Mitsubishi Electronics FR-A500L Operatio, Panel Unit Name Description Display FR-PU04 FR-DU04

Page 37

 

 

 

PROTECTIVE FUNCTIONS

 

 

 

 

Operatio

Paramete

 

 

n Panel

 

 

r Unit

Name

Description

Display

(FR-PU04)

 

 

(FR-DU04)

 

 

 

 

 

 

 

 

When the operation panel power (P5S of the PU connector) is shorted,

 

 

Operation panel power

this function shuts off the power output. At this time, the operation

E.CTE

⎯⎯

panel (parameter unit) cannot be used and RS-485 communication from

short circuit

 

 

the PU connector cannot be made. To reset, enter the RES signal or

 

 

 

 

 

 

switch power off, then on again.

 

 

 

Inverters of 7.5K or less contains a brake resistor. When the

 

 

 

regenerative brake duty from the motor has reached 85% of the

 

 

Brake resistor overheat

specified value, pre-alarm (RB indication) occurs. If the specified value

⎯⎯

⎯⎯

is exceeded, the brake circuit operation is stopped temporarily to protect

protection

 

 

the brake resistor from overheating. (If the brake is operated in this

 

 

 

 

 

 

state, regenerative overvoltage shut-off will occur.) When the brake

 

 

 

resistor has cooled, the brake operation is resumed.

E.MB1 to

⎯⎯

Brake sequence error

This function stops the inverter output if a sequence error occurs

MB7

during the use of the brake sequence function (Pr. 278 to Pr. 285).

 

 

E.14

E.14

DC fuse blown

The inverter output will stop if the DC fuse blows.

 

 

 

 

 

 

 

Brake unit cooling fin overheat, control board ambient temperature error,

E.15

E.15

Main circuit error

output overcurrent, cooling fan power supply error, capacitor

overcurrent, cooling fin overheat, gate power supply error.

 

 

 

 

 

 

Refer to the next page (page 27) for details.

Note: 1. If Pr. 195 (A, B, C terminal function selection) is as set in the factory.

2. The terminals used must be allocated using Pr. 190 to Pr. 195.

3. External thermal relay operation is only activated when "OH" is set in any of Pr. 180 to Pr. 186 (input terminal function selection).

4. Indicates that the stall prevention operation level has been set to 150% (factory setting). If this value is changed, stall prevention is operated at the new value.

5. Resetting method

When the protective function is activated and the inverter stops its output (the motor is coasted to a stop), the inverter is kept stopped. Unless reset, the inverter cannot restart. To reset the inverter, use any of the following methods: switch power off once, then on again; short reset terminal RES-SD for more than 0.1 seconds, then open; press the [RESET] key of the parameter unit (use the help function of the parameter unit). If RES-SD is kept shorted, the operation panel will show "Err." or the parameter unit will show that the inverter is being reset.

26

Image 37
Contents FR-A560L-375K~900K-NA This section is specifically about safety matters Fire Prevention Electric Shock PreventionInjury Prevention Wiring Transportation and installationAdditional instructions Trial runOperation Maintenance, inspection and parts replacementEmergency stop Disposing of the inverterContents Chapter Outline Installation Precautions for operationWiring Pre-Operation InformationBasic configuration Basic ConfigurationName Description Chapter Instructions for installation InstallationAt 5cm 1.97 inch Terminal connection diagram WiringDescription of main circuit terminals Symbol Terminal Name DescriptionDescription of control circuit terminals Terminal Name DescriptionType Symbol Terminal Name Description Wiring instructions Wiring of the main circuitTerminal block layout P1, P, N Connection procedure NA version(OR Version) Wiring of the control circuitChanging the control logic RUN DC24V How to use terminals STOP, CS and PC For RS-485 communication Connection to the PU connectorDesign information Chapter Operation Chapter Parameters Parameters Parameter List17, 18 R a M E T E R S 173 200 278 Protective Functions Error alarm definitions Errors AlarmsOHT Panel Unit Name Description Display FR-PU04 FR-DU04 OperatioName Details Main circuit error E,15 detailsCorrespondences between digital and actual characters To know the operating status at the occurrence of alarmResetting the inverter Alarm code outputOperation Panel Output Terminal Signal On-Off Display Alarm Code Alarm Output across B-C (FR-DU04 )Checking the operation panel display at alarm stop TroubleshootingOperation Check Point Remedy Panel Display Operation Panel Check Point Remedy Display Speed greatly differs from the setting Faults and check pointsMotor remains stopped Motor rotates in opposite directionPower lamp is not lit Operation mode is not changed properlyMotor current is large Speed does not increasePrecautions for maintenance and inspection Precautions for Maintenance and InspectionCheck items Periodic inspectionDielectric strength test Insulation resistance test using meggerDaily and Periodic Inspection Checking method PreparationModule device numbers and terminals to be checked Part Name Standard Replacement Description Interval Replacement of partsCooling fan Smoothing capacitorsMeasurement of voltages and currents Measurement of main circuit voltages, currents and powerMeasuring Points and Instruments Chapter Specifications Model specifications Standard specificationCommon specifications Temperature applicable for a short period in transit, etc Outline drawings FR-A560L-450K, 375KFR-A560L-530K~900K Specifications Appendices Appendix AppendixCheck the air flow direction Wiring between cooling fan and terminals is as followsAppendix Shipment case example Mitsubishi Electric Corporation