Carrier RVC 50RHR,RVR Coaxial Water Pressure Drop, 50RHS,RVS,RDS Coaxial Water Pressure Drop

Page 35

Table 22 — 50RHR,RVR Coaxial

Water Pressure Drop

UNIT

 

 

WATER TEMPERATURE (F)

 

GPM

30 F

 

50 F

70 F

 

90 F

50RHR,RVR

 

 

 

 

 

Pressure Drop (psi)

 

 

 

 

 

 

006*

0.8

0.8

 

0.8

0.7

 

0.7

1.1

1.2

 

1.1

1.0

 

1.0

 

1.5

2.0

 

1.9

1.8

 

1.7

009

1.1

1.2

 

1.1

1.0

 

0.9

1.7

1.7

 

1.6

1.5

 

1.4

 

2.2

3.5

 

3.2

3.0

 

2.8

012

1.5

2.8

 

2.6

2.4

 

2.3

2.3

6.0

 

5.6

5.2

 

4.9

 

3.0

9.6

 

9.0

8.3

 

7.9

015

1.8

2.5

 

2.3

2.1

 

2.0

2.6

4.8

 

4.5

4.1

 

3.9

 

3.5

8.1

 

7.6

7.0

 

6.6

019

2.3

1.9

 

1.7

1.6

 

1.5

3.4

3.4

 

3.1

2.9

 

2.7

 

4.5

6.6

 

6.2

5.7

 

5.4

024

3.0

2.0

 

1.9

1.7

 

1.6

4.5

4.2

 

3.9

3.6

 

3.4

 

6.0

7.0

 

6.5

6.0

 

5.7

030

3.8

1.4

 

1.3

1.2

 

1.2

5.5

2.4

 

2.3

2.1

 

2.0

 

7.5

3.9

 

3.7

3.4

 

3.2

036

4.5

1.1

 

1.1

1.0

 

0.9

6.8

2.1

 

2.0

1.9

 

1.8

 

9.0

3.5

 

3.3

3.0

 

2.9

042

5.3

1.4

 

1.3

1.2

 

1.2

7.9

2.9

 

2.7

2.5

 

2.3

 

10.5

4.6

 

4.2

3.9

 

3.7

048

6.0

2.1

 

1.9

1.8

 

1.7

9.0

3.9

 

3.7

3.4

 

3.2

 

12.0

6.4

 

5.9

5.5

 

5.2

060

7.5

2.9

 

2.7

2.5

 

2.4

11.3

5.7

 

5.3

4.9

 

4.7

 

15.0

9.4

 

8.7

8.1

 

7.7

*Size 006 available in 50RHR unit only.

Table 23 — 50RHS,RVS,RDS Coaxial

Water Pressure Drop

UNIT

 

WATER TEMPERATURE (F)

GPM

30 F

50 F

70 F

90 F

50RHS,RVS,RDS

 

 

Pressure Drop (psi)

 

 

 

 

 

015

1.8

0.6

0.5

0.5

0.5

2.8

1.0

0.9

0.8

0.8

 

3.8

1.5

1.4

1.3

1.2

018

2.2

0.7

0.7

0.6

0.6

3.5

1.3

1.2

1.1

1.1

 

4.5

1.8

1.8

1.6

1.5

024

3.0

0.6

0.6

0.5

0.5

4.5

1.1

1.1

1.0

0.9

 

6.0

1.8

1.7

1.5

1.5

030

3.7

0.8

0.8

0.7

0.7

5.5

1.6

1.4

1.3

1.3

 

7.5

2.6

2.4

2.2

2.1

036

4.5

1.3

1.2

1.1

1.1

7.0

2.1

1.9

1.8

1.7

 

9.0

3.9

3.7

3.4

3.2

042

5.2

1.6

1.5

1.4

1.3

8.0

3.2

3.0

2.8

2.6

 

10.5

5.1

4.7

4.4

4.1

048

6.0

2.1

1.9

1.8

1.7

9.0

3.9

3.7

3.4

3.2

 

12.0

6.4

5.9

5.5

5.2

060

7.5

1.1

1.0

1.0

0.9

11.3

2.2

2.1

1.9

1.8

 

