Lincoln Electric IM10028-B manual Welder Operation, Auxiliary Power

Page 13

A-6

INSTALLATION

A-6

 

 

 

WELDER OPERATION

WELDER OUTPUT

Maximum Open Circuit Voltage at 3700 RPM is 80 Volts RMS.

Duty Cycle is the percentage of time the load is being applied in a 10 minute period. For example, a 60% duty cycle represents 6 minutes of load and 4 minutes of no load in a 10 minute period. Duty Cycle for the EAGLE™ 10,000 Plus is 100%.

EAGLE™ 10,000 Plus

Constant Current

210 Amps DC @ 25 Volts

 

 

120/240 VOLT DUAL VOLTAGE RECEPTACLE

The 120/240 volt receptacle can supply up to 38 amps of 240 volt power to a two wire circuit, up to 38 amps of 120 volts power from each side of a three wire circuit (up to 76 amps total). Do not connect the 120 volt circuits in parallel. Current sensing for the automatic idle feature is only in one leg of the three wire circuit as shown in the following column.

GND

AUXILIARY POWER

The EAGLE™ 10,000 Plus can provide up to 9,000 watts of 120/240 volts AC, single phase 60Hz power for continuous use, and up to 10,500 watts of 120/240 volts AC, single phase 60Hz power surge use. The front of the machine includes three receptacles for connecting the AC power plugs; one 50 amp 120/240 volt NEMA 14-50R receptacle and two 20 amp 120 volt NEMA 5-20R receptacles. Output voltage is within +/-10% at all loads up to rated capacity.

All auxiliary power is protected by circuit breakers. The 120V has 20 Amp circuit breakers for each duplex receptacle. The 120/240V Single Phase has a 40 Amp 2-pole Circuit Breaker that disconnects both hot leads simultaneously.

CAUTION

Do not connect any plugs that connect to the power receptacles in parallel.

------------------------------------------------------------------------

Start the engine and set the “IDLER” control switch to the desired operating mode. Set the “CONTROL” to

10.Voltage is now correct at the receptacles for auxil- iary power.

120 V

240 V

120 V*

*Current Sensing for Automatic Idle. (Receptacle viewed from front of Machine)

120 V DUPLEX RECEPTACLES

The 120V auxiliary power receptacles should only be used with three wire grounded type plugs or approved double insulated tools with two wire plugs.

The current rating of any plug used with the system must be at least equal to the current load through the associated receptacle.

MOTOR STARTING

Most 1.5 hp AC single phase motors can be started if there is no load on the motor or other load connected to the machine, since the full load current rating of a

1.5hp motor is approximately 20 amperes (10 amperes for 240 volt motors). The motor may be run at full load when plugged into only one side of the duplex receptacle. Larger motors through 2 hp can be run provided the receptacle rating as previously stated is not exceeded. This may necessitate 240V operation only.

EAGLE™ 10,000 Plus Extension Cord Length Recommendations

(Use the shortest length extension cord possible sized per the following table.)

Current

Voltage

Load

 

Maximum Allowable Cord Length in ft. (m) for Conductor Size

(Amps)

Volts

(Watts)

14 AWG

12 AWG

10 AWG

8 AWG

6 AWG

4 AWG

15

120

1800

30

(9)

40

(19)

75

(23)

125

(38)

175

(53)

300

(91)

20

120

2400

 

 

30

(9)

50

(15)

88

(27)

138

(42)

225

(69)

15

240

3600

60

(18)

75

(23)

150

(46)

225

(69)

350

(107)

600

(183)

20

240

4800

 

 

60

(18)

100

(30)

175

(53)

275

(84)

450

(137)

38

240

9000

 

 

 

 

50

(15)

90

(27)

150

(46)

225

(69)

Conductor size is based on maximum 2.0% voltage drop.

EAGLE™ 10,000 PLUS

Image 13
Contents Eagle 10,000 Plus Safety Depends on YouCalifornia Proposition 65 Warnings SafetySafety Welding and Cutting Sparks can Cause fire or explosion Précautions DE Sûreté IvSAFETYThank You Table of Contents Installation Machine Grounding Safety PrecautionsSpark Arrester TowingBattery Connections PRE-OPERATION ServiceGasoline Fuel only GasolineWelding Output Cables Additional Safety PrecautionTotal Combined Length of Electrode and Work Cables Angle of OperationInstructions Additional Safety PrecautionsLocation / Ventilation StackingWelder Operation Auxiliary PowerDevices Without Addi Tional Resistive Type Loads Simultaneous Welding and Power Auxiliary Power While WeldingStandby Power Connections Connection of Eagle 10,000 Plus to Premises Wiring Operation Engine SwitchGENERAL DESCRIPTION Welder Controls Function and Operation23 H.P. Command CH23S Range SwitchEagle 10,000 Plus Approximate Fuel Consumption Control DialBREAK-IN Period STARTING/SHUTDOWN InstructionsStarting the Engine Stopping the EngineTypical Current Ranges 1 for Tungsten ELECTRODES2 Welding ProcessStick Constant Current Welding Scratch Start TIG Constant Current WeldingARC Gouging 5OPERATIONB-5K1745-1 Welding GAS Cylinder LOX Tank Holder AccessoriesStick RECOMMENDED EQUIPMENTTIG K1783-4 TIG TorchSafety Precautions MaintenanceRoutine Maintenance Engine OIL ChangeOIL Filter Change AIR Cleaner and Other MaintenanceEngine Adjustments HOW to USE Troubleshooting Guide TroubleshootingTroubleshooting Troubleshooting Diagrams M22195 Dimension PrintEagle 10,000 Plus Eagle 10,000 Plus Precaucion Warnung