Carrier 48EJ, 48EW, 48EY024-068, 48AW, 48AY020-060, 48EK, 48AK, 48AJ Supply-Air Thermistor Connections

Page 31

Fig. 24 — Supply-Air Thermistor Connections

Features with Thermostat Control of Unit

two-stage heating

two-stage cooling

control of unit using Y1, Y2, W1, W2, and G thermostat inputs

control of the indoor fan

outdoor-air temperature/supply-air temperature monitoring

control of an outdoor air condenser fan based on out- door-air temperature

control of modulating economizer damper to provide free cooling when outdoor conditions are suitable, using supply-air temperature as a control point

control of the economizer damper and indoor fan to obtain unoccupied free cooling

provide power exhaust output to an external power exhaust controller

support a field test for field checkout

control of 2 stages of CV power exhaust

compressor Time Guard® (power up, minimum off and on times)

compressor lockout during low supply-air temperature

Additional features are provided by accessing the standard unit control board via software with a computer. These features are:

electronic expansion board features (if installed)

control board diagnostics

ability to change supply air set point (economizer control)

ability to change high outdoor temperature lockout set point (economizer control)

ability to change power exhaust set points

NOTE: A CV unit without a thermostat requires a field- supplied sensor for operation.

Features with Sensor Control of Unit (Stand-Alone Applica- tions — Unit control is limited to CV unoccupied default set points, 90 F for cooling, 55 F for heating unless a computer has been used to change the set points. There are 2 sensor options available:

T-55 sensor will monitor room temperature and provide unoccupied override capability (1 hour)

T-56 sensor will monitor room temperature, provide unoccupied override capability (1 hour), and provide a temperature offset of 5° F.

Standard features are:

support of remote occupied/unoccupied input to start and stop the unit

cooling capacity control of 3 stages using economizer and 2 compressors to maintain space temperature to an occupied or unoccupied set point

enable heating or cooling during unoccupied periods as required to maintain space temperature within the unoc- cupied set points

adjustment of space temperature set points of ±5° F when using a T-56 sensor

provides CCN (Carrier Comfort Network) IAQ (Indoor- Air Quality) participation

control of modulating economizer damper to maintain indoor air quality (IAQ) when outdoor conditions are suitable (this function is provided in the base unit con- trols on units with serial number 0600F or later)

NOTE: The IAQ sensor must be set for current output (4 to 20 mA), not voltage output. Ensure the jumper on the sensor is in the upper position. See Fig. 25.

Additional features with sensor control of unit (with com- puter access or Remote Enhanced Display) are:

365-day timeclock with backup (supports minute, hour, day of week, date, month, and year)

daylight savings time function

occupancy control with 8 periods for unit operation

holiday table containing up to 18 holiday schedules

ability to initiate timed override from T-55 or T-56 sen- sors for a timed period of 1 to 4 hours

ability to use multiple space temperature sensors to aver- age the space temperature

supply-air temperature reset for the supply-air tempera- ture set point

temperature compensated start to calculate early start times before occupancy

access to the Display, Maintenance, Configuration, Ser- vice, and Set Point data tables through network software

loadshed and demand limiting

When the unit is equipped with a field-supplied space tem- perature sensor and a remote contact closure (remote start/ stop) on the base control board, the occupied default set points will monitor unit operation. The occupied default set points are 78 F cooling and 68 F heating (if heating is present). See Fig. 26 for remote start/stop wiring.

NOTE: For units with a field-supplied space temperature sen- sor which have not had the base unit control board accessed via software to set an occupancy schedule, the remote start/ stop closure will allow the unit to operate in the pre-configured occupied default set points of 78 F cooling and 68 F heating. Without this feature, the unit will control to the unoccupied default set points of 90 F cooling and 55 F heating.

