Carrier 50RHC Unit Start-Up Heating Mode, Typical Unit Operating Pressures and Temperatures, Ewt

Page 34

Unit Start-Up Heating Mode

NOTE: Operate the unit in heating cycle after checking the cooling cycle. Allow 5 minutes between tests for the pressure or reversing valve to equalize.

1.Turn thermostat to lowest setting and set thermostat switch to HEAT position.

2.Slowly turn the thermostat to a higher temperature until the compressor activates.

3.Check for warm air delivery at the unit grille within a few minutes after the unit has begun to operate.

4.Check the temperature of both supply and discharge wa- ter. Compare to Table 21. If temperature is within range, proceed. If temperature is outside the range, check the heating refrigerant pressures in Table 21.

5.Once the unit has begun to run, check for warm air deliv- ery at the unit grille.

6.Check air temperature rise across the coil when compres- sor is operating. Air temperature rise should be between 20 and 30 F after 15 minutes at load.

7.Check for vibration, noise and water leaks.

Flow Regulation — Flow regulation can be accom- plished by two methods. Most water control valves have a flow adjustment built into the valve. By measuring the pressure drop through the unit heat exchanger, the flow rate can be deter- mined. See Tables 22-24. Adjust the water control valve until the flow of 1.5 to 2 gpm is achieved. Since the pressure con- stantly varies, two pressure gages may be needed in some applications.

An alternative method is to install a flow control device. These devices are typically an orifice of plastic material de- signed to allow a specified flow rate that are mounted on the outlet of the water control valve. Occasionally these valves produce a velocity noise that can be reduced by applying some back pressure. To accomplish this, slightly close the leaving isolation valve of the well water setup.

To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position before flushing system.

Flushing — Once the piping is complete, units require final purging and loop charging. A flush cart pump of at least 1.5 hp is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from the loop. Flush the loop in both

directions with a high volume of water at a high velocity. Fol- low the steps below to properly flush the loop:

1.Verify power is off.

2.Fill loop with water from hose through flush cart before using flush cart pump to ensure an even fill. Do not allow the water level in the flush cart tank to drop below the pump inlet line to prevent air from filling the line.

3.Maintain a fluid level in the tank above the return tee to avoid air entering back into the fluid.

4.Shutting off the return valve that connects into the flush cart reservoir will allow 50 psi surges to help purge air pockets. This maintains the pump at 50 psi.

5.To purge, keep the pump at 50 psi until maximum pump- ing pressure is reached.

6.Open the return valve to send a pressure surge through the loop to purge any air pockets in the piping system.

7.A noticeable drop in fluid level will be seen in the flush cart tank. This is the only indication of air in the loop.

NOTE: If air is purged from the system while using a 10 in. PVC flush tank, the level drop will only be 1 to 2 in. since liquids are incompressible. If the level drops more than this, flushing should continue since air is still being compressed in the loop. If level is less than 1 to 2 in., reverse the flow.

8.Repeat this procedure until all air is purged.

9.Restore power.

Antifreeze may be added before, during or after the flushing process. However, depending on when it is added in the process, it can be wasted. Refer to the Antifreeze section for more detail.

Loop static pressure will fluctuate with the seasons. Pres- sures will be higher in the winter months than during the warmer months. This fluctuation is normal and should be con- sidered when charging the system initially. Run the unit in either heating or cooling for several minutes to condition the loop to a homogenous temperature.

When complete, perform a final flush and pressurize the loop to a static pressure of 40 to 50 psi for winter months or 15 to 20 psi for summer months.

After pressurization, be sure to remove the plug from the end of the loop pump motor(s) to allow trapped air to be discharged and to ensure the motor housing has been flooded. Be sure the loop flow center provides adequate flow through the unit by checking pressure drop across the heat exchanger. Compare the results to the data in Tables 22-24.

Table 21 — Typical Unit Operating Pressures and Temperatures

ENTERING

 

 

 

 

COOLING

 

 

 

 

 

HEATING

 

 

 

WATER

GPM/

Suction

Discharge

Super-

Sub-

Water

Air

Suction

Discharge

 

Sub-

Water

Air

Temp

Temp

Super-

Temp

TEMP (F)

TON

Pressure

Pressure

heat

cooling

Pressure

Pressure

cooling

Temp

(EWT)

 

(psig)

(psig)

(F)

(F)

Rise

Drop (F)

(psig)

(psig)

heat (F)

(F)

Drop (F)

Rise (F)

 

 

 

 

 

 

 

(F)

DB

 

 

 

 

 

DB

 

 

30

1.5

75-85

90-105

25-40

12-20

21-24

21-26

34-

39

167-186

12-16

1-4

7.6-

8.4

14-20

2.3

74-84

80-

95

25-40

11-18

13-16

21-26

37-

43

172-191

12-16

1-4

4.8-

5.6

16-22

 

3.0

73-83

70-

85

25-40

10-16

6-11

21-26

40-

46

177-196

12-16

1-4

3.4-

4.2

16-22

50

1.5

75-85

125-155

12-20

10-18

20-23

20-25

50- 60

180-210

10-17

1-5

10.8-11.9

23-29

2.3

74-84

120-142

12-20

9-16

12-15

20-25

53-

62

185-215

10-17

1-5

6.7-

8.1

24-30

 

