Mitsubishi Electronics FR-A500L instruction manual Type Symbol Terminal Name Description

Page 15

 

 

 

 

 

 

 

INSTALLATION AND WIRING

 

 

 

 

 

 

 

 

 

 

Type

Symbol

Terminal Name

 

 

Description

 

 

 

 

 

 

 

 

 

 

 

 

10E

 

10VDC, permissible load current

When the frequency setting potentiometer is

 

 

 

Frequency setting

10mA

 

connected in the factory-set state, connect it to

 

 

 

 

 

 

 

 

 

 

 

terminal 10.

 

 

 

 

 

power supply

5VDC, permissible load current

 

 

 

 

10

When it is connected to terminal 10E, change the

 

 

 

 

10mA

 

 

 

settingfrequencyAnalog

 

 

 

input specifications of terminal 2.

 

 

 

 

 

 

 

signalsInput

 

 

By entering 0 to 5VDC (0 to 10VDC), the maximum output frequency is reached at

 

 

 

 

 

 

 

 

2

Frequency setting

5V (or 10V) and I/O are proportional. Switch between input 0 to 5VDC (factory

 

 

 

(voltage)

setting) and 0 to 10VDC from operation terminal. Input resistance 10kΩ. Maximum

 

 

 

 

 

 

 

 

 

permissible voltage 20V.

 

 

 

 

 

 

Frequency setting

By entering 4 to 20mADC, the maximum output frequency is reached at 20mA and

 

 

 

4

I/O are proportional. This input signal is valid only when the AU signal is on. Input

 

 

 

(current)

 

 

 

 

resistance 250Ω. Maximum permissible current 30mA.

 

 

 

 

 

 

 

 

 

 

 

 

By entering 0 to ±5VDC 0 to ±10VDC, this signal is added to the frequency setting

 

 

 

1

Auxiliary frequency

signal of terminal 2 or 4. Switch between input 0 to ±5VDC and 0 to ±10VDC

 

 

 

setting

(factory setting) from operation terminal. Input resistance 10kΩ. Maximum

 

 

 

 

 

 

 

 

 

permissible voltage ±20V.

 

 

 

 

 

5

Frequency setting

Common to the frequency setting signal (terminal 2, 1 or 4) and analog output

 

 

 

input common

terminal AM. Do not earth.

 

 

 

 

 

 

 

 

 

 

Contact

 

 

Change-over contact output indicating that the output has been

 

 

 

 

 

(continuity across A-C), normal: continuity across B-C

 

 

 

 

 

 

stopped by the inverter protective function activated.

 

 

 

 

ABC

Alarm output

200VAC 0.3A, 30VDC 0.3A. Alarm: discontinuity across B-C

 

 

 

 

 

 

(discontinuity across A-C).

 

 

 

 

 

 

 

Switched low when the inverter output frequency is equal to or

 

 

 

 

 

 

higher than the starting frequency (factory set to 0.5Hz,

 

 

 

 

RUN

Inverter running

variable).

 

 

 

 

 

 

 

 

Switched high during stop or DC dynamic brake operation(note1)

 

 

 

 

 

 

Permissible load 24VDC 0.1A.

 

Output terminal

 

 

 

 

 

Switched low when the output frequency has reached within

function selection

 

 

 

SU

Up to frequency

±10% of the set frequency (factory setting, variable). Switched

(Pr. 190 to Pr.

 

signalsOutput

collectorOpen

high during acceleration, deceleration or stop(note 1). Permissible

195) change

 

 

 

load 24VDC 0.1A.

 

 

terminal

 

 

 

 

 

 

 

 

 

 

 

 

Switched low when the stall prevention function has caused

functions.

 

 

 

OL

Overload alarm

stall prevention to be activated. Switched high when stall

 

 

 

 

 

 

prevention is reset(note 1). Permissible load 24VDC 0.1A.

 

 

 

 

 

Instantaneous power

Switched low when instantaneous power failure or

 

 

 

 

IPF

undervoltage protection is activated(note 1). Permissible load

 

 

 

 

 

failure

24VDC 0.1A.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Switched low when the output frequency has reached or

 

 

 

 

FU

Frequency detection

exceeded the detection frequency set as appropriate. Switched

 

 

 

 

high when below the detection frequency(note 1). Permissible load

 

 

 

 

 

 

24VDC 0.1A

 

 

 

 

 

 

SE

Open collector output

Common to the RUN, SU, OL, IPF and FU terminals.

