Carrier 48AJ, 48EW, 48EY024-068, 48AW, 48AY020-060, 48EK, 48AK, 48EJ Thermistor Designations

Page 30

Table 5 — Controls Options and Configurations (Non-Thermostat Applications)

 

UNIT CONFIGURATION

DEFAULT COOLING

DEFAULT HEATING

CV or VAV Unit with SPT Sensor

Unoccupied Cooling — 90 F (32 C) (SPT)

Unoccupied Heating — 55 F (13 C) (SPT)

Occupied Cooling — NA

Occupied Heating — NA

 

 

CV Unit with SPT Sensor and Remote

Unoccupied Cooling — 90 F (32 C) (SPT)

Unoccupied Heating — 55 F (13 C) (SPT)

Start/Stop Switch

Occupied Cooling — 78 F (26 C) (SPT)

Occupied Heating — 68 F (20 C) (SPT)

VAV Unit Remote Start/Stop Switch Only

Unoccupied Cooling — 90 F (32 C)(SPT)

Unoccupied Heating — 55 F (13 C) (RAT)

Occupied Cooling — 55 F (13 C) SPT)

Occupied Heating — 68 F (20 C) (RAT)*

 

 

VAV Unit with SPT Sensor and Remote

Unoccupied Cooling — 90 F (32 C) (SPT)

Unoccupied Heating — 55 F (13C) (SPT)

Start/Stop Switch

Occupied Cooling — 55 F (13 C) (SAT)

Occupied Heating — 68 F (20 C) (RAT)*

 

LEGEND

 

 

CV

Constant Volume

 

 

NA

Not Available

 

 

RAT — Return-Air Temperature

 

 

SAT — Supply-Air Temperature

 

 

SPT

Space Temperature

 

 

VAV

Variable Air Volume

 

 

*With DIP Switch No. 5 configured to OPEN (Occupied Heat Enabled).

NOTE: Space temperature sensor and remote start/stop switch are field-supplied.

STAGED GAS UNIT APPLICATIONS — The rooftop units may be ordered with an optional factory-installed staged gas control system that monitors heating operation of the rooftop unit.

IMPORTANT: An accessory field-supplied Navigator dis- play module is required for all staged gas control units.

Install Supply-Air Thermistors (Staged Gas Units Only)Supply-air thermistors are a field-installed factory-provided component. Three supply-air thermistors are shipped with staged gas units and are inside the heating section. Thermistor wires must be connected to SGC (staged gas controller) in the heating section. See Table 6 and Fig 24. The supply-air ther- mistors should be located in the supply duct with the following criteria:

downstream of the heat exchanger cells

equally spaced as far as possible from the heat exchanger cells

a duct location where none of the supply air thermistors are within sight of the heat exchanger cells

a duct location with good mixed supply air portion of the unit.

THERMISTORS — All units are equipped with a supply air thermistor (SAT) located in the supply fan discharge and an outdoor air thermistor (OAT) located in the outdoor air hood. Variable air volume (VAV) units are supplied with a return air thermistor (RAT) located on the return air damper support.

CONSTANT VOLUME APPLICATIONS — The units, as shipped, are operable as stand-alone units, using either a stan- dard (mechanical or electronic) 2-stage heat, 2-stage cool ther- mostat, or with an electronic room sensor and a timeclock to establish unit start and stop times.

With a standard thermostat (programmable is optional), heating and cooling operation is set by space temperature.

With a space sensor and timeclock, the machine will operate at default values unless they are changed using appropriate in- put devices. The space sensor senses space temperature and may be equipped with a timed override feature, which allows unit operation during unoccupied periods.

The space sensors may be used in multiples of 4 or 9 to achieve space temperature averaging. The use of a space sensor also allows the unit to be turned on and off from a remote signal.

 

 

Table 6 — Thermistor Designations

 

 

 

 

 

 

PIN

FUNCTION AND LOCATION

 

THERMISTOR

CONNECTION

 

PART NO.

Thermistors

 

POINT

 

 

 

 

SAT 1

J8 – 1,2 (SGC)

Supply Air Thermistor (SAT) — Inserted into supply section

 

underneath the gas heat section (factory-provided, field-installed)

 

 

 

 

SAT 2

J8 – 3,4 (SGC)

Supply Air Thermistor (SAT) — Inserted into supply section

HH79NZ016

underneath the gas heat section (factory-provided, field-installed)

 

 

 

SAT 3

J8 – 5,6 (SGC)

Supply Air Thermistor (SAT) — Inserted into supply section

 

underneath the gas heat section (factory-provided, field-installed)

 

 

 

 

