Outback Power Systems FX 2024 T Maximum Overcurrent Protection Ampacity, Wire Sizes

Page 35

MAXIMUM OVERCURRENT PROTECTION AMPACITY

This rating specifies the proper overcurrent protection ampacity.

OBDC breakers are panel-mount circuit breakers.

Class T DC fuses are terminal-mounted and should always be used in conjuncture with a disconnect mechanism.

FXs used in home installations should use properly sized DC circuit breakers.

A DC breaker includes both overcurrent protection and disconnect capability.

OutBack Power Systems recommends Class T fuses for marine installations where a DC disconnect is not required.

MODEL

AMPACITY

DC BREAKER

DC FUSE

 

 

 

 

FX2012(M)T

260 amps

OBDC-250

Class T-400 (Mobile Only)

 

 

 

 

FX2024(M)T

175 amps

OBDC-175

Class T-300 (Mobile Only)

 

 

 

 

FX2532(M)T

175 amps

OBDC-175

Class T-300 (Mobile Only)

 

 

 

 

FX2548T

100 amps

OBDC-100

Not Recommended

 

 

 

 

VFX2812(M)

260 amps

OBDC-250

Class T-400 (Mobile Only)

 

 

 

 

VFX3524(M)

260 amps

OBDC-250

Class T-400 (Mobile Only)

 

 

 

 

VFX3232(M)

175 amps

OBDC-175

Class T-300 (Mobile Only)

 

 

 

 

VFX3648

175 amps

OBDC-175

Not Recommended

 

 

 

 

WIRE SIZES

The following chart contains information on wire sizes, the DC resistance of the wires and the corresponding diameters and areas of these wires. This information can be used to calculate the

voltage drop of the wires or to find

an equivalent

wire size.

 

 

 

 

 

 

 

 

 

SIZE

DC

 

CROSS-SECTIONAL AREA

APPROXIMATE DIAMETER

 

(AWG)

 

 

 

 

 

 

 

Resistance in Ohms

 

 

 

 

 

 

 

(1000 feet)

 

 

 

 

 

 

 

INCHES

 

MILLIMETERS

INCHES

MILLIMETERS

 

 

 

14

3.14

 

.0032

 

2.08

.078

1.98

12

1.98

 

.0051

 

3.31

.101

2.57

10

1.24

 

.0082

 

5.26

.126

3.20

8

0.78

 

.0130

 

8.37

.162

4.11

6

0.50

 

.0206

 

13.30

.215

5.46

4

0.31

 

.0328

 

21.15

.269

6.83

2

0.19

 

.0521

 

33.62

.337

8.56

1

0.15

 

.0657

 

42.41

.376

9.55

1/0

0.12

 

.0829

 

53.50

.423

10.74

2/0

0.10

 

.1045

 

67.43

.508

12.90

3/0

0.08

 

.1318

 

85.01

.576

14.63

4/0

0.06

 

.1662

 

107.20

.645

16.38

32

Image 35
Contents FX and VFX Series INVERTER/CHARGER Page Warranty Introduction Table of Contents FX Series Inverter/Charger Models Initial Inspection Important Safety InstructionsGenerate Explosive Gases During Normal Operation Personal PrecautionsSystem Protection DC Wiring OriginationAC Wiring Compartment Board AC Wiring OriginationAC and DC Grounding Requirements FX-DCA DC Conduit Adapter AC Conduit Plate Battery Terminal CoversTurbo FAN Cover FX-DCC DC Compartment Cover Mounting LOW Voltage Terminals Control Terminal Wiring Block JumperFollow these steps to wire the FX to your system Wire ConnectionsConnection Torque in Pound Measures Torque RequirementsChassis Ground AC Wiring Notes for the NON-MOBILE FXAC HOT OUT AC Neutral OUT/AC NeutralAC Neutral OUT/AC Neutral AC Wiring Notes for the Mobile FXInverter and ON/OFF LOW-VOLTAGE WiringAuxiliary Output AUX + / AUX RJ-45 jack connects Mate or HUB to FX using CAT5 cable RTS, MATE/HUB WiringSingle FX System Sample InstallationsSeries or SERIES/PARALLEL Dual FX Configuration Series/Parallel Using Two FXs Series/Parallel Using Four FXs Paralleled Dual FX System SERIES/PARALLEL Quad FX System Phase FX System Three-Phase System Generator Auto Start Mobile FX Information GENMate HUB Installation Check ListMaximum DC Input Current Appendix RatingsNominal AC Output Voltage of AN FX System Recommended FX DC Voltage RangeMaximum AC Input Current Maximum Current for Battery ChargerRated DC Input Current AC Input Operating Voltage RangeMaximum AC Output Current Maximum Continuous Output PowerAC Input Frequency Range Maximum Overcurrent Protection Ampacity Wire SizesMaintenance OutBack Power Systems Two Year Limited Warranty WarrantyProduct Registration Extended Warranty Application U.S. and Canada only