15.0

3.6

3.4

3.1

3.0

070

9.0

1.5

1.4

1.3

1.2

13.5

3.0

2.8

2.6

2.5

 

18.0

5.0

4.7

4.3

4.1

Table 24 — 50RHC,RVC Coaxial

Water Pressure Drop

UNIT

 

 

WATER TEMPERATURE (F)

 

GPM

60 F

 

70 F

80 F

 

90 F

50RHC,RVC

 

 

 

 

 

Pressure Drop (psi)

 

 

 

 

 

 

 

0.9

0.7

 

0.7

0.7

 

0.6

006*

1.1

1.2

 

1.2

1.2

 

1.1

1.7

1.9

 

1.9

1.8

 

1.8

 

 

 

 

2.0

2.9

 

2.8

2.7

 

2.6

 

1.1

2.4

 

2.3

2.3

 

2.2

009

1.7

3.1

 

3.0

2.9

 

2.8

2.3

4.0

 

3.9

3.8

 

3.7

 

 

 

 

3.0

5.4

 

5.3

5.1

 

4.9

 

1.5

2.3

 

2.2

2.1

 

2.1

012

2.3

4.4

 

4.3

4.2

 

4.0

3.0

6.4

 

6.2

6.0

 

5.8

 

 

 

 

4.0

13.3

 

12.9

12.6

 

12.2

 

2.3

2.0

 

2.0

1.9

 

1.8

018

3.5

3.1

 

3.0

2.9

 

2.8

4.5

4.2

 

4.1

3.9

 

3.8

 

 

 

 

6.0

5.9

 

5.7

5.6

 

5.4

 

3.0

2.0

 

1.9

1.8

 

1.8

024

4.5

3.9

 

3.7

3.6

 

3.5

6.0

6.4

 

6.2

6.0

 

5.8

 

 

 

 

8.0

10.6

 

10.3

10.0

 

9.7

 

3.8

1.5

 

1.5

1.4

 

1.4

030

5.5

2.7

 

2.6

2.5

 

2.4

7.5

4.3

 

4.2

4.1

 

3.9

 

 

 

 

10.0

6.9

 

6.7

6.5

 

6.3

 

4.5

1.7

 

1.7

1.6

 

1.6

036

6.8

3.2

 

3.1

3.0

 

2.9

9.0

5.0

 

4.9

4.8

 

4.6

 

 

 

 

12.0

8.2

 

7.9

7.7

 

7.5

 

5.3

0.9

 

0.9

0.9

 

0.9

041†

7.9

2.2

 

2.1

2.1

 

2.0

10.5

4.0

 

3.9

3.8

 

3.6

 

 

 

 

13.0

6.2

 

6.0

5.8

 

5.7

 

5.3

1.0

 

1.0

1.0

 

0.9

042

8.0

2.6

 

2.6

2.5

 

2.4

11.0

5.3

 

5.1

4.9

 

4.8

 

 

 

 

14.0

8.7

 

8.5

8.2

 

8.0

 

6.0

1.2

 

1.2

1.2

 

1.1

048

9.0

2.9

 

2.8

2.7

 

2.6

12.0

5.3

 

5.1

4.9

 

4.8

 

 

 

 

16.0

9.5

 

9.2

8.9

 

8.6

 

7.5

4.4

 

4.2

4.1

 

4.0

060

11.3

7.6

 

7.3

7.1

 

6.9

15.0

11.4

 

11.1

10.8

 

10.4

 

 

 

 

20.0

17.6

 

17.1

16.6

 

16.1

*Size 006 available in 50RHC unit only. †Size 041 available in 50RVC unit only.

Antifreeze — In areas where entering loop temperatures drop below 40 F or where piping will be routed through areas subject to freezing, antifreeze is needed.

Alcohols and glycols are commonly used as antifreeze agents. Freeze protection should be maintained to 15 F below the lowest expected entering loop temperature. For example, if the lowest expected entering loop temperature is 30 F, the leav- ing loop temperature would be 22 to 25 F. Therefore, the freeze protection should be at 15 F (30 F – 15 F = 15 F).

IMPORTANT: All alcohols should be pre-mixed and pumped from a reservoir outside of the building or introduced under water level to prevent fuming.

