Carrier RVC, RVS, RDS006-060, RVR, RHR, RHS, 50RHC Field Power Supply Wiring, Field Control Wiring

Page 18

Step 8 — Field Power Supply Wiring

To avoid possible injury or death due to electrical shock, open the power supply disconnect switch and secure it in an open position during installation.

Use only copper conductors for field-installed electrical wiring. Unit terminals are not designed to accept other types of conductors. Failure to follow this safety precaution could lead to equipment damage.

All field installed wiring, including the electrical ground, MUST comply with the National Electrical Code (NEC) as well as applicable local codes. In addition, all field wiring must conform to the Class II temperature limitations described in the NEC.

Refer to unit wiring diagrams Fig. 19-22 for a schematic of the field connections, which must be made by the installing (or electrical) contractor. Refer to Tables 5-7 for fuse sizes.

Consult the unit wiring diagram located on the inside of the compressor access panel to ensure proper electrical hookup. The installing (or electrical) contractor must make the field connections when using field-supplied disconnect.

Operating voltage must be the same voltage and phase as shown in Electrical Data shown in Tables 5-7.

Make all final electrical connections with a length of flexi- ble conduit to minimize vibration and sound transmission to the building.

POWER CONNECTION — Make line voltage connection by connecting the incoming line voltage wires to the L side of the CC terminal as shown in Fig. 23. See Tables 5-7 for correct wire and maximum overcurrent protection sizing.

SUPPLY VOLTAGE — Operating voltage to unit must be within voltage range indicated on unit nameplate.

On 3-phase units, voltages under load between phases must be balanced within 2%. Use the following formula to deter- mine the percentage voltage imbalance:

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

 

average voltage

 

Example: Supply voltage is 460-3-60.

 

AB = 452 volts

 

 

 

BC = 464 volts

 

 

 

AC = 455 volts

 

 

 

Average Voltage =

452 + 464 + 455

 

 

3

 

 

 

 

 

=

1371

 

 

 

3

 

= 457

Determine maximum deviation from average voltage:

(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v. Determine percent voltage imbalance.

% Voltage Imbalance =

100 x

 

7

 

457

=

1.53%

 

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electri- cal components.

NOTE: If more than 2% voltage imbalance is present, contact your local electric utility.

208-VOLT OPERATION — All 208-230 volt units are factory wired for 208 volts. The transformers may be switched to 230-volt operation by switching the red (208 volt) wire with the orange (230 volt) wire at the L1 terminal.

Step 9 — Field Control Wiring

THERMOSTAT CONNECTIONS — The thermostat should be wired directly to the Aquazone™ control board. See Fig. 19-22, and 24.

WATER FREEZE PROTECTION — The Aquazone control allows the field selection of source fluid freeze protection points through jumpers. The factory setting of jumper JW3 (FP1) is set for water at 30 F. In earth loop applications, jumper JW3 should be clipped to change the setting to 10 F when using antifreeze in colder earth loop applications. See Fig. 25.

AIR COIL FREEZE PROTECTION — The air coil freeze protection jumper JW2 (FP2) is factory set for 30 F and should not need adjusting.

ACCESSORY CONNECTIONS — Terminal A on the control is provided to control accessory devices such as water valves, electronic air cleaners, humidifiers, etc. This signal operates with the compressor terminal. See Fig. 26. Refer to the specific unit wiring schematic for details.

NOTE: The A terminal should only be used with 24 volt signals — not line voltage signals.

WATER SOLENOID VALVES — Water solenoid valves may be used on primary secondary pump and ground water installa- tions. A typical well water control valve wiring, which can limit waste water in a lockout condition is shown in Fig. 26. A slow closing valve may be required to prevent water hammer. When using a slow closing valve, consider special wiring con- ditions. The valve takes approximately 60 seconds to open (very little water will flow before 45 seconds) and it activates the compressor only after the valve is completely opened by closing its end switch. When wired as shown, the valve will have the following operating characteristics:

1.Remain open during a lockout

2.Draw approximately 25 to 35 VA through the “Y” signal of the thermostat.