3.0

73-83

115-138

12-20

8-14

8-12

20-25

55-

65

190-220

10-17

1-5

5.1-

5.9

25-31

70

1.5

75-85

179-198

9-16

8-15

19-22

19-24

71- 82

205-230

14-19

1-5

14.0-15.2

28-34

2.3

74-84

168-186

9-16

8-14

12-17

19-24

73-

85

210-238

14-19

1-5

9.0-10.2

30-37

 

3.0

73-83

158-175

9-16

8-12

7-12

19-24

76-

88

215-242

14-19

1-5

6.7-

7.9

31-38

90

1.5

75-85

229-251

9-17

8-15

18-21

17-23

85- 95

220-260

18-28

2-5

14.4-16.6

32-39

2.3

74-84

218-241

9-17

8-14

10-14

17-23

90-100

225-265

18-28

2-5

10.8-12.4

33-41

 

3.0

73-83

208-230

9-17

8-12

6-11

17-23

95-105

230-270

18-28

2-5

7.2-

8.3

35-42

110

1.5

77-87

280-320

8-15

10-25

17-20

15-20

 

 

 

 

 

 

 

 

2.3

76-86

270-310

8-15

10-24

9-13

15-20

 

 

 

 

 

 

 

 

 

3.0

75-85

260-300

8-15

10-22

5-10

15-20

 

 

 

 

 

 

 

 

LEGEND

DB — Dry Bulb

EAT — Entering Air Temperature

NOTES:

1.Based on nominal 400 cfm per ton airflow, 70 F EAT heating and 80/67 F EAT cooling.

2.Cooling air and water numbers can vary greatly with changes in humidity.

3.Subcooling is based upon the head pressure at compressor service port.

4.Unit should not be operated in heating mode with an EWT of 110.

34

Image 34
Contents Contents Safety ConsiderationsInstallation GeneralPage Physical Data Aquazone 50RHC,RVC006-060 Units PSC FAN Motor and BlowerPhysical Data Aquazone 50RHS,RVS,RDS015-070 Units Physical Data Aquazone 50RHR,RVR006-060 UnitsPermanent Split Capacitor Code Return Discharge Airflow ConfigurationRight 015-024 Ext Power Cond Therm Supply ReturnDepth Height Out Pump Supply Ensate 030Back Right Right BackTypical Installation 50RHC,RHR,RHS Units Top Right TopIsometric Configuration Top View-Left ReturnConfiguration Left Return Left View ViewCode Configuration Left Return Left View Air Coil OpeningIsometric View Front ViewTop View Ht Return/Bottom DischargeReturn/Bottom Discharge Isometric View Front-ViewRotate Remove ScrewsSide Discharge Move to Side50RHR Units Mounting the Unit50RHC Units 50RHS UnitsCondensate Drain Horizontal Unit PitchCondition Acceptable Level Field Power Supply Wiring Field Control WiringNEC LOCBMC ComprTypical Aquazone Deluxe D Control Wiring RVSLON HpwsTrans A50-8154 Low Voltage Field Wiring FLA 50RHC,RVC Electrical DataRLA LRA Motor Unit Circuit FUSE/HACR RLAUnit Circuit Units 50RHR,RVR VOLTS-PHASE Voltage Compressor FAN Total MIN MAX50RHR,RVR Electrical Data RLA LRA FUSE/HACRPRE-START-UP 50RDS, RHS, RVS Electrical Data50RHR,RVR Rated MIN FAN 50RHR,RVR Blower PerformanceSpeed Reheat External Static Pressure ESP Loss Coil Face Velocity 50RHC,RVC Blower Performance50RVC Blower Performance with Hot Water Reheat HWR Option 50RHC,RVC Rated MIN FANCoil Face Velocity WET Coil Reduction 50RVC Blower Performance with Wet Coil50RHS,RVS,RDS Blower Performance 50RHS,RVS,RDS Rated FAN50RHS, RVS Blower Performance with HWR Control Jumper Settings See FigField Selectable Inputs Coil Face 50RHS, RVS with Reheat ESP LossHumidistat/Dehumidistat Logic Deluxe D DIP Switch Settings DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options Accessory DIP Switch Position Relay OptionsHWR Operating Modes Control Accessory Relay ConfigurationsSTART-UP OutputOperating Limits Unit Start-Up Cooling ModeWater Temperature Change Through Heat Exchanger Operating Limits 50RHC,RVC UnitsEntering Cooling Heating Water GPM Unit Start-Up Heating ModeTypical Unit Operating Pressures and Temperatures Temp F TON50RHS,RVS,RDS Coaxial Water Pressure Drop 50RHR,RVR Coaxial Water Pressure Drop50RHC,RVC Coaxial Water Pressure Drop Operation Approximate Fluid Volume gal Per 100 Ft of PipeAntifreeze Percentages by Volume Units with Aquazone Complete C ControlUnits with HWR Option Complete C Control LED Code Fault DescriptionsSystem Test Aquazone Deluxe D Control LED Indica ServiceESD Gravity Flow Method Refrigerant Charging TroubleshootingAir Coil Fan Motor Removal Troubleshooting Fault Heating Cooling Possible Cause SolutionUnit Does Not Operate 50RHC,RVC,RHR,RHS,RVR,RVS,RDS START-UP Checklist II. START-UPHeating Cycle Analysis Cooling Cycle Analysis