Calculate the total volume of fluid in the piping system. See Table 25. Use the percentage by volume in Table 26 to deter- mine the amount of antifreeze to use. Antifreeze concentration should be checked from a well mixed sample using a hydrome- ter to measure specific gravity.

FREEZE PROTECTION SELECTION — The 30 F FP1 factory setting (water) should be used to avoid freeze damage to the unit.

Once antifreeze is selected, the JW3 jumper (FP1) should be clipped on the control to select the low temperature (anti- freeze 13 F) set point to avoid nuisance faults.

35

Image 35
Contents Safety Considerations ContentsGeneral InstallationPage PSC FAN Motor and Blower Physical Data Aquazone 50RHC,RVC006-060 UnitsPermanent Split Capacitor Physical Data Aquazone 50RHR,RVR006-060 UnitsPhysical Data Aquazone 50RHS,RVS,RDS015-070 Units Right Airflow ConfigurationCode Return Discharge 030 Ext Power Cond Therm Supply ReturnDepth Height Out Pump Supply Ensate 015-024Right Back Back RightTypical Installation 50RHC,RHR,RHS Units Right Top TopView Configuration Top View-Left ReturnConfiguration Left Return Left View IsometricFront View Configuration Left Return Left View Air Coil OpeningIsometric View CodeFront-View Ht Return/Bottom DischargeReturn/Bottom Discharge Isometric View Top ViewMove to Side Remove ScrewsSide Discharge Rotate50RHS Units Mounting the Unit50RHC Units 50RHR UnitsHorizontal Unit Pitch Condensate DrainCondition Acceptable Level Field Control Wiring Field Power Supply WiringCompr LOCBMC NECRVS Typical Aquazone Deluxe D Control WiringTrans HpwsLON A50-8154 Low Voltage Field Wiring RLA 50RHC,RVC Electrical DataRLA LRA Motor Unit Circuit FUSE/HACR FLARLA LRA FUSE/HACR 50RHR,RVR VOLTS-PHASE Voltage Compressor FAN Total MIN MAX50RHR,RVR Electrical Data Unit Circuit Units50RDS, RHS, RVS Electrical Data PRE-START-UPSpeed 50RHR,RVR Blower Performance50RHR,RVR Rated MIN FAN 50RHC,RVC Rated MIN FAN 50RHC,RVC Blower Performance50RVC Blower Performance with Hot Water Reheat HWR Option Reheat External Static Pressure ESP Loss Coil Face Velocity50RHS,RVS,RDS Rated FAN 50RVC Blower Performance with Wet Coil50RHS,RVS,RDS Blower Performance Coil Face Velocity WET Coil ReductionCoil Face 50RHS, RVS with Reheat ESP Loss Control Jumper Settings See FigField Selectable Inputs 50RHS, RVS Blower Performance with HWRAccessory DIP Switch Position Relay Options DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options Humidistat/Dehumidistat Logic Deluxe D DIP Switch SettingsOutput Control Accessory Relay ConfigurationsSTART-UP HWR Operating ModesOperating Limits 50RHC,RVC Units Unit Start-Up Cooling ModeWater Temperature Change Through Heat Exchanger Operating LimitsTemp F TON Unit Start-Up Heating ModeTypical Unit Operating Pressures and Temperatures Entering Cooling Heating Water GPM50RHC,RVC Coaxial Water Pressure Drop 50RHR,RVR Coaxial Water Pressure Drop50RHS,RVS,RDS Coaxial Water Pressure Drop Units with Aquazone Complete C Control Approximate Fluid Volume gal Per 100 Ft of PipeAntifreeze Percentages by Volume OperationSystem Test Complete C Control LED Code Fault DescriptionsUnits with HWR Option ESD ServiceAquazone Deluxe D Control LED Indica Gravity Flow Method Air Coil Fan Motor Removal TroubleshootingRefrigerant Charging Fault Heating Cooling Possible Cause Solution TroubleshootingUnit Does Not Operate II. START-UP 50RHC,RVC,RHR,RHS,RVR,RVS,RDS START-UP ChecklistCooling Cycle Analysis Heating Cycle Analysis