Carrier RHR, RVS, RDS006-060, RVR, RVC, RHS, 50RHC specifications Condition Acceptable Level

Page 17

Water Supply and Quantity — Check water supply. Water supply should be plentiful and of good quality. See Table 4 for water quality guidelines.

IMPORTANT: Failure to comply with the above required water quality and quantity limitations and the closed- system application design requirements may cause damage to the tube-in-tube heat exchanger that is not the responsi- bility of the manufacturer.

In all applications, the quality of the water circulated through the heat exchanger must fall within the ranges listed in the Water Quality Guidelines table. Consult a local water treat- ment firm, independent testing facility, or local water authority for specific recommendations to maintain water quality within the published limits.

GROUND-LOOP APPLICATIONS (Not Applicable to 50RHC,RVC Units) — Temperatures between 25 to 110 F and a cooling capacity of 2.25 to 3 gpm of flow per ton is rec- ommended. In addition to complying with any applicable codes, consider the following for system piping:

Limit piping materials to only polyethylene fusion in the buried sections of the loop.

Do not use galvanized or steel fittings at any time due to corrosion.

Avoid all plastic to metal threaded fittings due to the potential to leak. Use a flange fitted substitute.

Do not overtighten connections.

Route piping to avoid service access areas to unit.

Use pressure-temperature (P/T) plugs to measure flow of pressure drop.

Water Flow

Control Regulator

Valve

Boiler

Drains

Pressure-

Temperature

Plugs

Pressure

Tank

Water Out

Water In

From Pump

Shut-Off

Valve

Strainer – Field-Installed Accessory (16 to 20 mesh recommended for filter sediment)

Fig. 18 — Typical Ground-Water Piping Installation

 

Table 4 — Water Quality Guidelines

 

 

 

 

 

CONDITION

ACCEPTABLE LEVEL

 

pH

7 to 9 range for copper. Cupronickel may be used in the 5 to 9 range.

 

Total Hardness

Calcium and magnesium carbonate should not exceed 20 grains per gallon (350 ppm).

Iron Oxides

Less than 1 ppm.

 

 

Iron Bacteria

No level allowable.

 

 

Corrosion*

 

Max Allowable Level

Coaxial Metal

 

Ammonia, Ammonium Hydroxide

0.5 ppm

Cu

 

Ammonium Chloride, Ammonium Nitrate

0.5 ppm

Cu

 

Ammonium Sulfate

0.5 ppm

Cu

 

Chlorine/Chlorides

0.5 ppm

CuNi

 

Hydrogen Sulfide†

None Allowable

Brackish

Use Cupronickel heat exchanger when concentrations of calcium or sodium chloride are greater

 

than 125 ppm are present. (Seawater is approximately 25,000 ppm.)

 

*If the concentration of these corrosives exceeds the maximum allowable level, then the potential for serious corrosion problems exists.

†Sulfides in the water quickly oxidize when exposed to air, requiring that no agitation occur as the sample is taken. Unless tested immediately at the site, the sample will require stabilization with a few drops of one Molar zinc acetate solution, allowing accurate sulfide determination up to 24 hours after sampling. A low pH and high alkalinity cause sys- tem problems, even when both values are within ranges shown. The term pH refers to the acidity, basicity, or neutrality of the water supply. Below 7.0, the water is considered to be acidic. Above 7.0, water is considered to be basic. Neutral water contains a pH of 7.0.

NOTE: To convert ppm to grains per gallon, divide by 17. Hardness in mg/l is equivalent to ppm.

17

Image 17
Contents Safety Considerations ContentsGeneral InstallationPage PSC FAN Motor and Blower Physical Data Aquazone 50RHC,RVC006-060 UnitsPermanent Split Capacitor Physical Data Aquazone 50RHR,RVR006-060 UnitsPhysical Data Aquazone 50RHS,RVS,RDS015-070 Units Right Airflow ConfigurationCode Return Discharge Depth Height Out Pump Supply Ensate Ext Power Cond Therm Supply Return015-024 030Right Back Back RightTypical Installation 50RHC,RHR,RHS Units Right Top TopConfiguration Left Return Left View Configuration Top View-Left ReturnIsometric ViewIsometric View Configuration Left Return Left View Air Coil OpeningCode Front ViewReturn/Bottom Discharge Isometric View Ht Return/Bottom DischargeTop View Front-ViewSide Discharge Remove ScrewsRotate Move to Side50RHC Units Mounting the Unit50RHR Units 50RHS UnitsHorizontal Unit Pitch Condensate DrainCondition Acceptable Level Field Control Wiring Field Power Supply WiringBMC LOCNEC ComprRVS Typical Aquazone Deluxe D Control WiringTrans HpwsLON A50-8154 Low Voltage Field Wiring RLA LRA Motor Unit Circuit FUSE/HACR 50RHC,RVC Electrical DataFLA RLA50RHR,RVR Electrical Data 50RHR,RVR VOLTS-PHASE Voltage Compressor FAN Total MIN MAXUnit Circuit Units RLA LRA FUSE/HACR50RDS, RHS, RVS Electrical Data PRE-START-UPSpeed 50RHR,RVR Blower Performance50RHR,RVR Rated MIN FAN 50RVC Blower Performance with Hot Water Reheat HWR Option 50RHC,RVC Blower PerformanceReheat External Static Pressure ESP Loss Coil Face Velocity 50RHC,RVC Rated MIN FAN50RHS,RVS,RDS Blower Performance 50RVC Blower Performance with Wet CoilCoil Face Velocity WET Coil Reduction 50RHS,RVS,RDS Rated FANField Selectable Inputs Control Jumper Settings See Fig50RHS, RVS Blower Performance with HWR Coil Face 50RHS, RVS with Reheat ESP LossDIP Switch Block S2 Accessory 2 Relay Options DIP Switch Block S2 Accessory 1 Relay OptionsHumidistat/Dehumidistat Logic Deluxe D DIP Switch Settings Accessory DIP Switch Position Relay OptionsSTART-UP Control Accessory Relay ConfigurationsHWR Operating Modes OutputWater Temperature Change Through Heat Exchanger Unit Start-Up Cooling ModeOperating Limits Operating Limits 50RHC,RVC UnitsTypical Unit Operating Pressures and Temperatures Unit Start-Up Heating ModeEntering Cooling Heating Water GPM Temp F TON50RHC,RVC Coaxial Water Pressure Drop 50RHR,RVR Coaxial Water Pressure Drop50RHS,RVS,RDS Coaxial Water Pressure Drop Antifreeze Percentages by Volume Approximate Fluid Volume gal Per 100 Ft of PipeOperation Units with Aquazone Complete C ControlSystem Test Complete C Control LED Code Fault DescriptionsUnits with HWR Option ESD ServiceAquazone Deluxe D Control LED Indica Gravity Flow Method Air Coil Fan Motor Removal TroubleshootingRefrigerant Charging Fault Heating Cooling Possible Cause Solution TroubleshootingUnit Does Not Operate II. START-UP 50RHC,RVC,RHR,RHS,RVR,RVS,RDS START-UP ChecklistCooling Cycle Analysis Heating Cycle Analysis