31

Image 31
Contents Installation, Start-Up Service Instructions Instructions on Make Unit Duct ConnectionsRoof Curb 48AJ,AK020-030 and 48EJ,EK024-034 Units Roof Curb 48AJ,AK034-050 and 48EJ,EK038-048 Units Roof Curb 48AJ,AK060 and 48EJ,EK054-068 Units Page Base Unit Dimensions 48AJ,AK020-030 Base Unit Dimensions 48AJ,AK035-050 Base Unit Dimensions 48AJ,AK060 Base Unit Dimensions 48AW,AY020-030 Base Unit Dimensions 48AW,AY035-050 Base Unit Dimensions 48W,AY060 Base Unit Dimensions 48EJ,EK024-034 Base Unit Dimensions 48EJ,EK038-048 Base Unit Dimensions 48EJ,EK054-068 Base Unit Dimensions 48EW,EY024-034 Base Unit Dimensions 48EW,EY038-048 Base Unit Dimensions 48EW,EY054-068 AT Each Corner % 48EJ,EW,EK,EYD030 Rigging Weights 48AJ,AK,AW,AY UnitsAT Each Corner % 48EJ,EW,EK,EYD024 48EJ,EW,EK,EYD028Unit 48AJ,AK,AW,AY Physical Data 48AJ,AK,AW,AY UnitsQuantity Rows...Fins/in Unit 48EJ,EK,EW,EY Physical Data 48EJ,EK,EW,EY Units06D537 06EA250 06EA265 Quantity...Type Ckt 1, Ckt Operating Weights Air Distribution Thru-the-Bottom Evaporator Fan Motor DataCombustion Fan Housing Location Install Flue HoodNumber of Stages Model Number Position Heat Size Htstgtyp 48A,E Series Staged Gas ImplementationStages Thermistor Designations Supply-Air Thermistor Connections Indoor Air Quality Sensor Configuration Make Electrical Connections DIP CCNCOM SIORLA LRA Unbalanced 3-Phase Supply VoltageElectrical Data 48AJ,AK,AW,AY Units Min MaxQty 30.8/28.0 180.5/177.7 225/225 236.3/230.9 MCA Mocp EW,EY Electrical Data 48EJ,EK,EW,EY UnitsRange Exhaust FAN Motor FLA LRAFLA LRA MCA Mocp EW,EY 54.0 23.6 41.6 NEC FLARLA GND Ground Field Power Wiring ConnectionsIFC CCBEquip GNDOFC CCN IFC Pesc Carrier Comfort Network Indoor-Fan CircuitIndoor-Fan Relay Terminal Block Color Code Recommendations CCN Connection Approved Shielded CablesSpace Temperature Averaging Wiring Make Outdoor-Air Inlet AdjustmentsAdding Seal Strip to Top of Hood Sides Adding Seal Strip to Sides of Hood Top Mounting Flange Mounting Angle With Tabs Attached to Filter Track Assembly Differential Enthalpy Control and Sensor Control Control Point Curve APPROX. DEG Psychrometric Chart for Enthalpy ControlBarometric Relief Damper and Power Exhaust Mounting Details 80.5 79.5 48EJ,EK,EW,EY024-054 Unit Size120.5 119.5 48EJ,EK,EW,EY058-068 Motormaster III Sensor Location 48EJ,EK,EW,EY054-064 Side Return Air Conversion Field ModificationsSTART-UP In. wg Pressure Control Signal VFD SET PointParameter Group Default Value Carrier Default Program Parameter ValuesMotor Standard Efficiency High Efficiency Typical Factory Wiring Optional Field Wiring Building Pressure Signal Level Closed DIP Switch ConfigurationSetting OpenFan Performance, 48AJ,AK020-030 Vertical Discharge Units DIP Switch Factory SettingsAirflow 18,000 Fan Performance, 48AJ,AK035 Vertical Discharge Units16,000 17,00017,000 18,000 19,000 20,000 Fan Performance, 48AJ,AK040,050 Vertical Discharge Units19,000 20,000Fan Performance, 48AJ,AK060 Vertical Discharge Units 11,000 12,000 13,000 14,000 15,000 Fan Performance, 48AW,AY020-030 Horizontal Discharge Units17,000 18,000 Fan Performance, 48AW,AY035 Horizontal Discharge Units13,000 14,000 15,000 16,000 17,000 18,000 19,000 20,000 Fan Performance, 48AW,AY040,050 Horizontal Discharge Units16,000 17,000 18,000 19,000 20,000 26,000 27,000 Fan Performance, 48AW,AY060 Horizontal Discharge UnitsFan Performance, 48EJ,EK024,034 Vertical Discharge Units 15,000 16,000 17,000 18,000 19,000 20,000 Fan Performance, 48EJ,EK038,044 Vertical Discharge Units19,000 20,000 Available External Static Pressure in. wg Rpm Bhp 000 1066 1096 1125Rpm Bhp Fan Performance, 48EJ,EK048 Vertical Discharge Units000 1086 11.10 1114 11.61 1141 12.14 10,000 949 13.81 970 14.54 990 15.26 Fan Performance, 48EJ,EK054-068 Vertical Discharge Units20,000 21,000 22,000 23,000 24,000 25,000 26,000 27,000 Fan Performance, 48EW,EY054-068 Horizontal Discharge Units26,000 27,000 Available External Static Pressure in. wg 10,000 956 12.99 976 13.66 996 14.32ESP Airflow LOW Speed Medium Speed High SpeedAir Quality Limits Motor LimitationsSequence of Operation Software Control Link Points User Defined Set PointsPage COM Common Heat Interlock Relay WiringInput Description Staged Gas System ComponentsStage Gas System Inputs/Outputs Function LocationNavigator Display Menu Structure Navigator DisplayCondition Occupied Morning Temperature Software HeatVersion Enabled DEG. F ResetField-Supplied Smoke Detector Wiring Stages Smoke Control ModesCooling Capacity Staging Table, CV Units with 2 Compressors Device Pressurization Smoke Purge Evacuation Fire ShutdownService Typical Gas Heating Section Manufacturer Lubricant LubricationCondenser-Fan Adjustment Evaporator Fan Service and ReplacementBelt Tension Adjustment To adjust belt tension Evaporator-Fan Motor ReplacementCooling Charging Chart 48EJ,EK,EW,EY024-034 Gas Valve AdjustmentCooling Charging Chart 48EJ,EK,EW,EY054-068 Protective Devices 20 HP 208/230-3-60 Voltage WireIndoor Voltage Wire 06D-537 208/230-3-60 Following fan motors have twoTypical 48EK VAV 24-V Control Circuit Typical CV 24-V Control Circuit Typical 48EK VAV 115-V Control Circuit Typical 48EJ CV 115-V Control Circuit 101 102 Troubleshooting Typical Refrigerant Circuiting 48AJ,AK,AW,AY027,030 Typical Refrigerant Circuiting 48AJ,AK,AW,AY035 Typical Refrigerant Circuiting 48EJ,EK,EW,EY038,044 Typical Refrigerant Circuiting 48AJ,AK,AW,AY040,050 Typical Refrigerant Circuiting 48EJ,EK,EW,EY048 Typical Refrigerant Circuiting 48EJ,EK,EW,EY054 Typical Refrigerant Circuiting 48AJ,AK,AW,AY060 Typical Refrigerant Circuiting 48EJ,EK,EW,EY064 Typical Refrigerant Circuiting 48EJ,EK,EW,EY068 IGC Control Heating and Cooling Control Board LED Alarms IGC Control Board LED AlarmsIAQ O Channel Designations Base Module CVO Channel Designations Base Module VAV Terminal no AssignmentService Training START-UP Checklist General
Related manuals
Manual 64 pages 39.75 Kb Manual 36 pages 38.76 Kb