IMPORTANT: Connecting a water solenoid valve can overheat the anticipators of electromechanical thermo- stats. Only use relay based electronic thermostats.

18

Image 18
Contents Contents Safety ConsiderationsInstallation GeneralPage Physical Data Aquazone 50RHC,RVC006-060 Units PSC FAN Motor and BlowerPhysical Data Aquazone 50RHR,RVR006-060 Units Physical Data Aquazone 50RHS,RVS,RDS015-070 UnitsPermanent Split Capacitor Airflow Configuration Code Return DischargeRight 015-024 Ext Power Cond Therm Supply ReturnDepth Height Out Pump Supply Ensate 030Back Right Right BackTypical Installation 50RHC,RHR,RHS Units Top Right TopIsometric Configuration Top View-Left ReturnConfiguration Left Return Left View ViewCode Configuration Left Return Left View Air Coil OpeningIsometric View Front ViewTop View Ht Return/Bottom DischargeReturn/Bottom Discharge Isometric View Front-ViewRotate Remove ScrewsSide Discharge Move to Side50RHR Units Mounting the Unit50RHC Units 50RHS UnitsCondensate Drain Horizontal Unit PitchCondition Acceptable Level Field Power Supply Wiring Field Control WiringNEC LOCBMC ComprTypical Aquazone Deluxe D Control Wiring RVSHpws LONTrans A50-8154 Low Voltage Field Wiring FLA 50RHC,RVC Electrical DataRLA LRA Motor Unit Circuit FUSE/HACR RLAUnit Circuit Units 50RHR,RVR VOLTS-PHASE Voltage Compressor FAN Total MIN MAX50RHR,RVR Electrical Data RLA LRA FUSE/HACRPRE-START-UP 50RDS, RHS, RVS Electrical Data50RHR,RVR Blower Performance 50RHR,RVR Rated MIN FANSpeed Reheat External Static Pressure ESP Loss Coil Face Velocity 50RHC,RVC Blower Performance50RVC Blower Performance with Hot Water Reheat HWR Option 50RHC,RVC Rated MIN FANCoil Face Velocity WET Coil Reduction 50RVC Blower Performance with Wet Coil50RHS,RVS,RDS Blower Performance 50RHS,RVS,RDS Rated FAN50RHS, RVS Blower Performance with HWR Control Jumper Settings See FigField Selectable Inputs Coil Face 50RHS, RVS with Reheat ESP LossHumidistat/Dehumidistat Logic Deluxe D DIP Switch Settings DIP Switch Block S2 Accessory 1 Relay OptionsDIP Switch Block S2 Accessory 2 Relay Options Accessory DIP Switch Position Relay OptionsHWR Operating Modes Control Accessory Relay ConfigurationsSTART-UP OutputOperating Limits Unit Start-Up Cooling ModeWater Temperature Change Through Heat Exchanger Operating Limits 50RHC,RVC UnitsEntering Cooling Heating Water GPM Unit Start-Up Heating ModeTypical Unit Operating Pressures and Temperatures Temp F TON50RHR,RVR Coaxial Water Pressure Drop 50RHS,RVS,RDS Coaxial Water Pressure Drop50RHC,RVC Coaxial Water Pressure Drop Operation Approximate Fluid Volume gal Per 100 Ft of PipeAntifreeze Percentages by Volume Units with Aquazone Complete C ControlComplete C Control LED Code Fault Descriptions Units with HWR OptionSystem Test Service Aquazone Deluxe D Control LED IndicaESD Gravity Flow Method Troubleshooting Refrigerant ChargingAir Coil Fan Motor Removal Troubleshooting Fault Heating Cooling Possible Cause SolutionUnit Does Not Operate 50RHC,RVC,RHR,RHS,RVR,RVS,RDS START-UP Checklist II. START-UPHeating Cycle Analysis Cooling Cycle Analysis