30

Image 30
Contents Installation, Start-Up Service Instructions Make Unit Duct Connections Instructions onRoof Curb 48AJ,AK020-030 and 48EJ,EK024-034 Units Roof Curb 48AJ,AK034-050 and 48EJ,EK038-048 Units Roof Curb 48AJ,AK060 and 48EJ,EK054-068 Units Page Base Unit Dimensions 48AJ,AK020-030 Base Unit Dimensions 48AJ,AK035-050 Base Unit Dimensions 48AJ,AK060 Base Unit Dimensions 48AW,AY020-030 Base Unit Dimensions 48AW,AY035-050 Base Unit Dimensions 48W,AY060 Base Unit Dimensions 48EJ,EK024-034 Base Unit Dimensions 48EJ,EK038-048 Base Unit Dimensions 48EJ,EK054-068 Base Unit Dimensions 48EW,EY024-034 Base Unit Dimensions 48EW,EY038-048 Base Unit Dimensions 48EW,EY054-068 AT Each Corner % 48EJ,EW,EK,EYD028 Rigging Weights 48AJ,AK,AW,AY UnitsAT Each Corner % 48EJ,EW,EK,EYD024 48EJ,EW,EK,EYD030Physical Data 48AJ,AK,AW,AY Units Unit 48AJ,AK,AW,AYQuantity Rows...Fins/in Physical Data 48EJ,EK,EW,EY Units Unit 48EJ,EK,EW,EY06D537 06EA250 06EA265 Quantity...Type Ckt 1, Ckt Operating Weights Evaporator Fan Motor Data Air Distribution Thru-the-BottomInstall Flue Hood Combustion Fan Housing Location48A,E Series Staged Gas Implementation Number of Stages Model Number Position Heat Size HtstgtypStages Thermistor Designations Supply-Air Thermistor Connections Indoor Air Quality Sensor Configuration Make Electrical Connections SIO CCNCOM DIPMin Max Unbalanced 3-Phase Supply VoltageElectrical Data 48AJ,AK,AW,AY Units RLA LRAQty 30.8/28.0 180.5/177.7 225/225 236.3/230.9 FLA LRA Electrical Data 48EJ,EK,EW,EY UnitsRange Exhaust FAN Motor MCA Mocp EW,EYFLA LRA MCA Mocp EW,EY 54.0 23.6 41.6 FLA NECRLA Field Power Wiring Connections GND GroundGND CCBEquip IFCOFC Carrier Comfort Network Indoor-Fan Circuit CCN IFC PescIndoor-Fan Relay Terminal Block CCN Connection Approved Shielded Cables Color Code RecommendationsMake Outdoor-Air Inlet Adjustments Space Temperature Averaging WiringAdding Seal Strip to Top of Hood Sides Adding Seal Strip to Sides of Hood Top Mounting Flange Mounting Angle With Tabs Attached to Filter Track Assembly Differential Enthalpy Control and Sensor Psychrometric Chart for Enthalpy Control Control Control Point Curve APPROX. DEGBarometric Relief Damper and Power Exhaust Mounting Details Unit Size 80.5 79.5 48EJ,EK,EW,EY024-054120.5 119.5 48EJ,EK,EW,EY058-068 Motormaster III Sensor Location 48EJ,EK,EW,EY054-064 Field Modifications Side Return Air ConversionSTART-UP Pressure Control Signal VFD SET Point In. wgCarrier Default Program Parameter Values Parameter Group Default ValueMotor Standard Efficiency High Efficiency Typical Factory Wiring Optional Field Wiring Building Pressure Signal Level Open DIP Switch ConfigurationSetting ClosedDIP Switch Factory Settings Fan Performance, 48AJ,AK020-030 Vertical Discharge UnitsAirflow 17,000 Fan Performance, 48AJ,AK035 Vertical Discharge Units16,000 18,00020,000 Fan Performance, 48AJ,AK040,050 Vertical Discharge Units19,000 17,000 18,000 19,000 20,000Fan Performance, 48AJ,AK060 Vertical Discharge Units Fan Performance, 48AW,AY020-030 Horizontal Discharge Units 11,000 12,000 13,000 14,000 15,000Fan Performance, 48AW,AY035 Horizontal Discharge Units 17,000 18,00013,000 14,000 15,000 16,000 17,000 18,000 Fan Performance, 48AW,AY040,050 Horizontal Discharge Units 19,000 20,00016,000 17,000 18,000 19,000 20,000 Fan Performance, 48AW,AY060 Horizontal Discharge Units 26,000 27,000Fan Performance, 48EJ,EK024,034 Vertical Discharge Units Rpm Bhp 000 1066 1096 1125 Fan Performance, 48EJ,EK038,044 Vertical Discharge Units19,000 20,000 Available External Static Pressure in. wg 15,000 16,000 17,000 18,000 19,000 20,000Fan Performance, 48EJ,EK048 Vertical Discharge Units Rpm Bhp000 1086 11.10 1114 11.61 1141 12.14 Fan Performance, 48EJ,EK054-068 Vertical Discharge Units 10,000 949 13.81 970 14.54 990 15.2610,000 956 12.99 976 13.66 996 14.32 Fan Performance, 48EW,EY054-068 Horizontal Discharge Units26,000 27,000 Available External Static Pressure in. wg 20,000 21,000 22,000 23,000 24,000 25,000 26,000 27,000Airflow LOW Speed Medium Speed High Speed ESPMotor Limitations Air Quality LimitsSequence of Operation User Defined Set Points Software Control Link PointsPage Heat Interlock Relay Wiring COM CommonFunction Location Staged Gas System ComponentsStage Gas System Inputs/Outputs Input DescriptionNavigator Display Navigator Display Menu StructureDEG. F Reset Occupied Morning Temperature Software HeatVersion Enabled ConditionField-Supplied Smoke Detector Wiring Device Pressurization Smoke Purge Evacuation Fire Shutdown Smoke Control ModesCooling Capacity Staging Table, CV Units with 2 Compressors StagesService Typical Gas Heating Section Lubrication Manufacturer LubricantEvaporator-Fan Motor Replacement Evaporator Fan Service and ReplacementBelt Tension Adjustment To adjust belt tension Condenser-Fan AdjustmentGas Valve Adjustment Cooling Charging Chart 48EJ,EK,EW,EY024-034Cooling Charging Chart 48EJ,EK,EW,EY054-068 Protective Devices 06D-537 208/230-3-60 Following fan motors have two Voltage WireIndoor Voltage Wire 20 HP 208/230-3-60Typical 48EK VAV 24-V Control Circuit Typical CV 24-V Control Circuit Typical 48EK VAV 115-V Control Circuit Typical 48EJ CV 115-V Control Circuit 101 102 Troubleshooting Typical Refrigerant Circuiting 48AJ,AK,AW,AY027,030 Typical Refrigerant Circuiting 48AJ,AK,AW,AY035 Typical Refrigerant Circuiting 48EJ,EK,EW,EY038,044 Typical Refrigerant Circuiting 48AJ,AK,AW,AY040,050 Typical Refrigerant Circuiting 48EJ,EK,EW,EY048 Typical Refrigerant Circuiting 48EJ,EK,EW,EY054 Typical Refrigerant Circuiting 48AJ,AK,AW,AY060 Typical Refrigerant Circuiting 48EJ,EK,EW,EY064 Typical Refrigerant Circuiting 48EJ,EK,EW,EY068 IGC Control Heating and Cooling IGC Control Board LED Alarms Control Board LED AlarmsTerminal no Assignment O Channel Designations Base Module CVO Channel Designations Base Module VAV IAQService Training START-UP Checklist General
Related manuals
Manual 64 pages 39.75 Kb Manual 36 pages 38.76 Kb

