Mitsubishi Electronics FR-A500L instruction manual Common specifications

Page 54

SPECIFICATIONS

6.1.2Common specifications

 

Control system

 

Soft-PWM control/high carrier frequency PWM control (V/F control or advanced magnetic flux

 

 

vector control can be selected)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output frequency range

0.2 to 400Hz

 

 

 

 

 

 

 

 

 

Frequency

 

Analog input

0.015Hz/60Hz (terminal 2 input: 12 bits/0 to 10V, 11 bits/0 to 5V, terminal 1 input: 12 bits/10

 

setting

 

 

to +10V, 11 bits/5 to +5V)

 

 

specifications

resolution

 

Digital input

0.01Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency accuracy

Within ±0.2% of maximum output frequency (25°C ±10°C ) for analog input, within 0.01% of

 

 

set output frequency for digital input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage/frequency

Base frequency set as required between 0 and 400Hz. Constant torque or variable torque

Control

characteristic

 

pattern can be selected.

 

 

 

 

 

 

 

 

 

 

Starting torque

 

150%: At 0.5Hz (for advanced magnetic flux vector control)

 

 

 

 

 

 

 

 

 

 

 

 

Torque boost

 

Manual torque boost

 

 

 

 

 

 

 

Acceleration/deceleration

0 to 3600 sec (acceleration and deceleration can be set individually), linear or S-pattern

 

time setting

 

acceleration/deceleration mode can be selected.

 

 

 

 

 

 

DC dynamic brake

Operation frequency (0 to 120Hz), operation time (0 to 10 sec), voltage (0 to 30%) variable

 

 

 

 

 

Stall prevention operation

Operation current level can be set (0 to 150% variable), presence or absence can be

 

level

 

 

 

selected.

 

 

 

 

 

 

 

 

 

 

 

Frequency

 

Analog input

0 to 5VDC, 0 to 10VDC, 0 to ±10VDC, 4 to 20mADC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setting

 

Digital input

3-digit BCD or 12-bit binary using operation panel or parameter unit

 

 

signal

 

 

(when the FR-A5AX option is used)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Start signal

 

Forward and reverse rotation, start signal automatic self-holding input (3-wire input) can be

 

 

selected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Up to 15 speeds can be selected. (Each speed can be selected in the range of 0 to 400Hz.

 

 

 

Multi-speed selection

The operation speed can be changed from the operation panel or parameter unit during

 

 

 

 

 

 

operation.)

 

 

 

 

 

 

 

 

 

 

signals

 

Second, third

0 to 3600 sec (up to three different accelerations and decelerations

 

 

deceleration time

 

 

 

acceleration/

 

Input

 

selection

 

can be set individually.)

 

 

 

 

 

 

 

 

specifications

 

Current input selection

Input of frequency setting signal 4 to 20mADC (terminal 4) is selected.

 

 

 

 

 

 

 

Output stop

Maximum/minimum frequency setting, frequency jump operation, external thermal relay input

 

 

 

Instantaneous shut-off of inverter output (frequency, voltage)

 

 

 

 

Alarm reset

Alarm retained at the activation of protective function is reset.

 

Operational

 

 

 

 

 

selection, polarity reversible operation, automatic restart operation after instantaneous power

 

 

 

 

 

 

 

Operation functions

failure, commercial power supply-inverter switch-over operation, forward/reverse rotation

 

 

 

 

 

 

prevention, slip compensation, operation mode selection, offline auto tuning function, online

 

 

 

 

 

 

auto tuning function, PID control, programmed operation, computer link operation (RS-485)

 

 

 

 

 

 

 

 

 

 

 

 

 

5 different signals can be selected from inverter running, up to frequency, instantaneous

 

 

 

 

 

 

power failure (undervoltage), frequency detection, second frequency detection, third

 

 

 

 

 

 

frequency detection, during program mode operation, during PU operation, overload alarm,

 

 

 

Operating status

regenerative brake pre-alarm, electronic

overcurrent protection

pre-alarm, zero current

 

signals

 

 

 

 

detection, output current detection, PID

lower limit, PID upper

limit, PID forward/reverse

 

 

 

 

 

rotation, commercial power supply-inverter switch-over MC1, 2, 3, operation ready, brake

 

 

 

 

 

 

 

 

 

 

 

 

release request, fan fault and fin overheat pre-alarm minor fault. Open collector output.

 

 

 

 

 

 

 

 

 

Output

 

Alarm (inverter trip)

Contact output...change-over contact (230VAC 0.3A, 30VDC 0.3A)

 

 

 

Open collector...alarm code (4 bit) output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 signal can be selected from output frequency, motor current (steady or peak value), output

 

 

 

 

 

 

voltage, frequency setting, running speed, motor torque, converter output voltage (steady or

 

 

 

For meter

 

peak value), regenerative brake duty, electronic overcurrent protection load factor, input

 

 

 

 

 

 

power, output power, load meter, and motor exciting current. Pulse train output (1440

 

 

 

 

 

 

pulses/sec./full scale) and analog output (0 to 10VDC).

 

 

 

 

 

 

 

 

 

 

42

Image 54
Contents FR-A560L-375K~900K-NA This section is specifically about safety matters Electric Shock Prevention Fire PreventionInjury Prevention Additional instructions Transportation and installationWiring Trial runEmergency stop Maintenance, inspection and parts replacementOperation Disposing of the inverterContents Chapter Outline Wiring Precautions for operationInstallation Pre-Operation InformationBasic Configuration Basic configurationName Description Chapter Installation Instructions for installationAt 5cm 1.97 inch Wiring Terminal connection diagramDescription of control circuit terminals Symbol Terminal Name DescriptionDescription of main circuit terminals Terminal Name DescriptionType Symbol Terminal Name Description Wiring of the main circuit Wiring instructionsTerminal block layout P1, P, N Connection procedure Wiring of the control circuit NA version(OR Version)Changing the control logic RUN DC24V How to use terminals STOP, CS and PC Connection to the PU connector For RS-485 communicationDesign information Chapter Operation Chapter Parameters Parameter List Parameters17, 18 R a M E T E R S 173 200 278 Protective Functions Errors Alarms Error alarm definitionsOHT Operatio Panel Unit Name Description Display FR-PU04 FR-DU04Main circuit error E,15 details Name DetailsTo know the operating status at the occurrence of alarm Correspondences between digital and actual charactersOperation Panel Output Terminal Signal On-Off Display Alarm code outputResetting the inverter Alarm Code Alarm Output across B-C (FR-DU04 )Troubleshooting Checking the operation panel display at alarm stopOperation Check Point Remedy Panel Display Operation Panel Check Point Remedy Display Motor remains stopped Faults and check pointsSpeed greatly differs from the setting Motor rotates in opposite directionMotor current is large Operation mode is not changed properlyPower lamp is not lit Speed does not increaseCheck items Precautions for Maintenance and InspectionPrecautions for maintenance and inspection Periodic inspectionInsulation resistance test using megger Dielectric strength testDaily and Periodic Inspection Preparation Checking methodModule device numbers and terminals to be checked Cooling fan Replacement of partsPart Name Standard Replacement Description Interval Smoothing capacitorsMeasurement of main circuit voltages, currents and power Measurement of voltages and currentsMeasuring Points and Instruments Chapter Specifications Standard specification Model specificationsCommon specifications Temperature applicable for a short period in transit, etc FR-A560L-450K, 375K Outline drawingsFR-A560L-530K~900K Specifications Appendices Appendix AppendixWiring between cooling fan and terminals is as follows Check the air flow directionAppendix Shipment case example Mitsubishi Electric Corporation