INSTALLATION | ||
|
|
|
2.Take necessary steps to assure load is limited to the capacity of the AIR VANTAGE® 500 CUMMINS by installing a 50 amp, 240 VAC double pole circuit breaker. Maximum rated load for each leg of the 240 VAC auxiliary is 50 amps. Loading above the rated output will reduce output voltage below the allowable
3.Install a 50 amp 120/240 VAC plug (NEMA Type
4.Plug this cable into the 50 Amp 120/240 Volt recep- tacle on the AIR VANTAGE® 500 CUMMINS case front.
Figure A.1 Connection of the AIR VANTAGE® 500 to Premises Wiring
|
| 240 VOLT | |
240 | Volt | POWER | |
120 VOLT | |||
60 Hz. | |||
COMPANY | |||
120 VOLT | |||
Service | |||
METER | |||
|
|
GROUNDED CONDUCTOR
NEUTRAL
BUS
N
LOAD
DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES
SERVICE OVERCURRENT
PROTECTION.
50 AMP, 120/240
VOLT PLUG240 VOLT NEMA TYPE
50AMP
240 VOLT
DOUBLE
POLE
CIRCUIT
BREAKER
GND
N
PREMISES
DISCONNECT AND
SERVICE
GROUNDOVERCURRENT PROTECTION
50 AMP, 120/240 VOLT
RECEPTACLENOTE: No. 6 COPPER CONDUCTOR CABLE SEE NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE
SIZE RECOMMENDATIONS.
AIR VANTAGE® 500 CUMMINS