Carrier RVR, RVS, RDS006-060, RHR, RVC, RHS Field Selectable Inputs, Control Jumper Settings See Fig

Page 30

Table 13 — 50RHS, RVS Blower Performance with HWR

COIL FACE

 

 

 

50RHS, RVS WITH REHEAT ESP LOSS

 

 

 

50RHS, RVS

50RHS, RVS

50RHS, RVS

50RHS, RVS

50RHS, RVS

50RHS, RVS

VELOCITY (FPM)

 

 

015, 018 (in. wg)

024, 030 (in. wg)

036 (in. wg)

042, 048 (in. wg)

060 (in. wg)

070 (in. wg)

 

 

 

 

 

 

 

 

 

 

200

 

0.040

0.037

0.033

0.031

0.028

0.026

 

 

 

 

 

 

 

 

250

 

0.059

0.052

0.046

0.042

0.038

0.034

 

 

 

 

 

 

 

 

300

 

0.088

0.077

0.066

0.059

0.051

0.044

 

 

 

 

 

 

 

 

350

 

0.131

0.113

0.096

0.085

0.073

0.061

 

 

 

 

 

 

 

 

400

 

0.203

0.181

0.160

0.145

0.131

0.117

 

 

 

 

 

 

 

 

450

 

0.258

0.242

0.226

0.215

0.205

0.194

 

 

 

 

 

 

 

 

500

 

0.375

0.360

0.345

0.335

0.326

0.316

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

ESP — External Static Pressure

HWR — Hot Water Reheat

FIELD SELECTABLE INPUTS

Jumpers and DIP (dual in-line package) switches on the control board are used to customize unit operation and can be configured in the field.

IMPORTANT: Jumpers and DIP switches should only be clipped when power to control board has been turned off.

C Control Jumper Settings (See Fig. 19)

WATER COIL FREEZE PROTECTION (FP1) LIMIT SETTING — Select jumper 3, (JW3-FP1 Low Temp) to choose FP1 limit of 10 F or 30 F. To select 30 F as the limit, DO NOT clip the jumper. To select 10 F as the limit, clip the jumper.

AIR COIL FREEZE PROTECTION (FP2) LIMIT SET- TING — Select jumper 2 (JW2-FP2 Low Temp) to choose FP2 limit of 10 F or 30 F. To select 30 F as the limit, DO NOT clip the jumper. To select 10 F as the limit, clip the jumper.

ALARM RELAY SETTING — Select jumper 1 (JW1-AL2 Dry) for connecting alarm relay terminal (AL2) to 24 vac (R) or to remain as a dry contact (no connection). To connect AL2 to R, do not clip the jumper. To set as dry contact, clip the jumper.

C Control DIP Switches — The C Control has 1 DIP switch block with two switches. See Fig. 19.

PERFORMANCE MONITOR (PM) — DIP switch 1 will enable or disable this feature. To enable the PM, set the switch to ON. To disable the PM, set the switch to OFF.

STAGE 2 — DIP switch 2 will enable or disable compressor delay. Set DIP switch to OFF for stage 2 in which the compres- sor will have a 3-second delay before energizing.

NOTE: The alarm relay will not cycle during Test mode if switch is set to OFF, stage 2.

D Control Jumper Settings (See Fig. 20)

WATER COIL FREEZE PROTECTION (FP1) LIMIT SETTING — Select jumper 3, (JW3-FP1 Low Temp) to choose FP1 limit of 10 F or 30 F. To select 30 F as the limit, DO NOT clip the jumper. To select 10 F as the limit, clip the jumper.

AIR COIL FREEZE PROTECTION (FP2) LIMIT SET- TING — Select jumper 2 (JW2-FP2 Low Temp) to choose FP2 limit of 10 F or 30 F. To select 30 F as the limit, DO NOT clip the jumper. To select 10 F as the limit, clip the jumper.

ALARM RELAY SETTING — Select jumper 4 (JW4-AL2 Dry) for connecting alarm relay terminal (AL2) to 24 vac (R) or to remain as a dry contact (no connection). To connect AL2

to R, do not clip the jumper. To set as dry contact, clip the jumper.

LOW PRESSURE SETTING — The D Control can be con- figured for Low Pressure Setting (LP). Select jumper 1 (JW1- LP Norm Open) for choosing between low pressure input nor- mally open or closed. To configure for normally closed opera- tion, do not clip the jumper. To configure for normally open op- eration, clip the jumper.

D Control DIP Switches — The D Control has 2 DIP switch blocks. Each DIP switch block has 8 switches and is labeled either S1 or S2 on the circuit board. See Fig. 20.

DIP SWITCH BLOCK 1 (S1) — This set of switches offers the following options for D Control configuration:

Performance Monitor (PM) — Set switch 1 to enable or dis- able performance monitor. To enable the PM, set the switch to ON. To disable the PM, set the switch to OFF.

Compressor Relay Staging Operation — Switch 2 will en- able or disable compressor relay staging operation. The com- pressor relay can be set to turn on with stage 1 or stage 2 call from the thermostat. This setting is used with dual stage units (units with 2 compressors and 2 D controls) or in master/slave applications. In master/slave applications, each compressor and fan will stage according to its switch 2 setting. If switch is set to stage 2, the compressor will have a 3-second delay before ener- gizing during stage 2 demand.

