Outback Power Systems FX 2024 T AC Input Frequency Range, Maximum AC Output Current

Page 34

MAXIMUM AND DEFAULT AC INPUT AND DC (bulk stage) OUTPUT VALUES

FX2012(M)T

AC Max = 12 AAC (Default = 10 AAC)

DC Max = 100 ADC

 

 

 

 

FX2524(M)T

AC Max = 14 AAC (Default = 12 AAC)

DC Max = 55

ADC

FX2532(M)T

AC Max = 14 AAC (Default = 12 AAC)

DC Max = 40

ADC

 

 

 

 

FX3048T

AC Max = 14 AAC (Default = 12 AAC)

DC Max = 35

ADC

 

 

 

VFX2812(M)

AC Max = 16 AAC (Default = 14 AAC)

DC Max = 125 ADC

VFX3524(M)

AC Max = 20 AAC (Default = 18 AAC)

DC Max = 85

ADC

 

 

 

 

VFX3232(M)

AC Max = 20 AAC (Default = 18 AAC)

DC Max = 60

ADC

 

 

 

 

VFX3648

AC Max = 20 AAC (Default = 18 AAC)

DC Max = 45

ADC

 

 

 

 

AC INPUT FREQUENCY RANGE

Note: If the AC input source is out of the range noted below, the FX will not connect or stay connected.

All FX Models

56 - 64 Hz

MAXIMUM AC OUTPUT CURRENT

This is the amount of surge current that the FX will quickly supply for a split second. Depending on the size of the surge, the FX can be overloaded for a minimum time of 5 seconds to a maximum time of 30 minutes.

All 12 VDC FXs

56 AAC per FX for 1 millisecond

 

 

All Other FXs

70 AAC per FX for 1 millisecond

 

 

MAXIMUM CONTINUOUS OUTPUT POWER

An FX Series Inverter/Charger’s model number indicates its maximum continuous output power by changing the last two digits to zeros. For instance, an FX2012MT has a maximum continuous output

power of 2000VA (volt-amps).

FX2012(M)T

2000 VA (VA = volt-Amps)

FX2024(M)T

2000 VA

FX2532(M)T

2500 VA

FX2548T

2500 VA

VFX2812(M)

2800 VA

VFX3524(M)

3500 VA

VFX3232(M)

3200 VA

VFX3648

3600 VA

 

 

31

Image 34
Contents FX and VFX Series INVERTER/CHARGER Page Warranty Introduction Table of Contents FX Series Inverter/Charger Models Important Safety Instructions Initial InspectionPersonal Precautions Generate Explosive Gases During Normal OperationDC Wiring Origination System ProtectionAC Wiring Origination AC Wiring Compartment BoardAC and DC Grounding Requirements Turbo FAN Cover FX-DCC DC Compartment Cover AC Conduit Plate Battery Terminal CoversFX-DCA DC Conduit Adapter Mounting Control Terminal Wiring Block Jumper LOW Voltage TerminalsWire Connections Follow these steps to wire the FX to your systemTorque Requirements Connection Torque in Pound MeasuresAC Neutral OUT/AC Neutral AC Wiring Notes for the NON-MOBILE FXAC HOT OUT Chassis GroundAC Wiring Notes for the Mobile FX AC Neutral OUT/AC NeutralLOW-VOLTAGE Wiring Inverter and ON/OFFAuxiliary Output AUX + / AUX RTS, MATE/HUB Wiring RJ-45 jack connects Mate or HUB to FX using CAT5 cableSample Installations Single FX SystemSeries or SERIES/PARALLEL Dual FX Configuration Series/Parallel Using Two FXs Series/Parallel Using Four FXs Paralleled Dual FX System SERIES/PARALLEL Quad FX System Phase FX System Three-Phase System Generator Auto Start GEN Mobile FX InformationInstallation Check List Mate HUBRecommended FX DC Voltage Range Appendix RatingsNominal AC Output Voltage of AN FX System Maximum DC Input CurrentAC Input Operating Voltage Range Maximum Current for Battery ChargerRated DC Input Current Maximum AC Input CurrentAC Input Frequency Range Maximum Continuous Output PowerMaximum AC Output Current Wire Sizes Maximum Overcurrent Protection AmpacityMaintenance Warranty OutBack Power Systems Two Year Limited WarrantyExtended Warranty Application U.S. and Canada only Product Registration