Mitsubishi Electronics FR-A500L Basic Configuration, Basic configuration, Name Description

Page 9

1.2Basic Configuration

OUTLINE

1.2.1 Basic configuration

The following devices are required to operate the inverter. Proper peripheral devices must be selected and correct connections made to ensure proper operation. Incorrect system configuration and connections can cause the inverter to operate improperly, its life to be reduced considerably, and in the worst case, the inverter to be damaged.

Please handle the inverter properly in accordance with the information in each section as well as the precautions and instructions of this manual. (For connections of the peripheral devices, refer to the corresponding manuals.)

Name

Description

Power supply

Use the power supply within the permissible

power supply specifications of the inverter.

 

 

 

Earth leakage

The breaker should be selected with care

since a large inrush current flows in the

circuit breaker

inverter at power on.

(ELB) or no-fuse

The breaker must have overcurrent

breaker (NFB)

protection and earth leakage protection.

 

 

 

 

The magnetic contactor need not be

Magnetic

provided. When installed, do not use

contactor

it to start or stop the inverter. It might reduce

 

the inverter life.

 

 

 

The reactors must be used when the power

 

factor is to be improved or the inverter is

Reactors

installed near a large power supply system

(ten times or more of Inverter Output, and

 

 

wiring distance within 10m (32.81 feet) ).

 

Make selection carefully.

 

z The inverter life is influenced by ambient

 

temperature. The ambient temperature

 

should be as low as possible within the

 

permissible range.

Inverter

This must be noted especially when the

inverter is installed in an enclosure.

 

 

z Incorrect wiring might lead to inverter

 

damage. The control signal lines must be

 

kept fully away from the main circuit to

 

protect them from noise.

 

 

Devices

Do not connect a power capacitor, surge

connected to the

suppressor or radio noise filter to the output

output

side.

 

 

Ground

To prevent an electric shock, always ground

the motor and inverter.

 

 

 

2

Image 9
Contents FR-A560L-375K~900K-NA This section is specifically about safety matters Electric Shock Prevention Fire PreventionInjury Prevention Wiring Transportation and installationAdditional instructions Trial runOperation Maintenance, inspection and parts replacementEmergency stop Disposing of the inverterContents Chapter Outline Installation Precautions for operationWiring Pre-Operation InformationBasic Configuration Basic configurationName Description Chapter Instructions for installation InstallationAt 5cm 1.97 inch Terminal connection diagram WiringDescription of main circuit terminals Symbol Terminal Name DescriptionDescription of control circuit terminals Terminal Name DescriptionType Symbol Terminal Name Description Wiring instructions Wiring of the main circuitTerminal block layout P1, P, N Connection procedure NA version(OR Version) Wiring of the control circuitChanging the control logic RUN DC24V How to use terminals STOP, CS and PC For RS-485 communication Connection to the PU connectorDesign information Chapter Operation Chapter Parameters Parameters Parameter List17, 18 R a M E T E R S 173 200 278 Protective Functions Error alarm definitions Errors AlarmsOHT Panel Unit Name Description Display FR-PU04 FR-DU04 OperatioName Details Main circuit error E,15 detailsCorrespondences between digital and actual characters To know the operating status at the occurrence of alarmResetting the inverter Alarm code outputOperation Panel Output Terminal Signal On-Off Display Alarm Code Alarm Output across B-C (FR-DU04 )Troubleshooting Checking the operation panel display at alarm stopOperation Check Point Remedy Panel Display Operation Panel Check Point Remedy Display Speed greatly differs from the setting Faults and check pointsMotor remains stopped Motor rotates in opposite directionPower lamp is not lit Operation mode is not changed properlyMotor current is large Speed does not increasePrecautions for maintenance and inspection Precautions for Maintenance and InspectionCheck items Periodic inspectionDielectric strength test Insulation resistance test using meggerDaily and Periodic Inspection Preparation Checking methodModule device numbers and terminals to be checked Part Name Standard Replacement Description Interval Replacement of partsCooling fan Smoothing capacitorsMeasurement of voltages and currents Measurement of main circuit voltages, currents and powerMeasuring Points and Instruments Chapter Specifications Model specifications Standard specificationCommon specifications Temperature applicable for a short period in transit, etc Outline drawings FR-A560L-450K, 375KFR-A560L-530K~900K Specifications Appendices Appendix AppendixCheck the air flow direction Wiring between cooling fan and terminals is as followsAppendix Shipment case example Mitsubishi Electric Corporation