Outback Power Systems FX 2024 T installation manual AC and DC Grounding Requirements

Page 10

AC AND DC GROUNDING REQUIREMENTS

Connect only to a grounded, permanent wiring system. Ensure there is only one neutral-ground connection in the system at any time. Some codes require this connection be made at the main panel only.

If the system has a generator, its neutral-ground connection will probably need to be disengaged.

For all installations, the negative battery conductor should be bonded to the grounding system at one (and only one) point in the system.

The FX should never be positive grounded.

The equipment ground on each is marked with this symbol:

Box lug for grounding the FX chassis

7

Image 10
Contents FX and VFX Series INVERTER/CHARGER Page Warranty Introduction Table of Contents FX Series Inverter/Charger Models Important Safety Instructions Initial InspectionPersonal Precautions Generate Explosive Gases During Normal OperationDC Wiring Origination System ProtectionAC Wiring Origination AC Wiring Compartment BoardAC and DC Grounding Requirements Turbo FAN Cover FX-DCC DC Compartment Cover AC Conduit Plate Battery Terminal CoversFX-DCA DC Conduit Adapter Mounting Control Terminal Wiring Block Jumper LOW Voltage TerminalsWire Connections Follow these steps to wire the FX to your systemTorque Requirements Connection Torque in Pound MeasuresAC Neutral OUT/AC Neutral AC Wiring Notes for the NON-MOBILE FXAC HOT OUT Chassis GroundAC Wiring Notes for the Mobile FX AC Neutral OUT/AC NeutralLOW-VOLTAGE Wiring Inverter and ON/OFFAuxiliary Output AUX + / AUX RTS, MATE/HUB Wiring RJ-45 jack connects Mate or HUB to FX using CAT5 cableSample Installations Single FX SystemSeries or SERIES/PARALLEL Dual FX Configuration Series/Parallel Using Two FXs Series/Parallel Using Four FXs Paralleled Dual FX System SERIES/PARALLEL Quad FX System Phase FX System Three-Phase System Generator Auto Start GEN Mobile FX InformationInstallation Check List Mate HUBRecommended FX DC Voltage Range Appendix RatingsNominal AC Output Voltage of AN FX System Maximum DC Input CurrentAC Input Operating Voltage Range Maximum Current for Battery ChargerRated DC Input Current Maximum AC Input CurrentAC Input Frequency Range Maximum Continuous Output PowerMaximum AC Output Current Wire Sizes Maximum Overcurrent Protection AmpacityMaintenance Warranty OutBack Power Systems Two Year Limited WarrantyExtended Warranty Application U.S. and Canada only Product Registration