Outback Power Systems FX 2024 T installation manual Phase FX System

Page 27

3-PHASE FX SYSTEM

This system produces 120VAC per phase and 208VAC from phase to phase. There can only be one FX per phase on a 3-phase system.

The non-Mobile AC wiring from the AC source and to the AC loads must handle 60 amps AC.

All other non-Mobile AC wiring must handle a capacity of 60 amps AC; Mobile must handle 30 amps AC.

This system can power continuously up to 10.8kW of loads depending on which model is used.

Connecting more power than the continuous rating of the FX may cause breakers to trip or the FX to shut off its AC output.

The jumper in the HUB must be moved for 3-phase configuration (please see the HUB Installation and User Guide).

Note: Program the bottom FX as Master (3ph MASTER) and the two lower FXs as 3-phase Slaves

(3ph SLAVE). Keep the phases in order: phase one is connected to the FX programmed L1; phase two is connected to L2; and phase three to L3 (or phases A, B, and C to inverters A, B, and C).

24

Image 27
Contents FX and VFX Series INVERTER/CHARGER Page Warranty Introduction Table of Contents FX Series Inverter/Charger Models Initial Inspection Important Safety InstructionsGenerate Explosive Gases During Normal Operation Personal PrecautionsSystem Protection DC Wiring OriginationAC Wiring Compartment Board AC Wiring OriginationAC and DC Grounding Requirements AC Conduit Plate Battery Terminal Covers Turbo FAN Cover FX-DCC DC Compartment CoverFX-DCA DC Conduit Adapter Mounting LOW Voltage Terminals Control Terminal Wiring Block JumperFollow these steps to wire the FX to your system Wire ConnectionsConnection Torque in Pound Measures Torque RequirementsChassis Ground AC Wiring Notes for the NON-MOBILE FXAC HOT OUT AC Neutral OUT/AC NeutralAC Neutral OUT/AC Neutral AC Wiring Notes for the Mobile FXInverter and ON/OFF LOW-VOLTAGE WiringAuxiliary Output AUX + / AUX RJ-45 jack connects Mate or HUB to FX using CAT5 cable RTS, MATE/HUB WiringSingle FX System Sample InstallationsSeries or SERIES/PARALLEL Dual FX Configuration Series/Parallel Using Two FXs Series/Parallel Using Four FXs Paralleled Dual FX System SERIES/PARALLEL Quad FX System Phase FX System Three-Phase System Generator Auto Start Mobile FX Information GENMate HUB Installation Check ListMaximum DC Input Current Appendix RatingsNominal AC Output Voltage of AN FX System Recommended FX DC Voltage RangeMaximum AC Input Current Maximum Current for Battery ChargerRated DC Input Current AC Input Operating Voltage RangeMaximum Continuous Output Power AC Input Frequency RangeMaximum AC Output Current Maximum Overcurrent Protection Ampacity Wire SizesMaintenance OutBack Power Systems Two Year Limited Warranty WarrantyProduct Registration Extended Warranty Application U.S. and Canada only