NOTE: If DIP switch is set for stage 2, the alarm relay will not cycle during Test mode.

Heating/Cooling Thermostat Type — Switch 3 provides selec- tion of thermostat type. Heat pump or heat/cool thermostats can be selected. Select OFF for heat/cool thermostats. When in heat/cool mode, Y1 is used for cooling stage 1, Y2 is used for cooling stage 2, W1 is used for heating stage 1 and O/W2 is used for heating stage 2. Select ON for heat pump applications. In heat pump mode, Y1 used is for compressor stage 1, Y2 is used for compressor stage 2, W1 is used for heating stage 3 or emergency heat, and O/W2 is used for RV (heating or cooling) depending upon switch 4 setting.

O/B Thermostat Type — Switch 4 provides selection for heat pump O/B thermostats. O is cooling output. B is heating out- put. Select ON for heat pumps with O output. Select OFF for heat pumps with B output.

Dehumidification Fan Mode — Switch 5 provides selection of normal or dehumidification fan mode. Select OFF for dehu- midification mode. The fan speed relay will remain OFF dur- ing cooling stage 2. Select ON for normal mode. The fan speed relay will turn on during cooling stage 2 in normal mode.

Switch 6 — Not used.

Boilerless Operation — Switch 7 provides selection of boiler- less operation and works in conjunction with switch 8. In

30

Image 30
Contents Contents Safety ConsiderationsInstallation GeneralPage Physical Data Aquazone 50RHC,RVC006-060 Units PSC FAN Motor and BlowerPhysical Data Aquazone 50RHR,RVR006-060 Units Physical Data Aquazone 50RHS,RVS,RDS015-070 UnitsPermanent Split Capacitor Airflow Configuration Code Return DischargeRight 015-024 Ext Power Cond Therm Supply ReturnDepth Height Out Pump Supply Ensate 030Back Right Right BackTypical Installation 50RHC,RHR,RHS Units Top Right TopIsometric Configuration Top View-Left ReturnConfiguration Left Return Left View ViewCode Configuration Left Return Left View Air Coil OpeningIsometric View Front ViewTop View Ht Return/Bottom DischargeReturn/Bottom Discharge Isometric View Front-ViewRotate Remove ScrewsSide Discharge Move to Side50RHR Units Mounting the Unit50RHC Units 50RHS UnitsCondensate Drain Horizontal Unit PitchCondition Acceptable Level Field Power Supply Wiring Field Control WiringNEC LOCBMC ComprTypical Aquazone Deluxe D Control Wiring RVSHpws LONTrans A50-8154 Low Voltage Field Wiring FLA 50RHC,RVC Electrical DataRLA LRA Motor Unit Circuit FUSE/HACR RLAUnit Circuit Units 50RHR,RVR VOLTS-PHASE Voltage Compressor FAN Total MIN MAX50RHR,RVR Electrical Data RLA LRA FUSE/HACRPRE-START-UP 50RDS, RHS, RVS Electrical Data50RHR,RVR Blower Performance 50RHR,RVR Rated MIN FANSpeed Reheat External Static Pressure ESP Loss Coil Face Velocity 50RHC,RVC Blower Performance50RVC Blower Performance with Hot Water Reheat HWR Option 50RHC,RVC Rated MIN FANCoil Face Velocity WET Coil Reduction 50RVC Blower Performance with Wet Coil50RHS,RVS,RDS Blower Performance 50RHS,RVS,RDS Rated FAN50RHS, RVS Blower Performance with HWR Control Jumper Settings See FigField Selectable Inputs Coil Face 50RHS, RVS with Reheat ESP LossHumidistat/Dehumidistat Logic Deluxe D DIP Switch Settings DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options Accessory DIP Switch Position Relay OptionsHWR Operating Modes Control Accessory Relay ConfigurationsSTART-UP OutputOperating Limits Unit Start-Up Cooling ModeWater Temperature Change Through Heat Exchanger Operating Limits 50RHC,RVC UnitsEntering Cooling Heating Water GPM Unit Start-Up Heating ModeTypical Unit Operating Pressures and Temperatures Temp F TON50RHR,RVR Coaxial Water Pressure Drop 50RHS,RVS,RDS Coaxial Water Pressure Drop50RHC,RVC Coaxial Water Pressure Drop Operation Approximate Fluid Volume gal Per 100 Ft of PipeAntifreeze Percentages by Volume Units with Aquazone Complete C ControlComplete C Control LED Code Fault Descriptions Units with HWR OptionSystem Test Service Aquazone Deluxe D Control LED IndicaESD Gravity Flow Method Troubleshooting Refrigerant ChargingAir Coil Fan Motor Removal Troubleshooting Fault Heating Cooling Possible Cause SolutionUnit Does Not Operate 50RHC,RVC,RHR,RHS,RVR,RVS,RDS START-UP Checklist II. START-UPHeating Cycle Analysis Cooling Cycle Analysis