48EJ, 48AJ, 48AK, 48EK, 48AY020-060 specifications

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 are cutting-edge rooftop air conditioning units designed for commercial applications. These models are renowned for their reliability, energy efficiency, and innovative technologies aimed at providing optimal indoor comfort.

One of the standout features of these units is their advanced cooling and heating capabilities. They employ a multi-stage compressor system that allows for precise temperature control, accommodating various load requirements. This flexibility is particularly beneficial in commercial settings where the cooling load can fluctuate throughout the day.

Energy efficiency is paramount in today’s environmental landscape, and Carrier has ensured that these models meet stringent efficiency standards. They incorporate high-efficiency scroll compressors, which significantly reduce energy consumption while delivering powerful performance. The units are also equipped with variable speed fans that adjust airflow based on demand, further optimizing energy use.

In terms of construction, these rooftop units feature a robust design that enhances durability and longevity. The cabinet is constructed to withstand harsh weather conditions, ensuring reliable performance year-round. Additionally, the units are equipped with corrosion-resistant coatings, particularly useful in coastal environments where salt exposure can be a concern.

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY models utilize advanced controls and connectivity features, allowing for easy integration into building management systems. This connectivity enables remote monitoring and control, facilitating quick response to changing conditions and simplifying maintenance tasks.

Noise reduction is another key characteristic of these models. They are designed with sound-absorbing insulation and low-noise fan blades to ensure quiet operation, making them suitable for noise-sensitive environments such as schools and hospitals.

These units are also available with various options for air filtration and dehumidification. The use of high-efficiency air filters enhances indoor air quality by trapping dust, pollen, and other airborne particles. Enhanced dehumidification capabilities ensure that spaces remain comfortable even in humid conditions.

In conclusion, the Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 rooftop units are engineered to offer exceptional performance, energy efficiency, and durability. With their advanced technologies and user-friendly features, they stand out as reliable solutions for meeting diverse commercial cooling and heating needs, making them a popular choice for many businesses.