Carrier 50RHC, RVS, RDS006-060, RVR Troubleshooting, Fault Heating Cooling Possible Cause Solution

Page 41

Table 30 — Troubleshooting

FAULT

HEATING

COOLING

POSSIBLE CAUSE

SOLUTION

Main Power Problems

X

X

Green Status LED Off

Check line voltage circuit breaker and disconnect.

 

 

 

 

Check for line voltage between L1 and L2 on the contactor.

 

 

 

 

Check for 24 vac between R and C on controller.

 

 

 

 

Check primary/secondary voltage on transformer.

HP Fault — Code 2

 

X

Reduced or no water flow in

Check pump operation or valve operation/setting.

High Pressure

 

 

cooling

 

 

 

Check water flow adjust to proper flow rate.

 

 

 

 

 

 

X

Water temperature out of

Bring water temperature within design parameters.

 

 

 

range in cooling

 

 

X

 

Reduced or no airflow in

Check for dirty air filter and clean or replace.

 

 

 

heating

 

 

 

 

Check fan motor operation and airflow restrictions.

 

 

 

 

 

 

 

 

Dirty air coil — construction dust etc.

 

 

 

 

External static too high. Check Tables 8-13.

 

X

 

Air temperature out of range

Bring return air temperature within design parameters.

 

 

 

in heating

 

 

X

X

Overcharged with refrigerant

Check superheat/subcooling vs typical operating condition Table 21.

 

X

X

Bad HP switch

Check switch continuity and operation. Replace.

LP/LOC Fault — Code 3

X

X

Insufficient charge

Check for refrigerant leaks.

Low Pressure/Loss of

 

 

 

 

X

 

Compressor pump down at

Check charge and start-up water flow.

Charge

 

 

 

start-up

 

 

 

 

 

FP1 Fault — Code 4

X

 

Reduced or no water flow in

Check pump operation or water valve operation/setting.

Water Freeze Protection

 

 

heating

 

 

 

Plugged strainer or filter. Clean or replace.

 

 

 

 

 

 

 

 

Check water flow adjust to proper flow rate.

 

X

 

Inadequate antifreeze level

Check antifreeze density with hydrometer.

 

X

 

Improper freeze protect set-

Clip JW2 jumper for antifreeze (10 F) use.

 

 

 

ting (30 F vs 10 F)

 

 

X

 

Water temperature out of

Bring water temperature within design parameters.

 

 

 

range

 

 

X

X

Bad thermistor

Check temperature and impedance correlation.

FP2 Fault — Code 5

 

X

Reduced or no airflow in

Check for dirty air filter and clean or replace.

Air Coil Freeze

 

 

cooling

 

 

 

Check fan motor operation and airflow restrictions.

Protection

 

 

 

 

 

 

External static too high. Check Tables 8-13.

 

 

 

 

 

 

X

Air temperature out of range

Too much cold vent air. Bring entering air temperature within design

 

 

 

 

parameters.

 

 

X

Improper freeze protect set-

Normal airside applications will require 30 F only.

 

 

 

ting (30 F vs 10 F)

 

 

X

X

Bad thermistor

Check temperature and impedance correlation.

Condensate Fault —

X

X

Blocked drain

Check for blockage and clean drain.

Code 6

 

 

 

 

X

X

Improper trap

Check trap dimensions and location ahead of vent.

 

 

 

X

Poor drainage

Check for piping slope away from unit.

 

 

 

 

Check slope of unit toward outlet.

 

 

 

 

Poor venting. Check vent location.

 

 

X

Moisture on sensor

Check for moisture shorting to air coil.

Over/Under Voltage —

X

X

Under voltage

Check power supply and 24 vac voltage before and during operation.

Code 7

 

 

 

 

 

 

 

Check power supply wire size.

(Auto Resetting)

 

 

 

 

 

 

Check compressor starting.

 

 

 

 

 

 

 

 

Check 24 vac and unit transformer tap for correct power supply voltage.

 

X

X

Over voltage

Check power supply voltage and 24 vac before and during operation.

 

 

 

 

Check 24 vac and unit transformer tap for correct power supply voltage.

Performance Monitor —

X

 

Heating mode FP2>125 F

Check for poor airflow or overcharged unit.

Code 8

 

 

 

 

 

X

Cooling mode FP1>125 F

Check for poor water flow or airflow.

 

 

 

 

 

OR FP2< 40 F

 

FP1 and FP2

X

 

FP1 temperature is higher

Swap FP1 and FP2 thermistors.

Thermistors —

 

 

than FP2 temperature.

 

Code 9

 

 

 

 

 

X

FP2 temperature is higher

Swap FP1 and FP2 thermistors.

 

 

 

 

 

than FP1 temperature.

