Mitsubishi Electronics FR-A500L instruction manual Design information

Page 25

INSTALLATION AND WIRING

2.2.5 Design information

1)For commercial power supply-inverter switch-over operation, provide electrical and mechanical interlocks for MC1 and MC2 designed for commercial power supply-inverter switch-over.

When there is a commercial power supply-inverter switch-over circuit as shown below, the inverter will be damaged by leakage current from the power supply due to arcs generated at the time of switch-over or chattering caused by a sequence error.

2)If the machine must not be restarted when power is restored after a power failure, provide a magnetic contactor in the inverter’s primary circuit and also make up a sequence which will not switch on the start signal.

If the start signal (start switch) remains on after a power failure, the inverter will automatically restart as soon as the power is restored.

3)When the power supply used with the control circuit is different from the one used with the main circuit, make up a circuit which will switch off the main circuit power supply terminals R, S, T<L1, L2, L3 > when the power supply terminals , R1, S1<L11, L21> for the control circuit are switched off.

4)Since the input signals to the control circuit are on a low level, use two parallel micro signal contacts or a twin contact for contact inputs to prevent a contact fault.

5)Do not apply a large voltage to the contact input terminals (e.g. STF) of the control circuit.

6)Do not apply a voltage directly to the alarm output signal terminals (A, B, C). Always apply a voltage to these terminals via a relay coil, lamp, etc.

7)Make sure that the specifications and rating match the system requirements.

1) Commercial power supply-inverter switch-over

2) Low-level signal contacts

 

 

 

 

MC1

 

 

 

 

 

Interlock

 

 

Power

R, <L1>

U

IM

 

 

 

 

 

 

supply

S, <L2>

V

 

 

MC2

 

 

 

 

 

 

T, <L3>

W

Sneak current

 

 

 

Inverter

 

 

Low-level signal contacts

Twin contact

17

Image 25
Contents FR-A560L-375K~900K-NA This section is specifically about safety matters Fire Prevention Electric Shock PreventionInjury Prevention Wiring Transportation and installationAdditional instructions Trial runOperation Maintenance, inspection and parts replacementEmergency stop Disposing of the inverterContents Chapter Outline Installation Precautions for operationWiring Pre-Operation InformationBasic configuration Basic ConfigurationName Description Chapter Instructions for installation InstallationAt 5cm 1.97 inch Terminal connection diagram WiringDescription of main circuit terminals Symbol Terminal Name DescriptionDescription of control circuit terminals Terminal Name DescriptionType Symbol Terminal Name Description Wiring instructions Wiring of the main circuitTerminal block layout P1, P, N Connection procedure NA version(OR Version) Wiring of the control circuitChanging the control logic RUN DC24V How to use terminals STOP, CS and PC For RS-485 communication Connection to the PU connectorDesign information Chapter Operation Chapter Parameters Parameters Parameter List17, 18 R a M E T E R S 173 200 278 Protective Functions Error alarm definitions Errors AlarmsOHT Panel Unit Name Description Display FR-PU04 FR-DU04 OperatioName Details Main circuit error E,15 detailsCorrespondences between digital and actual characters To know the operating status at the occurrence of alarmResetting the inverter Alarm code outputOperation Panel Output Terminal Signal On-Off Display Alarm Code Alarm Output across B-C (FR-DU04 )Checking the operation panel display at alarm stop TroubleshootingOperation Check Point Remedy Panel Display Operation Panel Check Point Remedy Display Speed greatly differs from the setting Faults and check pointsMotor remains stopped Motor rotates in opposite directionPower lamp is not lit Operation mode is not changed properlyMotor current is large Speed does not increasePrecautions for maintenance and inspection Precautions for Maintenance and InspectionCheck items Periodic inspectionDielectric strength test Insulation resistance test using meggerDaily and Periodic Inspection Checking method PreparationModule device numbers and terminals to be checked Part Name Standard Replacement Description Interval Replacement of partsCooling fan Smoothing capacitorsMeasurement of voltages and currents Measurement of main circuit voltages, currents and powerMeasuring Points and Instruments Chapter Specifications Model specifications Standard specificationCommon specifications Temperature applicable for a short period in transit, etc Outline drawings FR-A560L-450K, 375KFR-A560L-530K~900K Specifications Appendices Appendix AppendixCheck the air flow direction Wiring between cooling fan and terminals is as followsAppendix Shipment case example Mitsubishi Electric Corporation