OPERATION | ||
|
|
|
PARALLELING
When paralleling machines in order to combine their outputs, all units must be operated in the
AUXILIARY POWER OPERATION
If a GFCI receptacle is tripped, See the MAINTE- NANCE section for detailed information on testing and resetting the GFCI receptacle.
Start the engine and set the IDLER control switch to the desired operating mode. Full power is available regardless of the welding control settings, if no weld- ing current is being drawn.
The auxiliary power of the AIR VANTAGE® 500 KUB- OTA consists of two 20
The auxiliary power capacity is 12,000 watts of 60 Hz, single phase power or 20,000 watts of 60Hz, three phase power. The auxiliary power capacity rating in watts is equivalent to
The maximum permissible current of the 240 VAC output is 50 A. The 240 VAC single phase output can be split to provide two separate 120 VAC outputs with a maximum permissible current of 50 A per output to two separate 120 VAC branch circuits. Output voltage is within ± 10% at all loads up to rated capacity.
NOTE: The two 120V GFCI modules, receptacles and the two 120V circuits of the 120/240V receptacle are connected to different phases and cannot be paral- leled.
The auxiliary power receptacles should only be used with three wire grounded type plugs or approved dou- ble insulated tools with two wire plugs.
The current rating of any plug used with the system must be at least equal to the current capacity of the associated receptacle.
SIMULTANEOUS WELDING AND AUXIL- IARY POWER LOADS
It must be noted that the above auxiliary power ratings are with no welding load. Simultaneous welding and power loads are specified in table B.5. The permissi- ble currents shown assume that current is being drawn from either the 120 VAC or 240 VAC supply (not both at the same time).
TAbLE b.5 AIR VANTAGE® 500 KUbOTA SIMULTANEOUS WELDING AND POWER LOADS
WELD AMPS 0 100 200 250 300 400 500
PLUS
1PHASE
WATTS AMPS
12,000 50
12,000 50
12,000 50
12,000 50
10,000 42
5,600 | 23 |
0 | 0 |
OR
3PHASE
WATTS AMPS
20,000 50
17,800 43
14,000 34
12,000 29
10,000 24
5,600 | 13 |
0 | 0 |
OR
bOTH 1 AND 3 PHASE
WATTS | AMPS |
50 | |
50 | |
50 | |
12,000 | |
10,000 | |
5,600 | |
0 | 0 |
TAbLE b.6
AIR VANTAGE® 500 KUbOTA Extension Cord Length Recommendations (Use the shortest length extension cord possible sized per the following table.)
Current | Voltage | Load |
|
| Maximum Allowable Cord Length in ft. (m) for Conductor Size |
|
| |||||||
(Amps) | (Volts) | (Watts) | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG | 4 AWG | ||||||
15 | 120 | 1800 | 30 | (9) | 40 | (12) | 75 | (23) | 125 | (38) | 175 | (53) | 300 | (91) |
15 | 240 | 3600 | 60 | (18) | 75 | (23) | 150 | (46) | 225 | (69) | 350 | (107) | 600 | (183) |
20 | 120 | 2400 |
|
| 30 | (9) | 50 | (15) | 88 | (27) | 138 | (42) | 225 | (69) |
20 | 240 | 4800 |
|
| 60 | (18) | 100 | (30) | 175 | (53) | 275 | (84) | 450 | (137) |
25 | 240 | 6000 |
|
|
|
| 90 | (27) | 150 | (46) | 225 | (69) | 250 | (76) |
30 | 240 | 7200 |
|
|
|
| 75 | (23) | 120 | (37) | 175 | (53) | 300 | (91) |
38 | 240 | 9000 |
|
|
|
|
|
| 100 | (30) | 150 | (46) | 250 | (76) |
50 | 240 | 12000 |
|
|
|
|
|
|
|
| 125 | (38) | 200 | (61) |
Conductor size is based on maximum 2.0% voltage drop.
AIR VANTAGE® 500 KUbOTA