MAXIMUM OVERCURRENT PROTECTION AMPACITY
This rating specifies the proper overcurrent protection ampacity.
•OBDC breakers are
•Class T DC fuses are
•FXs used in home installations should use properly sized DC circuit breakers.
•A DC breaker includes both overcurrent protection and disconnect capability.
•OutBack Power Systems recommends Class T fuses for marine installations where a DC disconnect is not required.
MODEL | AMPACITY | DC BREAKER | DC FUSE |
|
|
|
|
FX2012(M)T | 260 amps | Class | |
|
|
|
|
FX2024(M)T | 175 amps | Class | |
|
|
|
|
FX2532(M)T | 175 amps | Class | |
|
|
|
|
FX2548T | 100 amps | Not Recommended | |
|
|
|
|
VFX2812(M) | 260 amps | Class | |
|
|
|
|
VFX3524(M) | 260 amps | Class | |
|
|
|
|
VFX3232(M) | 175 amps | Class | |
|
|
|
|
VFX3648 | 175 amps | Not Recommended | |
|
|
|
|
WIRE SIZES
The following chart contains information on wire sizes, the DC resistance of the wires and the corresponding diameters and areas of these wires. This information can be used to calculate the
voltage drop of the wires or to find | an equivalent | wire size. |
|
| |||
|
|
|
|
|
|
| |
SIZE | DC |
| APPROXIMATE DIAMETER | ||||
| (AWG) |
|
|
|
|
|
|
| Resistance in Ohms |
|
|
|
|
|
|
| (1000 feet) |
|
|
|
|
|
|
| INCHES |
| MILLIMETERS | INCHES | MILLIMETERS | ||
|
|
| |||||
14 | 3.14 |
| .0032 |
| 2.08 | .078 | 1.98 |
12 | 1.98 |
| .0051 |
| 3.31 | .101 | 2.57 |
10 | 1.24 |
| .0082 |
| 5.26 | .126 | 3.20 |
8 | 0.78 |
| .0130 |
| 8.37 | .162 | 4.11 |
6 | 0.50 |
| .0206 |
| 13.30 | .215 | 5.46 |
4 | 0.31 |
| .0328 |
| 21.15 | .269 | 6.83 |
2 | 0.19 |
| .0521 |
| 33.62 | .337 | 8.56 |
1 | 0.15 |
| .0657 |
| 42.41 | .376 | 9.55 |
1/0 | 0.12 |
| .0829 |
| 53.50 | .423 | 10.74 |
2/0 | 0.10 |
| .1045 |
| 67.43 | .508 | 12.90 |
3/0 | 0.08 |
| .1318 |
| 85.01 | .576 | 14.63 |
4/0 | 0.06 |
| .1662 |
| 107.20 | .645 | 16.38 |
32