 

No Fault Code Shown

X

X

No compressor operation

See scroll compressor rotation section.

 

X

X

Compressor overload

Check and replace if necessary.

 

X

X

Control board

Reset power and check operation.

Unit Short Cycles

X

X

Dirty air filter

Check and clean air filter.

 

X

X

Unit in 'Test Mode'

Reset power or wait 20 minutes for auto exit.

 

X

X

Unit selection

Unit may be oversized for space. Check sizing for actual load of space.

 

X

X

Compressor overload

Check and replace if necessary.

Only Fan Runs

X

X

Thermostat position

Ensure thermostat set for heating or cooling operation.

 

X

X

Unit locked out

Check for lockout codes. Reset power.

 

X

X

Compressor overload

Check compressor overload. Replace if necessary.

 

X

X

Thermostat wiring

Check Y and W wiring at heat pump. Jumper Y and R for compressor

 

 

 

 

operation in Test mode.

LEGEND

 

 

 

 

RV — Reversing Valve

 

 

 

 

41

Image 41
Contents Safety Considerations ContentsGeneral InstallationPage PSC FAN Motor and Blower Physical Data Aquazone 50RHC,RVC006-060 UnitsPermanent Split Capacitor Physical Data Aquazone 50RHR,RVR006-060 UnitsPhysical Data Aquazone 50RHS,RVS,RDS015-070 Units Right Airflow ConfigurationCode Return Discharge Depth Height Out Pump Supply Ensate Ext Power Cond Therm Supply Return015-024 030Right Back Back RightTypical Installation 50RHC,RHR,RHS Units Right Top TopConfiguration Left Return Left View Configuration Top View-Left ReturnIsometric ViewIsometric View Configuration Left Return Left View Air Coil OpeningCode Front ViewReturn/Bottom Discharge Isometric View Ht Return/Bottom DischargeTop View Front-ViewSide Discharge Remove ScrewsRotate Move to Side50RHC Units Mounting the Unit50RHR Units 50RHS UnitsHorizontal Unit Pitch Condensate DrainCondition Acceptable Level Field Control Wiring Field Power Supply WiringBMC LOCNEC ComprRVS Typical Aquazone Deluxe D Control WiringTrans HpwsLON A50-8154 Low Voltage Field Wiring RLA LRA Motor Unit Circuit FUSE/HACR 50RHC,RVC Electrical DataFLA RLA50RHR,RVR Electrical Data 50RHR,RVR VOLTS-PHASE Voltage Compressor FAN Total MIN MAXUnit Circuit Units RLA LRA FUSE/HACR50RDS, RHS, RVS Electrical Data PRE-START-UPSpeed 50RHR,RVR Blower Performance50RHR,RVR Rated MIN FAN 50RVC Blower Performance with Hot Water Reheat HWR Option 50RHC,RVC Blower PerformanceReheat External Static Pressure ESP Loss Coil Face Velocity 50RHC,RVC Rated MIN FAN50RHS,RVS,RDS Blower Performance 50RVC Blower Performance with Wet CoilCoil Face Velocity WET Coil Reduction 50RHS,RVS,RDS Rated FANField Selectable Inputs Control Jumper Settings See Fig50RHS, RVS Blower Performance with HWR Coil Face 50RHS, RVS with Reheat ESP LossDIP Switch Block S2 Accessory 2 Relay Options DIP Switch Block S2 Accessory 1 Relay OptionsHumidistat/Dehumidistat Logic Deluxe D DIP Switch Settings Accessory DIP Switch Position Relay OptionsSTART-UP Control Accessory Relay ConfigurationsHWR Operating Modes OutputWater Temperature Change Through Heat Exchanger Unit Start-Up Cooling ModeOperating Limits Operating Limits 50RHC,RVC UnitsTypical Unit Operating Pressures and Temperatures Unit Start-Up Heating ModeEntering Cooling Heating Water GPM Temp F TON50RHC,RVC Coaxial Water Pressure Drop 50RHR,RVR Coaxial Water Pressure Drop50RHS,RVS,RDS Coaxial Water Pressure Drop Antifreeze Percentages by Volume Approximate Fluid Volume gal Per 100 Ft of PipeOperation Units with Aquazone Complete C ControlSystem Test Complete C Control LED Code Fault DescriptionsUnits with HWR Option ESD ServiceAquazone Deluxe D Control LED Indica Gravity Flow Method Air Coil Fan Motor Removal TroubleshootingRefrigerant Charging Fault Heating Cooling Possible Cause Solution TroubleshootingUnit Does Not Operate II. START-UP 50RHC,RVC,RHR,RHS,RVR,RVS,RDS START-UP ChecklistCooling Cycle Analysis Heating Cycle Analysis