 

 

 

 

common

 

 

 

 

 

 

 

 

 

 

 

Pulse

 

 

 

 

Factory setting of output item:

 

 

 

FM

For meter

One selected from 16 monitoring

Frequency

 

 

 

items, such as output

 

Permissible load current 1mA

 

 

 

 

 

frequency, is output(note 2).

1440 pulses/second. at 60Hz

 

 

Analog

 

 

The output signal is proportional

Factory setting of output item:

 

 

 

AM

Analog signal output

to the magnitude of each

Frequency

 

 

 

 

monitoring item.

 

Output signal 0 to 10VDC

 

 

 

 

 

 

 

 

 

 

 

 

 

Permissible load current 1mA

 

Communication

RS485

 

 

· Overall length

: 500m

 

 

 

 

 

 

 

With the operation panel connector, communication can be made through RS-485.

 

 

 

 

 

· Conforming Standard

: EIA Standard RS-485

 

 

 

 

⎯⎯

PU connector

· Transmission format

: Multi-drop link

 

 

 

 

 

 

· Communication speed : Maximum 19200 baud rates

 

 

 

 

 

 

 

 

 

 

Note1: Low indicates that the open collector outputting transistor is on (conducts). High indicates that the transistor is off (does not conduct).

Note2: Not output while the inverter is reset.

7

Image 15
Contents FR-A560L-375K~900K-NA This section is specifically about safety matters Electric Shock Prevention Fire PreventionInjury Prevention Trial run Transportation and installationWiring Additional instructionsDisposing of the inverter Maintenance, inspection and parts replacementOperation Emergency stopContents Chapter Outline Pre-Operation Information Precautions for operationInstallation WiringBasic Configuration Basic configurationName Description Chapter Instructions for installation InstallationAt 5cm 1.97 inch Terminal connection diagram WiringTerminal Name Description Symbol Terminal Name DescriptionDescription of main circuit terminals Description of control circuit terminalsType Symbol Terminal Name Description Wiring instructions Wiring of the main circuitTerminal block layout P1, P, N Connection procedure NA version(OR Version) Wiring of the control circuitChanging the control logic RUN DC24V How to use terminals STOP, CS and PC For RS-485 communication Connection to the PU connectorDesign information Chapter Operation Chapter Parameters Parameters Parameter List17, 18 R a M E T E R S 173 200 278 Protective Functions Error alarm definitions Errors AlarmsOHT Panel Unit Name Description Display FR-PU04 FR-DU04 OperatioName Details Main circuit error E,15 detailsCorrespondences between digital and actual characters To know the operating status at the occurrence of alarmAlarm Code Alarm Output across B-C (FR-DU04 ) Alarm code outputResetting the inverter Operation Panel Output Terminal Signal On-Off DisplayTroubleshooting Checking the operation panel display at alarm stopOperation Check Point Remedy Panel Display Operation Panel Check Point Remedy Display Motor rotates in opposite direction Faults and check pointsSpeed greatly differs from the setting Motor remains stoppedSpeed does not increase Operation mode is not changed properlyPower lamp is not lit Motor current is largePeriodic inspection Precautions for Maintenance and InspectionPrecautions for maintenance and inspection Check itemsDielectric strength test Insulation resistance test using meggerDaily and Periodic Inspection Preparation Checking methodModule device numbers and terminals to be checked Smoothing capacitors Replacement of partsPart Name Standard Replacement Description Interval Cooling fanMeasurement of voltages and currents Measurement of main circuit voltages, currents and powerMeasuring Points and Instruments Chapter Specifications Model specifications Standard specificationCommon specifications Temperature applicable for a short period in transit, etc Outline drawings FR-A560L-450K, 375KFR-A560L-530K~900K Specifications Appendices Appendix AppendixCheck the air flow direction Wiring between cooling fan and terminals is as followsAppendix Shipment case example Mitsubishi Electric Corporation