine manufactur- erʼs recommended maintenance schedule.

The RANGER 305D can be permanently installed as a standby power unit for 240 VAC, 3 wire, single phase, 40 amp service. Connections must be made by a licensed electrician who can determine how the 120/240 VAC power can be adapted to the particular installation and comply with all applicable electrical codes.

Install the double-pole, double-throw switch between the power company meter and the premis- es disconnect. Switch rating must be the same or greater than the customerʼs premises disconnect and service over current protection.

Take necessary steps to assure load is limited to the capacity of the RANGER 305D by installing a 50 amp, 240 VAC double pole circuit breaker. Maximum rated load for each leg of the 240 VAC auxiliary is 40 amperes. Loading above the rated output will reduce output voltage below the allow- able - 10% of rated voltage which may damage appliances or other motor-driven equipment and may result in overheating of the RANGER 305D engine and/or alternator windings.

Install a 50 amp, 120/240 VAC plug (NEMA Type 14-50) to the double-pole circuit breaker using No. 6, 4 conductor cable of the desired length. (The 50 amp, 120/240 VAC plug is available in the optional K802R plug kit or as part number T12153-9.)

Plug this cable into the 50 Amp, 120/240 Volt recep- tacle on the RANGER 305D case front.

RANGER 305D

Image 14
Contents Ranger 305D Safety California Proposition 65 WarningsElectric Shock can kill Welding and Cutting Sparks can Cause fire or explosion IiiPrécautions DE Sûreté Sûreté Pour Soudage a LʼArcThank You Table of Contents Section F Section DSection E P492AIR Cleaner Engine Idler Muffler Engine Protection InstallationHeight Width Depth Weight Lubrication Emissions Fuel System GovernorSafety Precautions Location and Ventilation Vehicle Mounting PRE-OPERATION Engine Service Towing OILElectrical Connections Welding Output Cables Cable InstallationWelding Terminals Total Combined Length of Electrode and Work CablesAuxiliary Power Receptacles Standby Power ConnectionsConnection of Ranger 305D to Premises Wiring Across The-Arc Model Connection of Lincoln Electric Wire FeedersConnection of LN-15 to the Ranger 305D Control Cable ModelTerminals on Connection of Prince XL Spool GUN to the Ranger 305DOperation General DescriptionWeld Mode Selector Switch Figure B.1Start Push Button Wire Feeder Voltmeter SwitchGlow Plug Push Button Welder Operation Starting the EngineStopping the Engine Typical Ranger 305D Fuel ConsumptionDownhill Pipe Welding TIG WeldingTypical Current Ranges 1 for Tungsten ELECTRODES2 Table B.2Wire WELDING-CV ARC GougingAuxiliary Power Ranger 305D Extension Cord Length RecommendationsAccessories Field Installed Options / AccessoriesKubota D722 Diesel Engine MaintenanceEngine Maintenance Components Kubota D722 Diesel Engine Engine Oil Change AIR CleanerEngine Oil Refill capacities Without oil filter replacement Oil Filter ChangeService Instructions & Installation Tips 3MAINTENANCED-3Bleeding the Fuel System Cooling SystemTightening the FAN Belt For CodeServicing Optional Spark Engine AdjustmentBattery Maintenance ArrestorWelder / Generator Maintenance Gfci Receptacle Testing and RESET- Ting ProcedureTroubleshooting HOW to USE Troubleshooting GuideContact your local Lincoln Authorized Field Service FacilityLincoln Welding without a control cable Functioning properly / linkage Faulty control cable. Repair or Field Service Facility Your local Lincoln AuthorizedDiagrams Diagrams Diagrams Diagrams Diagrams Engine Welders LN/-8CONNECTION Diagram Diagrams Diagrams Diagrams Diagrams Enhanced For Codes 11188 Dimension Print M20334Ranger 305D Precaucion Warnung