Carrier 592-085 warranty Guide Specifications

Page 52

GUIDE SPECIFICATIONS (cont)

axial flow design, with integrated slinger ring. The indoor fan shall be a dynamically balanced, poly- mer, reverse curve blower wheel, to assure uniform air distribution. The Fan Motor shall be of an enclosed design to reduce the effects of moisture and corrosion.

D.Compressor and Refrigerant:

The rotary-type Compressor shall be fully hermetic with internal and external vibration isolation. The refrigeration system will be sealed and contain a full refrigerant charge (R-22).

E.Coils:

Condenser and evaporator coils to be constructed of high-efficiency, 11 element lance sine wave

enhanced aluminum fins and 3/8-in. seamless axial grooved copper tubing, necessary to achieve EER and COP rating, as specified on the chassis nameplate.

F.Factory-Installed Electric Heater:

The factory-installed, open coil type, electric heater is standard in heat/cool and heat pump chassis. The electric heater shall contain both an automatic reset and a one-shot overtemperature protection device. The heating capacity of the electric heater shall be as identified on the Contract drawing schedule and in the specifications.

G.Controls:

All standard models shall be equipped with electro- mechanical controls to simplify the serviceability of the unit.

1.The chassis shall have standard controls, accessible and covered by a hinged door. The mode selection control shall consist of a mechanical rotary selector switch, which pro- vides OFF, FAN ONLY, HEAT or COOL oper- ations. The temperature selection control shall be an adjustable thermostat with upper and lower limits.

2.All standard models shall have a continuous/ fan cycle selector switch located behind the front panel. It shall allow the selection of con- tinuous fan operation for maximum comfort or cycle operation (fan only runs with cooling or heating operation) for maximum energy savings.

3.All standard models shall have a Temperature Limiter control located behind the front panel. The temperature limiter allows a room temper- ature range to be set, to avoid extreme temper- ature settings, to maximize energy savings.

4.Emergency Heat Switch (Heat Pump Models Only) shall disable the compressor in heating mode and only allow the use of electric heat during heating cycles. The Emergency Heat switch is active at all outdoor ambient temperatures.

5.Wall thermostat chassis (RC and RP models) shall come from the factory ready for wall thermostat installation, including a blank out plate in place of the control knobs. No field- installed kits or wire harnesses shall be required.

6.Wall thermostat chassis (RC and RP models) shall have a user selectable fan speed control

switch, on the control panel, to optimize fan speed for maximum comfort.

H.Safeties:

Compressor shall have automatic reset, overtem- perature and overcurrent protection. The fan motor shall have an inherent, automatic reset overtemper- ature protection. The electric heater shall have two overtemperature protectors.

I.Front Panel (supplied with chassis):

Front panel shall be constructed of a polymer mate- rial to resist breakage and corrosion. It shall have a front louvered surface with integrated control door and air filters. The air filters shall be easily accessible without removing the front panel from the chassis.

J.Anti-Theft Control Knobs:

All chassis knobs shall resist breakage and corro- sion. They shall be mounted on to the control box section and captured behind the front panel, to pre- vent unauthorized removal.

K.Bi-Directional Discharge Grille:

Bi-directional polymer discharge grille shall resist corrosion and breakage. It shall be easily set to direct air at 40 degrees from horizontal or 80 degrees from horizontal. This non-metallic dis- charge grille shall be cool to the touch during the heating cycle.

L.Ventilation:

The chassis shall have a manual adjustable fresh air vent with a concealed manual control. The vent control shall allow a maximum of 50 cfm of fresh air to be drawn into the room when the indoor fan is operating and the door is open. The ventilation air can be increased to approximately 95 cfm by add- ing the Booster Ventilation accessory kit (see section Q.13)

M.High-Efficiency Condensate Removal System:

The chassis shall have a condensate removal sys- tem consisting of a condensate suction port, to draw and atomize condensate, and a slinger ring inte- grated in the outdoor fan, to disperse condensate onto the condenser coil to be evaporated.

N.Snow Baffle:

The chassis shall contain a snow baffle to prevent melting snow from freezing and potentially damag- ing the outdoor fan.

O.Corrosion Protection (CP and RP Models Only):

Chassis with Corrosion Protection (CP,RP) shall be used for coastal or corrosive environments, to pro- long the life of the product. Minimum requirements are:

1.All outdoor-exposed sheet metal parts shall be coated with a polyester powder coat paint.

2.Compressor and outdoor-fan motor finish shall be capable of withstanding 500 hours of salt spray testing per ASTM B-117.

3.Compressor mounting screws shall be SermaGuard™ coated.

4.Outdoor coil fin stock shall be coated and able to withstand 1000 hours of salt spray testing per ASTM B-117.

5.Outdoor coil tube sheets shall be made of 316L stainless steel.