48EJ, 48AJ, 48AK, 48EK, 48AY020-060 specifications

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 are cutting-edge rooftop air conditioning units designed for commercial applications. These models are renowned for their reliability, energy efficiency, and innovative technologies aimed at providing optimal indoor comfort.

One of the standout features of these units is their advanced cooling and heating capabilities. They employ a multi-stage compressor system that allows for precise temperature control, accommodating various load requirements. This flexibility is particularly beneficial in commercial settings where the cooling load can fluctuate throughout the day.

Energy efficiency is paramount in today’s environmental landscape, and Carrier has ensured that these models meet stringent efficiency standards. They incorporate high-efficiency scroll compressors, which significantly reduce energy consumption while delivering powerful performance. The units are also equipped with variable speed fans that adjust airflow based on demand, further optimizing energy use.

In terms of construction, these rooftop units feature a robust design that enhances durability and longevity. The cabinet is constructed to withstand harsh weather conditions, ensuring reliable performance year-round. Additionally, the units are equipped with corrosion-resistant coatings, particularly useful in coastal environments where salt exposure can be a concern.

The Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY models utilize advanced controls and connectivity features, allowing for easy integration into building management systems. This connectivity enables remote monitoring and control, facilitating quick response to changing conditions and simplifying maintenance tasks.

Noise reduction is another key characteristic of these models. They are designed with sound-absorbing insulation and low-noise fan blades to ensure quiet operation, making them suitable for noise-sensitive environments such as schools and hospitals.

These units are also available with various options for air filtration and dehumidification. The use of high-efficiency air filters enhances indoor air quality by trapping dust, pollen, and other airborne particles. Enhanced dehumidification capabilities ensure that spaces remain comfortable even in humid conditions.

In conclusion, the Carrier 48EJ, 48AW, 48EK, 48AJ, and 48EY024-068 rooftop units are engineered to offer exceptional performance, energy efficiency, and durability. With their advanced technologies and user-friendly features, they stand out as reliable solutions for meeting diverse commercial cooling and heating needs, making them a popular choice for many businesses.