52

Image 52
Contents Contents Architects and ENGINEERS’ ManualPage RETROFIT/REPLACEMENT Carrier WarrantyApplications NEW ConstructionApplications Application ConsiderationsUndersizing OversizingFan Cycle Switch Dual options Product Overview 52P and 52CProduct Features and Benefits 52P and 52C Quiet OperationMost Efficient Performance Efficient FAN MotorRemovable Front Panel NO-RUST Weather Last Wall Sleeve and Front PanelANTI-THEFT Knobs Product Features and Benefits TWO-PIECE Lifetime Indoor FilterWashable Vent AIR Filter BI-DIRECTIONAL Discharge GrilleBI-MOLDED Condenser Shroud Power Cord for 265-V UnitsSnow Baffle Easy Access to Chassis Temperature Limiter and Control KnobFan Cycle Switch Hidden ControlsEnhanced Copper Tubing Seamless BasepanCondensate Drain Valve Condensate Removal SystemHeat Pumps PAY Their OWN WAY Special FeaturesHow The Heat Pump Works Heat Pump Energy Savings Cooling Electric Premium Zone CapacityOrdering Data 52P and 52C NumberWall Thermostat Control RC,RP FACTORY-INSTALLED Options 52P and 52CCorrosion Protection CP,RP FIELD-INSTALLED Accessories 52P and 52C Wall SleevesInsulated Metal Wall Sleeves Wall Sleeve Molding KitFriedrich and ZoneAire Retro- fit Wall Sleeve Adapter Climate Master Wall Sleeve AdapterFIELD-INSTALLED Accessories 52P and 52C Outdoor GrillesAluminum Architectural Outdoor Grilles Louvered Polymeric Architectural Outdoor Grilles LouveredOutdoor Grille Selection Hardwire KitConduit Interface Kit Subbase Non-electrical subbaseLeveling legs Subbase Power Disconnect SwitchSubbase Fuse Kit Thermostats Digital Programmable ThermostatNon-Programmable Thermostat Manual Changeover Wall ThermostatSpeed Fan Control from Wall Thermostat Wall Thermostat Interface Retrofit KitThermostat Locking Cover Condensate Drain Kit Lateral Duct KitPower Vent with Power Door Kit Lateral Air DeflectorCurtain Deflector Security Door KitReplacement Filters Energy Management KitTypical Wall Installation Dimension Drawings and Installation Data NEW Construction208/230-V Units Dimension Drawings and Installation Data NEW Construction Typical Wall Installation Minimum Clearance for Indoor Outdoor Discharge AIR Typical Lateral Duct Installation 52P and 52C with Subbase Electrical ConnectionsWall Thermostat Connections Product Data 52P Model 52PQ 230/208-1-60Model 52PQ CAPACITY* Btuh52PQ Rev. Cycle 265Product Data 52P Model 52PC and PE 230/208-1-60Model 52PC and PE Product Data 52C Model 52CQ 230/208-1-60Cooling Heating 52CQ Rev. CycModel 52CQ Heating Cooling 52CQ Rev. CycleProduct Data 52C Model 52CE 230/208-1-60Heating† Cooling 52CEModel 52CE 52CE VoltsExpanded Ratings Data 52P and 52C Cooling PerformanceEvaporator entering air temp. 80 F Evap. air 260 CFM Evaporator entering air temp. 80 F Evap. air 350 CFMCooling Sensible Heat Factors SHF AT 80 F Indoor DB Cooling PerformanceEvaporator entering air temp. 80 F Evap. air 320 CFM Indoor Sound Data 52P and 52C Sound Data 52P and 52CSound Transmission Class STC = Wiring Diagrams 52P and 52C SLSWiring Diagrams 52P and 52C ‘R’ 24 VAC Output Power to Wall ‘C’ Common ThermostatPage Wiring Diagrams 52P and 52C Following are recommended wire sizes Maximum Length ftMaster Ptac Unit O C ’STAT Guide Specifications Hvac Guide SpecificationsGuide Specifications Page Typical Warranty CarrierCarrier Corporation Accessory List Accessory Form Number Part Number Description

592-085 specifications

The Carrier 592-085 is a leading-edge commercial air conditioning unit designed to provide efficient cooling solutions for various business environments. Known for its reliability, performance, and advanced technology, the Carrier 592-085 has become a popular choice among facility managers and HVAC professionals alike.

One of the primary features of the Carrier 592-085 is its impressive cooling capacity, which can handle large spaces with ease. The unit operates effectively in various climates, maintaining optimal indoor temperatures even during the hottest summer months. With a cooling capacity rating of 8.5 tons, it can accommodate medium to large commercial spaces, ensuring comfort for employees and customers.

The unit is equipped with advanced inverter technology, which allows it to adjust cooling output based on real-time demand. This not only enhances energy efficiency but also leads to significant cost savings over time. The inverter-driven compressor operates silently, reducing noise levels without compromising on performance.

In addition to its energy-efficient capabilities, the Carrier 592-085 features highly innovative refrigerant management. The unit uses R-410A refrigerant, which is environmentally friendly and contributes to reducing ozone depletion. This makes it an ideal choice for businesses looking to minimize their ecological footprint while maintaining effective cooling.

The Carrier 592-085 also boasts durable construction, with weather-resistant materials designed to withstand harsh external conditions. This ensures longevity and reduces maintenance needs in the long run. The unit's design also includes access panels for convenient servicing, making it easier for technicians to perform routine maintenance and repairs.

Moreover, the Carrier 592-085 is compatible with advanced building management systems, allowing for seamless integration into existing operations. Features such as remote monitoring and control provide users with the flexibility to manage their HVAC systems efficiently, enhancing overall operational efficiency.

In summary, the Carrier 592-085 stands out in the commercial air conditioning market due to its robust performance, energy efficiency, and advanced features. From its inverter technology to eco-friendly refrigerant usage and durable design, this unit provides a comprehensive solution for those seeking reliable cooling in commercial settings. It represents a smart investment for businesses that prioritize both comfort and sustainability.